DS221117032GEN© 2022 INTERRA
1/3
KNX-DALI Gateway DESCRIPTION
GENERAL FUNCTIONS
SAFETY PRECAUTIONS & IMPORTANT NOTES
Product Code ITR832-00X1 ITR832-00X2
DALI Line Output 1 x 64, Single Channel 2 x 64, Dual Channel
Max. ECG Devices Up to 64 devices (1 x 64) Up to 128 devices (2 x 64)
Display 2x16 LCD Display 2x16 LCD Display
Short-Circuit &
Overvoltage Proof Available Available
Power Supply 220 V AC 50/60 Hz 220 V AC 50/60 Hz
Power Consumption 6 W 13 W
KNX Line Current
Con. 13 mA 13 mA
DALI Line Current
Con. 1 x 250 mA 2 x 250 mA
DALI Voltage Typical 19 V DC (12...20.5) Typical 19 V DC (12...20.5)
Bus Connection 1 x KNX, 1 x Ethernet* and
1 x USB Port
1 x KNX, 1 x Ethernet* and 1
x USB Port
Type of Protection IP 20 IP 20
Temperature Range
Operation (-5°C...45°C)
Storage (-25°C...55°C)
Operation (-5°C...45°C)
Storage (-25°C...55°C)
Max. Air Humidity < 90 RH < 90 RH
Colour Light Grey and White Light Grey and White
Dimensions 90 x 70 x 64.5 mm
(H x W x D)
90 x 70 x 64.5 mm
(H x W x D)
Configuration Configuration with ETS Configuration with ETS
• Addressing operations can be done via ETS or manual buttons as a
short address assignment.
• Assigning group adressess to ballasts via ETS without need additional
software.
• Faulty ballast detection.
• Faulty lighting detection.
• Commissioning and control via an embedded web server (**).
• DALI line device selection with the manual button.
• Remote software update via Ethernet connection.(*)
• Emergency lighting test (according to EN 62386-202 standard).
• Automatic DALI Device Addressing.
•
•
• KNX Bus Voltage Failure Status.
• KNX Voltage Recovery Status.
• DALI Bus Voltage Failure Status.
• DALI Voltage Recovery Status.
• Ballast and / or Lighting Error.
• Working log analysis with UDP.
• Broadcast control can be made with manually and software.
• Tunable White color temperature control.
• RGB and RGBW color control.
COMISSIONING FUNCTIONS
• The device may only be installed and put into operation by a qualified
electrician or authorized personnel.
• For planning and construction of electric installations, the appropriate
specifications, guidelines and regulations in force of the respective
country have to comply.
• Special Programming: This device is designed for professional KNX
and DALI installation. It can be programmed by ETS and Web
Browser*.
• Cable Connections: Ensure making correct connections for Black and
Red wires.
• Input Voltage: The input voltage shall be 240 V AC.
• Installation only in dry locations and on a 35 mm DIN rail (TH 35).
• For mounting, only use appropriate equipment according to
IEC 60715.
• Rain, liquid and aggressive gas should not be allowed to be close to
the device.
• Screw down strength is less than 0.4 Nm.
• Do not get AC 240 V voltage into Bus lines, it can damage all the
devices in the system.
Device Type 0 (DT0) Fluorescent Lamp
Device Type 1 (DT1) Self-Contained Emergency
Device Type 6 (DT6) LED Lamp
Device Type 8 (DT8) Colour Control
The ITR832-00X1 & ITR832-00X2 single and dual-channel KNX-DALI
interface devices are used to provide an interface between DALI and
KNX installations, enabling communication between the two
protocols. DALI devices (ballasts, etc. ECGs) connected to the line
are supplied with the internal DALI power supply. With the
ITR832-00X1 single-channel device up to 1x64 DALI ballasts can be
connected, with the ITR832-00X2 dual-channel device up to 2 x 64
DALI ballasts can be connected. With each DALI channel, 16 groups,
16 scenarios and 64 devices can be controlled. In addition,
independent emergency lighting according to EN 62386-202 will be
supported with the 2nd version update. Emergency lighting tests (e.g.
function and time test) can be triggered via the KNX line. In addition,
feedback on the KNX line can be sent. Each DALI device can be
controlled individually, in group or broadcast control.
** Please ask the Manufacturer.
0 : Ethernet port | 1 : No Ethernet port * : ITR832-0011 & ITR832-0012 have no Ethernet port
DS221117032GEN© 2022 INTERRA
2/3
DIMENSIONS MOUNTING & DEMOUNTING PROCESSES
• First, the device is contacted to the DIN rail by holding it at an
oblique angle.
• Then, it is pushed slightly from above in the direction of the 1st
numbered arrow.
• Finally, the device is pushed slightly in the direction of the 2nd
arrow and placed on the DIN rail to finish the mounting.
FEATURES OF CONNECTORS & BUTTONS
1.
2.
• First, the device is pushed slightly from above in the direction of
the 1st numbered arrow.
• Then, the device is pulled slightly in the direction of the 2nd arrow.
• Finally, when the device is at a sufficient oblique angle, it is
completely withdrawn from the DIN rail and the demounting is
finished.
1.
2.
Mounting
Demounting:
1. DALI Bus Channel 1
2. DALI Bus Channel 2
3. KNX Programming
LED
4. KNX Programming
Button
5. KNX Connector
6. Power Input
7. Ethernet*
8. USB
9. Ethernet LED*
10. Error Status LED
11. Menu Mode Button
12. Menu Setting Button
13. Menu Back Button
90 mm
70 mm
64.5 mm
• All values given in the device dimensions are in millimetres.
• The device can be used in an area of up to 4 modules.
MARKS
CE : Interra KNX-DALI Gateway complies with Electromagnetic
Compatibility Directive (2014/30/EU), Low Voltage Directive (2014/35/
EU) and Restricting the Use of Hazardous Substances Directive
(2011/65/EU).
* : ITR832-0011 & ITR832-0012 have no Ethernet port
DS221117032GEN© 2022 INTERRA
3/3
DEVICE CONNECTION DIAGRAM
Single Channel ITR832-00X1 : Dual Channel ITR832-00X2 :
• ITR832-00X2 - KNX-DALI Gateway Dual Channel device
is supplied with 240 V AC mains voltage. The phase, neutral
and ground connections are shown in the figure (L, N, PE).
• The positive (+) and negative (-) poles of the DALI
electronic control units (ECGs) should be connected correctly
via the two independent DALI lines on the device to ensure
DALI communication.
• The supply voltages of the DALI electronic control units
are supplied from the mains and so the phase, neutral and
ground connections of the ECGs should be properly
connected.
• ITR832-00X1 - KNX-DALI Gateway Single Channel device
is supplied with 240 V AC mains voltage. The phase, neutral
and ground connections are shown in the figure (L, N, PE).
• The positive (+) and negative (-) poles of the DALI
electronic control units (ECGs) should be connected correctly
via the single DALI line on the device to ensure DALI
communication.
• The supply voltages of the DALI electronic control units
are supplied from the mains and so the phase, neutral and
ground connections of the ECGs should be properly
connected.

This manual suits for next models

1

Popular Gateway manuals by other brands

Plugwise Adam installation manual

Plugwise

Plugwise Adam installation manual

Rosslare AY-M26 Installation and configuration manual

Rosslare

Rosslare AY-M26 Installation and configuration manual

ABB ARG600 ANSI Product guide

ABB

ABB ARG600 ANSI Product guide

Blonder tongue NXG-MFR Setup and configuration guide

Blonder tongue

Blonder tongue NXG-MFR Setup and configuration guide

SSV IGW/935 First steps

SSV

SSV IGW/935 First steps

Pepperl+Fuchs AS-I 3.0 PROFINET manual

Pepperl+Fuchs

Pepperl+Fuchs AS-I 3.0 PROFINET manual

Dragino LG02 user manual

Dragino

Dragino LG02 user manual

Valcom VIP-802B manual

Valcom

Valcom VIP-802B manual

ZyXEL Communications P-870HN-5xb user guide

ZyXEL Communications

ZyXEL Communications P-870HN-5xb user guide

ITS Telecom CGW-I Installation and operation guide

ITS Telecom

ITS Telecom CGW-I Installation and operation guide

MatchX Box US MX1702 user guide

MatchX

MatchX Box US MX1702 user guide

Caimore CM510-x-50P Series Operation manual

Caimore

Caimore CM510-x-50P Series Operation manual

3Com OfficeConnect 3CRWE554G72 user guide

3Com

3Com OfficeConnect 3CRWE554G72 user guide

ZyXEL Communications ZyWALL 5 Series user guide

ZyXEL Communications

ZyXEL Communications ZyWALL 5 Series user guide

ProSoft Technology ICX35-HWC user manual

ProSoft Technology

ProSoft Technology ICX35-HWC user manual

Artistic Licence daliGate quad user guide

Artistic Licence

Artistic Licence daliGate quad user guide

Zte ZXHN H185 user manual

Zte

Zte ZXHN H185 user manual

hilscher netTAP NT 50 Series user manual

hilscher

hilscher netTAP NT 50 Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.