
INSTALLATION
1. Remove the four #10 hex head screws from the back
of the enclosure and attach mounting brackets to
enclosure.
2. Select the proper location for the Control Panel and
hang enclosure on a flat vertical surface or other
support, using hardware suitable for the purpose.
3. Prepare the necessary conduit runs, terminate
them at both ends and pull in the conductors as
specified by the installation layout.
4. Refer to Figure 1 below; note that
this enclosure contains one Time
Switch. To wire the panel, follow
the wiring diagram located inside
the enclosure door. Make sure that
connections to time switch terminals are tight
(25 lb.-in. minimum)and insulation clears the
pressure plate - see illustration.
5. If required by the heater manufacturer, install
fireman switch kit 156T4042A (not furnished)
on Time Switch Plate and make the fireman switch
connections. Use at least #18 AWG wiring with
insulation rated 300 Volt or higher. Place heater
ON/OFF switch on heater to ON (see Figure 2
on page 3). Some heaters may require a special con-
necting harness, contact heater manufacturer for details.
6. To install an additional wiring device inside the
enclosure, first remove rectangular knock-out(s) in
dead front. Next, remove hex head screws in back of
enclosure and install stand-offs* in place of screws.
Attach wiring device to stand-offs.
*Stand-offs are not furnished. Order 21T156A for a set of four
(4) stand-offs and mounting hardware.
7. If external bonding is required, install a bonding lug
at bottom of enclosure and bond installation
according to code requirements.
8. Testing of the installation is optional and
recommended only if pump is securely in place
and will not be damaged by this test:
a. Turn the manual lever of the Time Switch to OFF.
b. Turn ON power at breaker panel.
c. Move the manual lever of Time Switch to the
right (ON). Pump should start and run on full
speed. In case of unsatisfactory results, turn OFF
power, check your wiring, refer to Troubleshoot-
ing on Page 3.
2
Figure 1
9. The enclosure must be grounded as required by
NEC, Article 680 and any applicable local codes.
For Canadian installations, the transformer supply
circuit must be protected by a ground fault circuit
interrupter.
10. If this enclosure is used for direct connection of
underwater lights, refer to 1999 NEC 680-21(b),
2002 NEC 680-24(b) or CEC 68-060, 062 and 066
for further details.
11. Make sure that all unused transformer taps (leads)
are separately insulated.
12. Use the tables at the top of page 3 as a guide to
determine the correct wire size.
13. Check voltage at lamp terminals after installation.
It should be 12+0.3 volts.
14.Install front panel over wiring compartment. The
control is now ready for programming, see
OPERATION section on Page 3.
Risk of injury or property damage!
Do not install or operate this equipment and other associated equipment without basic safety
precautions.
Read and follow the safety instructions listed below and other basic safety precautions before
installation or operation of this control and other associated equipment.
1. This control must be installed by a qualified person, according to the national and local electrical
codes.
2. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool and 1 foot
(30cm) above ground.
3.USECOPPERCONDUCTORSONLYrated75˚Cminimum.
4. Do not exceed maximum ratings of individual components, wiring devices and current carrying
capacity of conductors.
5. For control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680
of the National Electrical Code or Article 68 of the Canadian Electrical Code.
6. The control should not operate any equipment which would cause bodily injury or property
damage should it be activated unexpectedly.
CAUTION