Part 2: Overview of display values and settings Expert area
19
HS2 Type (second heat generator type => A7)
(For HS1 with 2-stage burner – not active)
00 = No secondary heat generator
01 = Single stage HS switching
08 = Cooling 1
20 = Solid fuel integration
(additional non-controllable HS)
for switching behaviour, see parameter HS2 storage
21 = Collector pump
22 = Pump for HS1
(e.g. additional HS for cascades)
Storage HS2 (heat accumulator for HS2)
(Only where HS2 Type = Solid fuel)
Warm-up relief applies superordinated:
ON: T-HS2 > Min T-HS2
OFF: T-HS2 < [Min T-HS2 – 5K]
T-HS2 = Solid fuel burner temperature
00 = Heating vis-à-vis collector (no storage tank) => F8
ON: T-HS2 > [F8 + Hyst Burner 2 + 5K]
OFF: T-HS2 < [F8 + Hyst Burner 2]
01 = Heating vis-à-vis buffer storage tank => F1, F3
ON: T-HS2 > [F3 + Hyst Burner 2 + 5K]
OFF: T-HS2 < [F1 + Hyst Burner 2]
02 = Heating vis-à-vis HW tank => F6
ON: T-HS2 > [F6 + Hyst Burner 2 + 5K]
OFF: T-HS2 < [F6 + Hyst Burner 2]
03 = Heating vis-à-vis STORAGE III (Pool) => F15
ON: T-HS2 > [F15 + Hyst Burner 2 + 5K]
OFF: T-HS2 < [F15 + Hyst Burner 2]
Switching pattern
The pump is switched on if the temperature of the solid
fuel boiler exceeds the temperature of the Reference
sensor by the hysteresis (Hyst Burner 2 + 5K). Switching
off occurs when the temperature drops 5K below the
switch-on temperature.
Warm up Temp
Switching off occurs when the temperature of the solid
fuel boiler drops below the set limit temperature
(Min T-HS2) by 5K. The pump is enabled again when the
temperature of the solid fuel boiler exceeds the set limit
temperature (Min T-HS2).
Buffer type (heater buffer storage type)
!After activation (01 or 02) it is not possible to
connect a FBR for heatcircuit 1.
00 = no buffer storage for heating operation
01 = Buffer storage for heating operation (F2, F3)
HS1 is activated with reference to sensor "buffer top" (F3)
DHW Relief operates on sensor "buffer top".
HW charge pump ON:
"Upper buffer" > HWactual + 5K Hysteresis
HW charge pump OFF:
"Upper buffer" < HWactual
02 = Combination storage tank for heating and HW
operation
HS1 is activated with reference to sensor "buffer middle"
(F2)
DHW Relief operates on boiler sensor BS.
HW charge pump ON:
BS > HWactual + 5K Hysteresis
HW charge pump OFF:
BS < HWactual
03 = passive buffer storage for heating operation (F1, F3)
The buffer will not load by the conventional Heat
generator producers. The use occurs, e.g., through solar
buffer loading [Buffer charging pump], [return flow
temperature increase] or [transfer pump for buffer
storage] (sensor usable).
In this attitude no change of the regulation of the heating
takes place in relation to the without buffers
Cool Operation (Space cooling via operating mode)
The mode of operation cooling and the necessary
settings are released. In the mode of operation cooling
the heating circles can be used for the cooling of the
room. For this function a refrigerating machine is
necessary.
F15 function (sensor function for F15)
00 = Room sensor for heatcircuit 2. if a further sensor at
the pulse input [IMP = F17] is detected at this position, an
FBR is evaluated at F15 and F17. If F17 is used by a
different function, an RFB is evaluated at F15.
01 = 0-10V input for presetting an external collector set
temperature. On evaluation see Parameter [V-Curve] in
the “Expert/0-10V I/O”-level.
02 = Light sensor => without function
03 = 0...10V input for presetting an external modulation
depth. On evaluation see Parameter [V-Curve] in the
“Expert/0-10V I/O”-level.
! The internal determination of the burner
requirement is deactivated when this function is
used.
! It is exclusively the target set via the 0-10V output
that applies. Any changes, such as those relating
to external heating circuits, hot water preparation
or the frost protection function are ignored. The
operating mode switch also has no effect on the
burner requirement, only on the internal and
external determination of requirement and
distribution.
04 = secondary sensor for MF function
05 = storage tank 3 (e.g. pool)