Intelight OXIMIA LED User manual

RECOMMENDED PERIODICAL MAINTENANCE
The lighting fitting should be tested on regular basis in accordance with valid laws and regulations. The results of
the tests should be recorded and stored for the use of a fire safety inspector.
One time daily
It has to be visually checked if the LED indicator in the lighting fitting lights up green.
One time each month
It is necessary to disconnect the AC power supply for 3 seconds and check whether the lamp is operating in
emergency mode - the green LED indicator turns off, and 12 white LEDs light up.
One time each year
Disconnect the AC power supply and test if the lamp operates in emergency mode for a specified time. If the
time of emergency operation is not sufficient, the battery needs to be fully recharged and the test is to be
carried out again. If the result of the test continues to be negative, the battery needs to be replaced.
CAUTION!
All damage that may occur as a result of the device being used contrary to this instruction will result in loss of
guarantee. The guarantee shall not cover the light source and batteries.
Handling of o solete equipment
Pursuant to the Act of 29 July 2 5 on
waste electrical and electronic
equipment and the Act of 24 April 2 9
on batteries and accumulators, the
presented device, after use, due to
hazardous substances contained in it, is
subject to collection of waste electrical
and electronic equipment. Detailed
information on WEEE collection can be
obtained from municipal authorities.
Intelight Sp. z o.o.
8, Rydygiera str.
01 -793 Warsaw
Poland
KTM 97131 - nstruction Oximia, EN, ver.20161024
OXIMIA LED EMERGENCY LIGHTING FITTING
nstallation and maintenance instructions
TECHNICAL SPECIFICATIONS:
Light source
(
non
-
replaceable
)
:
White LED
Operating modes:
SA
(
M
)
-
mains and emergency operation or
A (NM) - emergency operation
E
mergency operation duration:
3 hours
Battery
(
non
-
replaceable
)
:
Ni
-
Cd 8 mAH / 3.6V
Battery charging duration:
24h
Power supply:
22
-
24 V AC 5 Hz
Max. power:
3W
Module:
Oximia LED
Visibility:
3 metres
Enclosure IP rating:
IP2
INTRODUCTION
1. The lamp should be installed when power supply is off. Safety rules, construction and electrical installation
standards should be observed at all times.
2. The lighting fitting should not be powered with circuits connected to inductive power-receiving devices at
the same time. This type of solution may cause damage to the electronic module of the lighting fitting.
3. The lighting fitting should be used indoors.

INSTALLATION
1. Before installation one has to make sure that the lighting fitting will be connected to 22 -24 VAC power
supply by the use of minimum a 1.5mm2 wire.
2. The lighting fitting is designed for mains and emergency operation and appropriate wiring connection is
required for its correct operation.
- Brown insulation colour - phase wire (Lch terminal) is to be connected with the mains phase wire,
- Blue insulation colour - neutral wire (N terminal) is to be connected with the mains neutral wire
- Yellow and green insulation colour - protective earth wire (PE terminal) is to be connected with the
protective earth mains wire.
Before connecting the lighting fitting to mains, connect the battery to the electronic system (white
terminal).
3. For operation testing - activate the AC power supply.
LED indicator should light up green, indicating the connection to AC power supply and battery charging.
After the battery is charged, the LED indicator should light up green, which means that the lighting fitting is
ready for emergency operation. Pressing the manual test button will result in the lighting fitting switching
into emergency mode operation and the LED indicator turning off.
4. First-time charge of the lighting fitting (battery) should be carried out continuously for 48 hours, due to the
characteristics of Ni-Cd batteries. This will allow appropriate formatting of the battery pack. During the first-
time charge, no testing should be carried and power supply should not be disconnected for any other
purposes. Power supply should be disconnected after 48 hours for the first time. The lighting fitting should
complete a full emergency operation cycle, after which it should be connected to power supply for another
36 hours. This sequence shall complete the formatting cycle.
OPERATION
Emergency operation mode
With standard wiring mode, described in part “Installation” point 2, the lamp will operate in emergency mode. In
this mode the lamp operates when powered by AC supply voltage. Correct operation of the device is confirmed
by LED indicator lighting up green. The battery is continuously topped up for the purpose of possible emergency
operation. When AC power supply is off, the lamp automatically starts operating in emergency mode and the
source of light is activated for the period specific for particular model. In emergency mode, the LED indicator
does not light up.
Mains and emergency operation mode
To enable emergency operation of the lighting fitting, in addition to the standard wiring described in part
“Installation” point 2, the Lch and Lsw terminals have to be interconnected. In this mode the lamp operates
when powered by AC supply voltage. Correct operation of the device is also confirmed by LED indicator lighting
up green. Battery is continuously topped up for the purpose of possible emergency operation. When AC power
supply is off, the lamp automatically starts operating in emergency mode and the light source is activated for the
period specific for particular model.
Information on lamp operation
The lamp is operating correctly and is ready for emergency operation if the LED indicator lights up green. Battery
charging is indicated by LED indicator lighting up red.
Battery
The lamp is equipped with a rechargeable Ni-Cd battery. Please remember to carry out the correct first-time
charge cycle. It is crucial with this type of batteries - it determines the battery capacity and its life during
subsequent operation.
Battery charging is indicated by the LED indicator lighting up green. Battery full and battery ready are indicated
by the LED indicator lighting up green. It is recommended to discharge and then recharge the battery one time
every three months, even if it has not been used, in order to prolong its life. It is recommended to replace the
battery one time every four years of operation or in case of negative testing results. Obsolete batteries are
recyclable products that should be disposed to a recyclable waste collection point.
FAULTY OPERATION AND ITS POSSIBLE DIAGNOSIS
LED indicator does not light up and the lamp does not produce light output
AC mains power failure.
LED lighting fitting lights up red, the lamp does not produce light output (e.g. in mains and emergency mode)
The battery is disconnected or damaged.
The lighting fitting does not operate in emergency mode the required time for the selected model
It is possible that the battery requires a full charge cycle (48h). If after 48 hours of charging the lamp still does
not maintain a given operation time, it is possible that the battery is worn out or damaged due to possible
incorrect formatting and needs to be replaced.
Other Intelight Light Fixture manuals
Popular Light Fixture manuals by other brands

Robe
Robe Beam 250XT user manual

Cooper Lighting
Cooper Lighting Halo L1751 Specifications

Agilent Technologies
Agilent Technologies 16092A Operation and service manual

Konstsmide
Konstsmide 2386 technical information

Lightolier
Lightolier QVS2GPASQ2TT specification

Maxim Lighting
Maxim Lighting Granville manual