INSTALLATION, USE AND MAINTENANCE MANUAL
DUCTO MULTI
The integrated multi-zone ductable fancoil
DUCTO MULTI - MULTI-ZONE DUCTABLE FANCOIL

Innova Srl
Page 2
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
INDEX
1GENERALITY ...................................................................................................................................................................................... 4
1.1 INTRODUCTION ....................................................................................................................................................................... 4
1.2 BASIC SAFETY RULES .............................................................................................................................................................. 4
1.3 SYMBOLOGY ............................................................................................................................................................................ 5
1.4 WARNINGS .............................................................................................................................................................................. 5
1.5 COMPLIANCE ........................................................................................................................................................................... 6
1.6 RANGE ..................................................................................................................................................................................... 7
1.7 IDENTIFICATION ..................................................................................................................................................................... 7
1.8 DELIVERY STATE....................................................................................................................................................................... 7
1.11 START-UP REQUIREMENTS ................................................................................................................................................ 8
1.10 DISASSEMBLY AND DISPOSAL ........................................................................................................................................... 8
1.11 MAIN COMPONENTS UNITS ................................................................................................................................................ 8
1.12 DIMENSIONAL ..................................................................................................................................................................... 9
2INSTALLATION ................................................................................................................................................................................... 9
2.1 INSTALLATION CONDITIONS ................................................................................................................................................ 10
2.2 UNIT POSITIONING ................................................................................................................................................................ 10
2.3 CONDENSATE DRAIN CONNECTION .................................................................................................................................... 11
3AERAULIC CONNECTIONS................................................................................................................................................................ 12
3.1 AERAULIC CONNECTIONS .................................................................................................................................................... 12
3.2 AERAULIC CONNECTIONS WITH ACCESSORIES...................................................................................................................... 13
4HYDRAULIC CONNECTIONS ............................................................................................................................................................. 14
4.1 GENERALITY........................................................................................................................................................................... 14
4.2 POSITIONING AND CONNECTION PROCEDURES ................................................................................................................... 15
4.3 3-WAY VALVE CONNECTION.................................................................................................................................................. 16
5ELECTRICAL CONNECTIONS............................................................................................................................................................. 17
5.1 GENERALITY........................................................................................................................................................................... 17

Innova Srl
Page 3
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
5.2 POSITIONING AND CONNECTION PROCEDURES ................................................................................................................... 17
5.3 S VERSION UNIT WIRING DIAGRAMS - (command 0-10vdc) ................................................................................................. 18
5.4 ELECTRICAL DIAGRAMS OF UNIT VERSION I.......................................................................................................................... 19
5.5 ELECTRICAL CONNECTIONS VERSION -S-............................................................................................................................... 21
5.6 ELECTRICAL CONNECTIONS VERSION -I-................................................................................................................................ 22
6COMMISSIONING AND METHOD OF USE ....................................................................................................................................... 27
6.1 OPERATION VERSION –S- ...................................................................................................................................................... 27
6.2 OPERATION VERSION -I- ........................................................................................................................................................ 27
6.3 TURNING THE UNIT ON AND OFF.......................................................................................................................................... 28
6.4 MODIFICATION OF FANS SPEED AND BOOSTER FUNCTION.................................................................................................. 28
6.5 AUTO FUNCTION ................................................................................................................................................................... 28
6.6 CHANGE OF SEASON.............................................................................................................................................................. 28
6.7 KEY LOCK................................................................................................................................................................................ 29
6.8 PANEL BRIGHTNESS ADJUSTMENT ........................................................................................................................................ 29
7MAINTENANCE................................................................................................................................................................................ 30
7.1 CLEANING OR REPLACING FILTERS ........................................................................................................................................ 30
7.2 GENERAL CLEANING OF THE UNIT......................................................................................................................................... 31
8ALARMS........................................................................................................................................................................................... 32
8.1 GENERALITY........................................................................................................................................................................... 32
8.2 PROBLEMS WITHOUT ERROR INDICATION ON THE DISPLAY ................................................................................................ 32
8.3 ALARM SIGNAL ...................................................................................................................................................................... 32
8.4 TABLE OF ALARMS SIGNALED BY DISPLAY - VERSIONS I -...................................................................................................... 33
9NOTES AND INFORMATION MAINTENANCE................................................................................................................................... 34
NOTE ............................................................................................................................................................................................... 34

Innova Srl
Page 4
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
1GENERALITY
1.1 INTRODUCTION
This manual has been conceived with the aim of making the installation and management of your system as simple as possible.
By reading and applying the suggestions in this manual, you will be able to get the best performance from the product you have purchased.
We would like to thank you for the choice you made with the purchase of our product.
Read this booklet carefully before carrying out any operation on the unit.
You must not install the unit or carry out any work on it if you have not carefully read and understood this manual in all its parts. In
particular, all the precautions listed in the manual must be taken.
The documentation accompanying the unit must be delivered to the plant manager so that he can keep it carefully (at least 10 years) for
any future assistance, maintenance and repairs.
The installation of the unit must take into account both the purely technical requirements for proper functioning, and any local legislation in
force and specific prescriptions.
Make sure that upon delivery of the unit, there are no obvious signs of damage caused by transportation. In this case indicate it on the
delivery note.
This manual reflects the state of the art at the time the machine was marketed and cannot be considered inadequate as it is subsequently
updated on the basis of new experiences. The Manufacturer reserves the right to update the production and the manuals, without the
obligation to update the previous ones, except in exceptional cases.
Contact the Manufacturer's Sales Department to receive further information or updates to the technical documentation and for any
improvement proposals to this manual. All reports received will be rigorously examined.
1.2 BASIC SAFETY RULES
We remind you that the use of products that use electricity and water implies the observance of some fundamental safety rules:
•The use of the appliance by disabled and unassisted people is prohibited.
•It is forbidden to touch the appliance with bare feet and with wet or humid peers of the body.
•Any cleaning operation is forbidden before disconnecting the appliance from the power supply by turning the main switch of the
system to off.
•It is forbidden to modify the safety or adjustment devices without the authorization and indications of the manufacturer of the
appliance.
•It is forbidden to pull, disconnect or twist the electric cables coming out of the appliance, even if it is disconnected from the mains
electricity supply.
•It is forbidden to introduce objects and substances through the air intake and delivery grilles.
•It is forbidden to open the access doors to the internal parts of the appliance without first setting the system main switch to off.
•It is forbidden to disperse and leave the packaging material within the reach of children as it can be a potential source of danger.
•Respect the safety distances between the machine and other equipment or structures to ensure sufficient access space to the unit
for maintenance and assistance operations as indicated in this booklet.
•The unit must be powered with electric cables with a section suitable for the power of the unit. The voltage and frequency values
must correspond to those indicated for the respective machines; all the machines must be earthed as per the regulations in force
in the various countries.

Innova Srl
Page 5
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
1.3 SYMBOLOGY
The symbols shown in the following booklet allow you to quickly provide information necessary for the correct use of the unit.
Safety symbols
ATTENTION
Only authorized personnel Warns that the operations indicated are important for the safe operation of the machines
DANGER
Risk of electric shock Warns you that failure to comply with the prescriptions creates a risk of electric shock.
DANGER Warns that failure to comply with the prescriptions entails a risk of harm to exposed persons.
WARNING Warns that failure to comply with the prescriptions entails a risk of damage to the unit or to the
system.
DANGER It warns that there is the presence of moving parts and involves a risk of damage to exposed people
1.4 WARNINGS
The unit must be installed by qualified and authorized personnel according to the regulations in force in the various countries.
If the installation is not carried out it could become a dangerous situation
Avoid installing the unit in very humid rooms or with large heat sources.
On the electrical side, to prevent any risk of electrocution, it is essential to disconnect the main switch before carrying out
electrical connections and all maintenance operations.
In the event of water leaks inside the unit, set the main system switch to "Off", close the taps of the
water and contact the technical service
It is recommended to use a dedicated power supply circuit; Never use a common power supply with other appliances.

Innova Srl
Page 6
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
It is recommended to install an earth leakage breaker; Failure to install this device may cause shock electric.
For connection, use a cable that is long enough to cover the entire distance, without any connection; do not use extension cords and
do not apply other loads to the power supply but use a dedicated power circuit.
After connecting the electrical cables, make sure that the cables are arranged so as not to exert excessive forces on the covers or
electrical panels; any incomplete connection of the covers can cause overheating of the terminals.
Make sure that the earth connection is made; do not ground the appliance on distribution pipes.
Momentary surges of high intensity could damage the unit
Installations performed outside the warnings in this manual or use outside the operating limits will instantly void the warranty.
Make sure that the first start-up is carried out by personnel authorized by the company (see first start-up request form)
1.5 COMPLIANCE
The CE marking (present on each machine) certifies compliance with the following Community standards:
•Low Voltage Directive 2014/35 / EC
•Electromagnetic Compatibility Directive 2014/30 / EC
•RoHS2 2011/65 / EU
•WEEE 2012/19 / EC

Innova Srl
Page 7
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
1.6 RANGE
-1- -2- -3-
SLC + 600 H I
(1) Defines the size
600 = 2 fans
800 = 3 fans
1000 = 4 fans
1200 = 5 fans
2) Type of installation
H: horizontal
3) Electronic type
S: With 0-10v dc control signal for single fan
I: Version with electronics and EC motors for single zone
1.7 IDENTIFICATION
-The unit is identifiable through the plate placed on the lower front panel of the same.
- On the packaging there will be an additional identification plate with the model of the unit and the shipping references.
-The plate on the packaging has no validity for the traceability of the product in the years following the sale.
The removal, deterioration and illegibility of the plate placed on the unit involves major problems in identifying the machine, in the
availability of spare parts and therefore in any future maintenance.
1.8 DELIVERY STATE
The supply includes:
•Air handling unit
•Coarse class filters pre-inserted inside the unit;
•Electrical box with provision for connection terminal block;
•Side condensate drain connections
•Side inlet and outlet water connections
•Labels / stickers (safety pictograms, channel identification, CE marking ...) already positioned on the unit.
•Installation, use and maintenance manual

Innova Srl
Page 8
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
1.11 START-UP REQUIREMENTS
Before starting, make sure that there are no foreign bodies inside the unit.
Check the fastening of the closing panels and inspection doors.
If there are no channels installed on the aeraulic sockets, install an adequate protection net.
Check the power supply and grounding of the unit.
1.10 DISASSEMBLY AND DISPOSAL
Do not disassemble or dispose of the product yourself. Disassembly, demolition, disposal of the product must be carried out by authorized
personnel in compliance with local regulations.
1.11 MAIN COMPONENTS UNITS
The main components of the unit are described below in order to understand the layout and characteristics of the machine.
1 Fan
2 Hydronic battery
3 Filter
4 Electrical connection box
5 Hydraulic connections
6 Condensate drain

Innova Srl
Page 9
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
1.12 DIMENSIONAL
SLC +
600 800 1000 1200
DIM SIZE 2 SIZE 3 SIZE 4 SIZE 5
TO mm 790 990 1190 1480
B. mm 750 950 1150 1440
C. mm 240 240 240 240
D. mm 695 695 695 695
AND mm 770 970 1170 1460
F. mm 637 637 637 637
G. mm 373 316 287 287
H. mm 90 90 90 90
DN mm 160 160 160 160
IN WATER 1 3/4 "F 3/4 "F 3/4 "F 3/4 "F
OUT WATER 2 3/4 "F 3/4 "F 3/4 "F 3/4 "F
EXHAUST H 3 mm Ø 20 Ø 20 Ø 20 Ø 20
QE No. 2 3 4 5

Innova Srl
Page 10
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
2INSTALLATION
2.1 INSTALLATION CONDITIONS
The unit must be installed according to national and local standards that regulate the use of electrical devices and according to the following
indications:
•install the unit inside residential buildings with an ambient temperature between 3 ° C and 45 ° C;
•avoid areas near sources of heat, steam, flammable and / or explosive gases and particularly dusty areas;
•install the unit in a place not subject to frost (the condensation water must be drained not frozen, at a certain inclination, using a
siphon;
•do not install the unit in areas with a high relative humidity rate (such as a bathroom or toilet) to avoid condensation on the
external surface;
•choose an installation site where there is sufficient space around the unit for the connections of the air ducts and to be able to
carry out maintenance operations;
•the consistency of the ceiling / wall / floor where the unit will be installed must be adequate for the weight of the unit and not
cause vibrations.
The environment chosen for the installation must contain:
•connections of the air ducts;
•230 V single-phase electrical connection
•connection for condensate drain
•water inlet and outlet water connection
2.2 UNIT POSITIONING
Ceiling mount
To mount the unit on the ceiling, you need:
•Use the 4 mounting holes on the top of the unit.
•Fix the unit to the ceiling, using the brackets, using
suitable anchoring systems (dowels, threaded bars,
chains…) and check the leveling with the help of a
level.
•Ensure sufficient space for carrying out
maintenance activities: the opening of the unit
cover (from below) and accessibility to the
electrical box and to the hydraulic connections
must be guaranteed;

Innova Srl
Page 11
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
Do not mount the unit with sides or surfaces in direct
contact with the walls to avoid possible contact noises,
insert rubber or neoprene strips in this case.
Ceiling mount
2.3 CONDENSATE DRAIN CONNECTION
For the heat recovery unit to function correctly, a condensate drain must be connected to the plumbing system (drain) of the house.
Furthermore, to allow the condensate water to flow correctly and avoid unpleasant odors, the condensate drain must always be equipped
with the appropriate siphon to be placed on the drain line by the installer;
To install the condensate drain, comply with the following
standards:
•give a slope of at least 2% to the exhaust pipe;
•provide for the possibility of disconnecting the drain
hose for any maintenance (in particular in the case of
ceiling installation);
•make sure that the discharge end of the pipe is at
least below the water level of the siphon;
•make sure that the siphon is always full of water.
In horizontal positioning the drain is 18 mm in diameter;
Horizontal installation drain

Innova Srl
Page 12
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
3AERAULIC CONNECTIONS
3.1 AERAULIC CONNECTIONS
The unit is equipped with circular male connections for the air delivery part which correspond to each zone;
On the other hand, a rectangular outlet is provided for the part of the room return air located on the rear side of the unit;
For the correct connection of the air ducts, refer to the following diagram and the stickers placed on the unit.
Horizontal installation
The configurations for the aeraulic flows
and connections are indicated on the side:
A- Air delivery
B- Air intake
Aeraulic attacks
Air delivery and return dimensions table
SLC +
600
800
1000
1200
A Base Delivery x Height mm
2 x 160 mm
3 x 160 mm
4x160 mm
5x160 mm
B Base recovery x Height mm
630x143 mm
830x143 mm
1030x143 mm
1317x143 mm
We recommend installing at least 500 mm of flexible piping to avoid entrainment of vibrations and annoying noises due to installation

Innova Srl
Page 13
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
3.2 AERAULIC CONNECTIONS WITH ACCESSORIES
Accessories are provided to facilitate the
installation of the ducts;
The available accessories are:
- D - Return plenum with circular inlets
3
Aeraulic attacks
Air delivery and return dimensions table with accessories
SLC +
600
800
1000
1200
D. Return Plenum Number of connections / Diameter mm
2 x 160 mm
3 x 160 mm
4x160 mm
5x160 mm

Innova Srl
Page 14
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
4HYDRAULIC CONNECTIONS
4.1 GENERALITY
The units are equipped with hydronic coils with water-air exchange;
-The connections on the units, even in the different applications and versions, are always common to all the units.
-Make sure to respect the flows indicated on the labels: inlet (water entering the unit), outlet (water leaving the unit)
- Make sure that the weight of the pipes does not weigh on the predisposed connections
-Provide shut-off valves on the delivery and return pipes to the system
-All the chilled water pipes must be insulated to minimize unwanted heat exchanges and the formation of condensation.
- Before filling the pipes, make sure that they do not contain foreign materials: such as sand, stones, rust flakes, welding drops, slag, etc.
Otherwise, wash the hydraulic circuit by bypassing the unit.
- Absolutely avoid pump cavitation and the consequent presence of air in the hydraulic circuit.
Physico-chemical characteristics of water
Incompatible chemical-physical characteristics could compromise the integrity of the hydraulic parts of the unit.
Check the characteristics of the water:
DESCRIPTION
Limit value
Hardness
<10 ° F
PH value
7.5 / 9
Oxygen
<2 mg / l
Conductivity
<500 uS / cm
Iron
<2 mg / l
Manganese
<1 mg / l
Nitrate
<70 mg / l
Sulphate
<70 mg / l
Chlorine compounds
<300 mg / l
Free radical carbon dioxide
<10 mg / l
Ammonium
<20 mg / l

Innova Srl
Page 15
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
4.2 POSITIONING AND CONNECTION PROCEDURES
The hydraulic connections are located on the side of the
unit.
The connections are with Eurokonus ¾ ”male thread.
Respect IN as the water inlet to the
unit and OUT as the
water outlet from the unit.
Connect the pipes with a Eurokonus threaded fitting and
tighten it with dedicated tools;
The external thread is connected through a swivel fitting to
the battery to prevent rotation in the tightening
from
damaging the internal pipes;
In any case, be careful not to rotate or twist the pipes
coming from inside the unit;
Rotating the pipes during connection could damage the
connections inside the unit and cause water leaks during
operation;

Innova Srl
Page 16
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
4.3 3-WAY VALVE CONNECTION
2 and 3-way valve groups are available as
accessories for connection to the outside of the unit.
The groups are supplied as a kit to be assembled
and contain all the fittings to facilitate the
connection to the installer.
3-way valve group kit
Two-way valve assembly kit

Innova Srl
Page 17
N420740A _manuale-
SLC+ 2022
multi_EN_Rev.01.docx
5ELECTRICAL CONNECTIONS
5.1 GENERALITY
- Before starting any operation to make the electrical connection make sure that the unit is not electrically powered
- Make the necessary electrical connections by consulting only the wiring diagram attached to this manual.
- Install a suitable breaking device and differential protection for the exclusive service of the unit.
- IS it is essential that the unit is connected to an earth socket.
- Check that the electrical components chosen for the installation (main switch, circuit breakers, cable section and terminals) are suitable for
the electrical power of the installed unit and that they take into account the starting currents of the compressor as well as the maximum
load that can be reached. The relative data are indicated on the attached wiring diagram and on the unit identification plate
- IS It is forbidden to enter the unit with electric cables unless specified in this booklet.
- Use cables and electrical conductors with adequate sections and in compliance with the regulations in force in the various countries.
- Absolutely avoid running electrical cables in direct contact with pipes or components inside the unit
- After the first few moments of operation, check the tightening of the screws of the power supply terminals
Power line sizing table:
SLC+
600
800
1000
1200
Diet
V / Ph / Hz
230/1/50
Max absorbed power
kW 0.19 0.28 0.37 0.46
Max absorbed current
TO
0.7
1.4
2.1
2.8
5.2 POSITIONING AND CONNECTION PROCEDURES
On the side of the unit there are the electrical
boxes for the electrical connections of each single
output, while inside the box there are the cable
clamps and the screws supplied.
Electrical connections

Innova Srl
Page 18
N420740A _manuale-SLC+ 202
2
multi_EN_Rev.01.docx
5.3 S VERSION UNIT WIRING DIAGRAMS - (0-10V DC COMMAND)
General wiring diagram S versions
Wiring diagram for single zone S versions
CONNECTIONS BY THE CUSTOMER
L - N - PE
Power supply 230/1/50
Check power in the previous tables
10v Reference voltage signal Voltage supplied by the motor
(I max = 20ma)
Y
0-10v dc signal to the zone motor
Gnd
Reference signal

Innova Srl
Page 19
N420740A _manuale-SLC+ 202
2
multi_EN_Rev.01.docx
5.4 ELECTRICAL DIAGRAMS OF UNIT VERSION I
General wiring diagram I versions
NB: The connection must be of the "in-out" type and not "star" or "tree".

Innova Srl
Page 20
N420740A _manuale-SLC+ 202
2
multi_EN_Rev.01.docx
Wiring diagram I versions
CONNECTIONS BY THE CUSTOMER
LN-PE
Power supply 230v / 1/50
In parallel with the other areas
GRID
Window contact
Contact closed / Unit on
CP
Contact presence
Contact closed / unit off
CHILLER Generator / pump consent
Clean Contact
(cold request activation)
BOILER Generator / pump consent
Clean Contact
(hot request activation)
WATER VALVE (N-EV1) Water valve
Live contact (230 V)
In parallel with the other areas
REMOTE DISPLAY
Remote control (4 wires)
REMOTE ON OFF (ON
DISPLAY)
Remote ON OFF contact present on remote display Contact closed / unit OFF
Table of contents
Other Innova Fan manuals
Popular Fan manuals by other brands

CONSTRUCTA
CONSTRUCTA Tumble dryer installation instructions