SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
Product Description
The Battery Control Center is a centralized power switching, fusing and distribution center. Power from the
Main and the Auxiliary batteries is fed into the Battery Control Center. The full power of both batteries is
available within the box. The system consists of two (2) Battery Disconnect Relays, a bi-directional battery
charging circuit, an auxiliary start function to provide a "jump start" from the Auxiliary battery, ignition power
switching and a fog light relay circuit.
Low current Test Light,Accurate Voltmeter, (digital read-out preferred).
Gently lift the cover catches, located on each side of the box, and pull them
outward and towards yourself. The cover may then be lowered to allow easy access to the fuses and
circuitry.
CAUTION:
TOOLS REQUIRED:
TO REMOVE COVER:
All servicing of the Battery Control Center should be done only by a qualified Service Technician.
Inadvertent shorts inside the Battery Control Center could result in severe damage and/or injury.
1
Part Number 00-00606-100

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
How The Battery Control Center Works
Battery Disconnect -
Charging Circuit -
Auxiliary Start -
Ignition Switched Power -
Fog Light Relay -
Circuit Breakers -
The Battery Disconnect relays are used to disconnect the batteries during periods of storage, or during service.
The disconnect relays operate by momentarily applying 12 volts to the solenoid coil in either of two directions,
(+12 volts on the "S" terminal and ground on the "I" terminal for opening) and (+12 volts on the "I" terminal and
ground on the "S" terminal for engaging). The actuation voltage is supplied from the highest voltage of either
the Auxiliary or Main battery through F19. The voltage is supplied to the momentary switches mounted in the
coach and then fed back to the relays in the box. (See Battery Disconnect schematic, Figure 2).
The charging circuit, (which utilizes an isolator solenoid to connect the two batteries together for charging) will
charge both batteries if either battery is being charged. It operates by sensing the voltage on the Main and
Auxiliary batteries. If either voltage goes above 13.3 volts (the minimum necessary to fully charge a battery)
for more than 14 seconds, the isolator solenoid will pull in, charging both batteries. If, while the ignition is on,
the voltage falls below 12 volts for more than 4 seconds, the isolator relay will open, keeping all of the
alternator's output available for the chassis functions. If the ignition is off and the Auxiliary battery voltage
should drop below 12.8 volts (voltage of a fully charged battery) for 4 seconds, the isolator relay will open,
preventing the coach loads from discharging the main battery. (See Charging Circuit/Aux Start schematic,
Figure 3).
The Auxiliary Start function is used to provide a "jump start" from the auxiliary battery in the event that the Main
battery does not have sufficient charge to start the engine. It operates by momentarily connecting the Main and
the Auxiliary batteries together through the isolator relay. This function is accomplished by pressing the dash
mounted switch, which applies 12 volts to the isolator relay coil. The switch power is supplied by fuse F17.
(See Charging Circuit/Aux Start schematic, Figure 3).
The ignition circuits are switched by three relays, K1, K2, and K4, to supply power to the horn, rear heater,
power windows and the power seat. The power for these relay coils comes from the ignition switch through J4,
pin 11. (See Charging Circuit/Aux Start schematic, Figure 3).
The Fog Light relay supplies 12 volts to the fog lights, when the coach is so equipped. To operate the fog lights,
12 volts from the ignition is fed to a dash mounted fog light switch and is applied to the relay's coil, through pin 12
of J4. The fog light's power comes from the Main battery through fuse F13. It is switched by the relay and is
routed from the printed circuit board through plug J4, pin 9. (See Fog Light schematic, Figure 4).
Each of the ignition relays is rated at 30 Amps,
therefore the sum of the total continuous currents through relay K2, which includes fuse F6 (J5, pin 4)+F8 (J5,
pin 6), must not exceed 30 Amps. In like manner, the sum of the total continuous currents through relay K1
which includes fuse F9 (J5, pin 7)+F10 (J5, pin 8)+F11 (J11) must not exceed 30 Amps, and the sum of the total
continuous currents through relay K4 which includes fuse F12 (J12)+F22 (J17)+F23 (J18) must not exceed 30
Amps.
There are two 30 Amp circuit breakers, located near the front at the bottom of the box, that are used to protect
the wiring between the Auxiliary battery and the converter. These breakers have manual reset buttons that pop
out when they are tripped ( See Figure 5)
2

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
TROUBLE SHOOTING
Note
.
The Battery Control Center is built in two layers, the printed circuit board and the relays. The box has been
designed so that nearlyALL trouble shooting can be done without the removal of the printed circuit board. Read
and understand the trouble shooting procedure first before EVER removing the printed board. The printed
circuit board must be removed to repair the relays on the lower level.
Once the outer box cover has been removed, ALL the fuses in the box are located on the printed circuit board
and are easily visible for testing and replacement. The fuses can be checked either visually, or with a test light.
To check the fuses visually: Remove the suspected fuse using the fuse tool supplied in the box and examine for
damage to the fusing element.
To check using a test light: Ground the test light to the test ground terminal, J20, provided on the board. (See
printed circuit board illustration, Figure 1) :
Check for power on both sides of the fuse. If applicable, make sure Battery Disconnect Relays and
fog light switches, are on when checking fuses.
The Battery Disconnect relay terminals are available at test points on the printed circuit board, making it
unnecessary to remove the board for testing . These test points are located near the left edge of the board and
are labeled. Each "S" terminal is available through a 1/4" spade connector so that the test light can be clipped to
it. There is a ground terminal at the bottom of the group that can be used for a test light ground.
To engage a relay, momentarily apply +12 volts to the "I" terminal, TP1 or TP2, and the "S" terminal, J19 or J21,
is grounded. To open the relay, momentarily apply +12 volts to the "S" terminal and the "I" terminal is grounded.
A push button to test the isolator relay is provided on the board to manually actuate the relay. It is located near
the upper right corner of the board and labeled "AUX START". (See Figure 1) The coach must be unplugged
and the engine and generator need to be off for at least ten minutes, to allow the isolator electronics to turn off
the relay drive. Pressing this button should close the isolator relay, which can be detected by the clicking sound
of the relay.
The converter circuit breakers, which are in parallel, carry the current between the Auxiliary battery and the
converter. If the coach is not being supplied 120 volts AC, the current is flowing from the battery to the
converter. If the coach is being supplied 120 volts AC, the converter is usually charging the batteries and the
current will flow from the converter to the batteries. If there is a fault or overload between the converter and the
batteries, the circuit breakers will open as indicated by the reset buttons being popped out. To reset the
breakers, turn off the 12 loads and push the buttons in until they latch.
Checking Fuses
This ground terminal should never be used for any other
purpose
Checking the Battery Disconnects
Isolator Relay
Circuit Breakers
3

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
PRINTED CIRCUIT BOARD REMOVAL
PRINTED CIRCUIT BOARD REPLACEMENT
In the event that the printed circuit board needs to be removed, the following procedure should be followed.
1) Remove the negative wires from both batteries to prevent injury to individuals and the equipment.
Be sure that these wires stay clear of the battery posts. Remove power to the converter.
2) Remove the cover of the Battery Control Center to expose the board.
3) Pull chassis harness plugs from connectors, J2, J4, and J5.
4) Note the locations of wires connected to Faston connectors, J9 through J12, and J15 through
J18, located along the lower edge of the board next to J5. It is best to write down the wire positions
and colors so that they can be re-connected correctly.
5) Pull relay harness plug from J1.
6) Note the locations of wires connected to output Faston connectors, J6, J7, J8, and J13, located
along the upper edge of the board. It is best to write down the wire positions and colors so that
these wires can be re-connected correctly.
7) Remove the 1/4" hex head bolt located near the center-right side of the board.
8) Remove the four #8 hex head screws located in the four corners and center of the board.
9) Remove the board.
Replace the board in the reverse order from the removal. Be sure to tighten the 1/4" hex head bolt going
through the board, for it provides the power connection to the battery feed. Failure to properly tighten this bolt
will lead to failure.
4

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
5
Generator Auxiliary Battery Converter Circuit
Breakers
Main Battery
Pictorial View
Figure 1
MAIN BD

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
TROUBLE SHOOTING - Battery Disconnect
A. Both relays fail to operate.
B. One relay fails to operate.
C. Main battery relay fails to operate.
D. Coach functions operate when coach is plugged in, but not from the battery.
1. Batteries may be dead. Check for voltage at the top end of F19 which is the feed from the higher of
either the auxiliary or main battery. (F19 is located at the top left center of the printed circuit board).
The voltage on F19 should be at least 11 volts. If the voltage is less, charge either battery. If the
voltage is more than 11 volts, continue.
2. F19 may be blown. Check for voltage at the top of F19 using a test light. This voltage should be
the same as at the bottom end. Replace fuse F19, if the voltage is not the same.
3. Ground lead to switches may be open. Check for ground and 12 volts on the "I" and "S" test points
on the printed circuit board of the Disconnect Relay, while an assistant presses the Battery
Disconnect switch in the coach.
1. Wiring or switch may be faulty. To check the operation, have an assistant operate the Battery
Disconnect switch inside the coach. Check for voltage on the "I" and ground on the "S" terminal
at the test points on the printed circuit board.
2. Disconnect Relay may be faulty. If at least 11 volts is available on the "I" or "S" terminal
and the relay fails to operate, replace the relay.
1. Ignition may be on. Check to be certain that the switched-ignition is 0 volts.
2. Interlock relay may be faulty. Check for 12 volt power feeding switch at plug J2 pin 8.
3. There may not be 12 volt power to the switch. If there is not 12 volts check fuse F19.
1. Circuit breakers feeding converter may be open. Reset circuit breakers in box.
6

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
TROUBLE SHOOTING - Charging Circuit
A. Auxiliary battery does not charge.
no
B. Main battery continues to drain.
C. Main battery doesn't charge from converter.
A. Auxiliary Start fails to operate.
1. The isolator relay may not be closing. Operate the engine at a high idle for at least twenty (20)
seconds and check the chassis battery voltage. The voltage must be at least 13.3 volts before
the isolator activates. Check the alternator, if the voltage is less than 13.3 volts.
Check for voltage on the coil terminal of the isolator relay. This voltage is available on J1-5. If
there is voltage on the coil, replace the printed board. If there is voltage on the coil, check for
voltage between the main and auxiliary batteries. If the voltage is more than 0.1 volts replace the relay.
1. Isolator relay may be bad. Check for voltage on the solenoid coil lead which is available on J1-5,
when the engine is off. If there is no voltage, replace the relay.
1. The converter is not putting out at least 13.3 volts. Check converter, turn off excess 12 volt loads if
necessary.
2. Converter circuit breakers in Battery Control Center open. Reset breakers are located on lower
edge of box.
1. Fuse 17 may be blown. Check F17.
2. The Auxiliary battery may be dead. Charge battery.
3. Isolator relay may be defective. To test the relay, press the "AUX START" switch on printed
circuit board while measuring the voltage between the two batteries. (The isolator relay should
"click" indicating that it is closing.) If the voltage is more than 0.1 volt, replace the relay.
4. Switch or wires may be faulty. Check for 12 volts at J4 pin 2, while pushing switch. If there is not 12
volts, check wiring, if OK, replace the switch.
Auxiliary Start
7

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
TROUBLE SHOOTING - Ignition Relay
A. The horn, the electric step, power window, the rear heater or the power seat fail to operate.
A. Fog Lights fail to operate.
1. Check for 12 volt ignition power coming into printed circuit board on plug J4, pin 11.
2. Check respective fuse.
3. Check for faulty wiring from the ignition switch.
4. Replace the printed circuit board.
1. Bulbs are burned out. Replace.
2. Ignition is not on.
3. No 12 volt power. Check fuse F13.
4. No power from the fog light switch. Check for voltage at J4, pin 12.
5. No 12 volt power to fog lights. Check for voltage at J4, pin 9.
6. Fog light relay has failed. Replace printed circuit board.
Fog Light Relay
8

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
FUSES
The fuses used on the Battery Control Center are standard, plastic "ATO", blade (automotive) type. There are
23 positions for fuses on the board. These are fed from five main sources, the Disconnect-Switched Main
Battery, Ignition-Switched Main Battery, Disconnect-Switched Auxiliary Battery and the Auxiliary Battery.
The 23 fuses and their size are as follows:
Spare F20 15 Amp J15
Spare F21 15 Amp J16
Spare F1 15 Amp J9
Spare F2 15 Amp J10
Step Motor F3 25 Amp J5-1
Step Switch F4 5 Amp J5-2
LP Detector F5 5 Amp J5-3
Power Seat F7 15 Amp J5-5
Ignition Signal F6 7.5 Amp J5-4
Rear Heater F8 15 Amp J5-6
Power Window F9 20 Amp J5-7
Horn/Leveling Jacks F10 15 Amp J5-8
Spare F11 15 Amp J11
Spare F12 15 Amp J12
Spare F22 15 Amp J17
Spare F23 15 Amp J18
F13 15 Amp J4-9
Connector
Disconnect-Switched Main Battery Pin-Out
Ignition-Switched Main Battery
Fog Light
NOTE: Each of the ignition relays is rated at 30 Amps, therefore care must be exercised when substituting
fuses or adding additional loads. The sum of the total continuous currents through relay K2, which includes
fuse F6 (J5, pin 4)+F8 (J5, pin 6), must not exceed 30 Amps. In like manner, the sum of the total
continuous currents through relay K1A which includes fuse F9 (J5, pin 7)+F10 (J5, pin 8)+F11 (J11) must
not exceed 30 Amps, and the sum of the total continuous currents through relay K1B which includes fuse
F12 (J12)+F22 (J17)+F23 (J18) must not exceed 30 Amps.
Disconnect-Switched Auxiliary Battery
Spare F14 15 Amp J6
LP Detector F15 5 Amp J4-4
Radio Switch F16 10 Amp J4-1
9

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
FUSES (CONT’D)
Connector
CIRCUIT BREAKERS
PLUGS - PINS & FUNCTIONS
J1 - 8 pin in-line (KK-156)
Pin Function
Auxiliary Battery Pin-Out
Battery Disconnect
Auxiliary Start F17 5 Amp J4-2
Solar Panel F18 5 Amp J4-3
Battery Disconnect Relay F19 5 Amp J2-7
There are two, 30 Amp type III (manual reset) circuit breakers mounted in the box. They are connected to the
Auxiliary battery through the Disconnect relay. These breakers are intended to connect to the converter and
fuse panel within the Auxiliary. These circuit breakers are located at the bottom of the box, near the front edge.
To reset the breakers, press the buttons on the ends.
1 Main BD "I" terminal
2 Main BD "S" terminal
3 Auxiliary BD "S" terminal
4 Auxiliary BD "I" terminal
5 Isolator Relay "HOT" terminal
6 Isolator Relay GROUND terminal
10

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
PLUGS - PINS & FUNCTIONS (Cont’d)
1 Main BD "I" terminal
2 Main BD "S" terminal
3 Auxiliary BD "S" terminal
4NC
5NC
6 Auxiliary BD "I" terminal
7 Auxiliary BD power, (Aux. Bat.) F19
8 Main BD power, (Aux. Bat.), ignition switch
9 BD Relay ground
1 Radio Switch F16
2 Aux Start Switch F17
3 Solar Panel F18
4 L. P. Det. (Aux.) F15
5NC
6 Ground
7NC
8NC
9 Fog Lights F13
10 Aux Start Relay Coil
11 Ignition Relay Coil
12 Fog Light Relay Coil
J2 - 9 pin Mate-N-Lok Mating Housing Amp 1-480706-0
Pin Function Fuse
J4 - 12 pin Mate-N-Lok Mating Housing AMP 1-480708-0
Pin Function Fuse
11

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
PLUGS - PINS & FUNCTIONS (Cont’d)
J5 - 8 pin Mate-N-Lok Mating Housing AMP 640586-1
Pin Function Fuse
J22 - 2 pin Mate-N-Lok Mating Housing AMP 1-480698-0
Pin Function Fuse
1 Step Motor F3
2 Step Switch F4
3 L. P. Det. (Main) F5
4 Ignition Signal F6
5 Power Seat F7
6 Rear Heater F8
7 Power Window F9
8 Horn/Leveling Jacks F10
1 Isolator Relay Coil Power F24
2 Isolator Relay Coil Ground
12

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
13

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
14
From Gen-Set
Run Light
External
Isolator
Solenoid
Coil
Ground
F24

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
15

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
16
NOTE: Each of the ignition relays is rated at 30 Amps, therefore care must be exercised when substituting
fuses or adding additional loads. The sum of the total continuous currents through relay K2, which
includes fuse F6 (J5, pin 4)+F8 (J5, pin 6), must not exceed 30 Amps. In like manner, the sum of the total
continuous currents through relay K1A which includes fuse F9 (J5, pin 7)+F10 (J5, pin 8)+F11 (J11) must
not exceed 30 Amps, and the sum of the total continuous currents through relay K1B which includes fuse
F12 (J12)+F22 (J17)+F23 (J18) must not exceed 30 Amps.
External
Isolator
Solenoid
K5
K2
K1
K4

1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00606-100 Rev. D 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
BATTERY CONTROL CENTER - MINI DIESEL
Table of contents
Other Intellitec Controllers manuals
Popular Controllers manuals by other brands

Tornatech
Tornatech GPL Installation and maintenance manual

Panasonic
Panasonic WVCU161C - SYSTEM CONTROLLER Specifications

Mitsubishi Electric
Mitsubishi Electric MHK2 installation manual

Emerson
Emerson Aventics SENTRONIC HD 616 Series installation manual

Danfoss
Danfoss 088U0200 manual

Control Industries
Control Industries RC 1T5A Service instructions