DS221117032GEN© 2022 INTERRA
1/3
KNX-DALI Gateway DESCRIPTION
GENERAL FUNCTIONS
SAFETY PRECAUTIONS & IMPORTANT NOTES
Product Code ITR832-00X1 ITR832-00X2
DALI Line Output 1 x 64, Single Channel 2 x 64, Dual Channel
Max. ECG Devices Up to 64 devices (1 x 64) Up to 128 devices (2 x 64)
Display 2x16 LCD Display 2x16 LCD Display
Short-Circuit &
Overvoltage Proof Available Available
Power Supply 220 V AC 50/60 Hz 220 V AC 50/60 Hz
Power Consumption 6 W 13 W
KNX Line Current
Con. 13 mA 13 mA
DALI Line Current
Con. 1 x 250 mA 2 x 250 mA
DALI Voltage Typical 19 V DC (12...20.5) Typical 19 V DC (12...20.5)
Bus Connection 1 x KNX, 1 x Ethernet* and
1 x USB Port
1 x KNX, 1 x Ethernet* and 1
x USB Port
Type of Protection IP 20 IP 20
Temperature Range
Operation (-5°C...45°C)
Storage (-25°C...55°C)
Operation (-5°C...45°C)
Storage (-25°C...55°C)
Max. Air Humidity < 90 RH < 90 RH
Colour Light Grey and White Light Grey and White
Dimensions 90 x 70 x 64.5 mm
(H x W x D)
90 x 70 x 64.5 mm
(H x W x D)
Configuration Configuration with ETS Configuration with ETS
• Addressing operations can be done via ETS or manual buttons as a
short address assignment.
• Assigning group adressess to ballasts via ETS without need additional
software.
• Faulty ballast detection.
• Faulty lighting detection.
• Commissioning and control via an embedded web server (**).
• DALI line device selection with the manual button.
• Remote software update via Ethernet connection.(*)
• Emergency lighting test (according to EN 62386-202 standard).
• Automatic DALI Device Addressing.
•
•
• KNX Bus Voltage Failure Status.
• KNX Voltage Recovery Status.
• DALI Bus Voltage Failure Status.
• DALI Voltage Recovery Status.
• Ballast and / or Lighting Error.
• Working log analysis with UDP.
• Broadcast control can be made with manually and software.
• Tunable White color temperature control.
• RGB and RGBW color control.
COMISSIONING FUNCTIONS
• The device may only be installed and put into operation by a qualified
electrician or authorized personnel.
• For planning and construction of electric installations, the appropriate
specifications, guidelines and regulations in force of the respective
country have to comply.
• Special Programming: This device is designed for professional KNX
and DALI installation. It can be programmed by ETS and Web
Browser*.
• Cable Connections: Ensure making correct connections for Black and
Red wires.
• Input Voltage: The input voltage shall be 240 V AC.
• Installation only in dry locations and on a 35 mm DIN rail (TH 35).
• For mounting, only use appropriate equipment according to
IEC 60715.
• Rain, liquid and aggressive gas should not be allowed to be close to
the device.
• Screw down strength is less than 0.4 Nm.
• Do not get AC 240 V voltage into Bus lines, it can damage all the
devices in the system.
Device Type 0 (DT0) Fluorescent Lamp
Device Type 1 (DT1) Self-Contained Emergency
Device Type 6 (DT6) LED Lamp
Device Type 8 (DT8) Colour Control
The ITR832-00X1 & ITR832-00X2 single and dual-channel KNX-DALI
interface devices are used to provide an interface between DALI and
KNX installations, enabling communication between the two
protocols. DALI devices (ballasts, etc. ECGs) connected to the line
are supplied with the internal DALI power supply. With the
ITR832-00X1 single-channel device up to 1x64 DALI ballasts can be
connected, with the ITR832-00X2 dual-channel device up to 2 x 64
DALI ballasts can be connected. With each DALI channel, 16 groups,
16 scenarios and 64 devices can be controlled. In addition,
independent emergency lighting according to EN 62386-202 will be
supported with the 2nd version update. Emergency lighting tests (e.g.
function and time test) can be triggered via the KNX line. In addition,
feedback on the KNX line can be sent. Each DALI device can be
controlled individually, in group or broadcast control.
** Please ask the Manufacturer.
0 : Ethernet port | 1 : No Ethernet port * : ITR832-0011 & ITR832-0012 have no Ethernet port