DESICCANT CONTROLLER OPTIONS
1 On POWERUP shows program version (DD01v01) for 10 sec then shows PRESS ON .
2 Enter TECH MODE (TM) anytime. Press 2+3. To turn enabled optional features ON or OFF.
3 Enter FACTORY MODE (FM) only when OFF. Press 2 then 5 then 3. To enable option features . New controls (July, 2009 and newer) press 2&5 in order to enter FACTORY MODE.
4 Press OFF to execute 30 sec SHUTDOWN SEQUENCE, opens inlet valves, closes purge valves.
5 Press "i" 5 sec to set time, see inputs and outputs. Press "i" several times to exit.
6 Press SELECT DISPLAY to move to next screen.
7 Press ENT (if displayed) to move to alternate screen, such as ALARMS or % TIME.
8 Press BLANK KEY to go back one screen in Customer Mode.
9 Press BLANK KEY at BEGIN TECH MODE to go back to Customer Mode.
10 Press BLANK KEY at BEGIN FACTORY MODE to go back to Customer Mode.
11 Main Displays are RT DRY LT REGEN and STEP 4 TIME 10300 (sec)
12 ALARM LIST; ENT to see last 20 ALARMS, DATE (dd;mm) and TIMES (hh:mm)
13 OPERATING TIMES; ENT to see Operating Hours; No purge hours; Heater Hours
14 If OFF, hit OFF to get back to PRESS ON
Dryer Type DPC Display
FEATURE NAME HL EH HB CUSTOMER Tec Mode Factory Mode ADD HDWRE DESCRIPTION
1 PDP ADJUSTER : -40, -4, 40 std no yes no none Changes cycle length to
change dewpoint; 16 m for -4;
24 m for +40
2 Restart: ZERO or AT FAIL std std std no yes no none On power fail, restart at
beginning (zero) or where
failed.
3 PURGE ADJUST, % Purge Select std no Select % no none Match length of purge to
compressor output.
4 Fail To Shift (FTS) opt opt opt FTS Alarm no yes Pressure switches Alarm if incorrect pressures at
steps 1,4,15,18
5 Dewpoint Temp opt opt opt HH Alarm;
Dewpoint
On/Off; set Select DEW TRANS Dew trans: -100
only plus cell.
Display dewpoint and hi
humidity alarm
6 EMS opt opt opt NO PURGE On/Off; set BRD or DEW
TRANS
DEWTRANS HTLS - midpoint bed with
board; HTD - outlet with
DEWTRANS
7 Hi Humidity (HH) opt opt opt HH Alarm On/Off; set BRD or DEW
TRANS
DEWTRANS Measure outlet dewpoint;
alarm if high
8 COMPRESSOR INTERLOCK std NO PURGE On/Off Enable none Close purge valve when
compressor unloads and
current purge finishes
9 -100 opt opt opt no yes Enable Repress line;
25% Mol Sieve
4 minute NEMA Cycle
10 Primary Operating Mode: HTLS std no yes Select HTLS Heatless cycle
11 Primary Operating Mode: HTD std no yes Select HTD Heated Cycle
12 Primary Operating Mode: BLWR std no yes Select BLWR Blower Cycle
13 High Outlet Temp Alarm (HOT) opt opt On Alarm On/Off; set Enable Thermistor in outlet Display alalrm on high outlet
temp
14 Power Saver (PSV)
(EMS)
opt opt No Purge On/Off Enable; Set Purge out
connection,
thermistor
Terminate purge when heat
comes through bed
15 Cool Sweep opt no On/Off Enable Purge line Add 1 hour of dry purge to
cooldown
16 Dual Mode std std no Select mode Enable none Standard with HTD or BLWR
17 Extended Heating (EXT HTG) opt opt no On/Off Enable DP TRANS plus
PWR SAVER
Extends heating for new dryers
with MLC and PWR Saver
18 PID Heater Control std std HTR Temp HTR Temp
Setpoint
P=200; I = 50; D=
10; PWM = 120
none Smooth operating heater
control
Bergh Desiccant DPC
Cheatsheet_IR Data.xls