Inverex NITROX-12KW User manual

PV Solar On Grid Inverter
NITROX- 12KW-3Ph-5G / NITROX-15KW-3Ph-5G
NITROX- 20KW-3Ph-5G / NITROX-25KW-3Ph-5G
User Manual

ContentsContents
1. Introduction
1.1 Appearance Introduction
1.2 Parts list
2. Safety warnings and instructions
2.1 Safety signs
2.2 Safety instructions
2.3 Notes for using
3. Operation Interface
3.1 Interface View
3.2 Status Indicator
3.3 Buttons
3.4 LCD Display
4. Product installation
4.1 Select installation location
4.2 Inverter Installation
5. Electrical Connection
5.1 DC input terminal connection
5.2 AC input terminal connection
5.3 The connection of the ground line
5.4 Inverter monitoring connection
6. Startup and Shutdown
6.1 Start up the inverter
6.2 Inverter Shutdown
7. Limiter function (Optional)
7.1 Limiter function wiring diagram
7.2 Connect the limiter to inverter
7.3 Debugging Limiter
8. General Operation
8.1 The initial interface
8.2 Statistics information
8.3 Fault Record
8.4 ON/OFF setting
8.5 Parameter setting
8.5.1 System Param
8.5.2 Running Param
8.5.3 Comm.Param
- 1 - - 39 -
- 39 -
- 39 -
- 42 -
- 42 -
- 1 -
- 2 -
- 3 -
- 3 -
- 3 -
- 5 -
- 6 -
- 6 -
- 6 -
- 7 -
- 7 -
- 8 -
- 8 -
- 10 -
- 12 -
- 12 -
- 15 -
- 18 -
- 18 -
- 21 -
- 21 -
- 21 -
- 22 -
- 22 -
- 23 -
- 26 -
- 27 -
- 27 -
- 30 -
- 32 -
- 33 -
- 34 -
- 35 -
…………………………………………………………
…………………………………………
………………………………………
…………………………………………………………
…………………………………………………………
………………………………………………
……………………………………
…………………………………………………
…………………………………………………………
………………………………………………………
…………………………………………………
……………………………………………………
……………………………………………………
……………………………………………………
……………………………………………………
………………………………………………………
……………………………………………
……………………………………………………
…………………………………………………………
…………………………………………
…………………………………………
………………………………………
………………………………………
……………………………………
…………………………………………………
…………………………………
……………………………………
………………………………………………
………………………………………………
………………………………………………
………………………………………………
……………………………………………………
…………………………………………………
………………………………………………………
……………………………………………………
……………………………………………………
……………………………………………………
…………………………………………………… - 37 -
…………………………………………………… - 38 -
……………………………………………………
………………………………………
Contents
9. Repair and Maintenance
10. Error information and processing
10.1 Error code
10.2 Troubleshooting
11. Specification

1. Introduction
Photovoltaic Grid-connected System
1.1 Appearance Introduction
1.2 Parts list
Three Phase String Power Inverter can convert solar panel DC power into AC power
which can directly input to the grid. Its appearance is shown below.These models contain
NITROX- 12KW-3Ph-5G / NITROX-15KW-3Ph-5G / NITROX- 20KW-3Ph-5G /
NITROX-25KW-3Ph-5G
Pic1.1 Front view Pic1.2 Bottom view
Pic1.3 Accessories drawing
1.1 Parts list
Description
PV Solar On Grid Inverter
Wall mounting bracket
Mounting stainless steel screws M4×12
AC power connectors
DC power connectors(including Inserted spring)
Stainless steel Collision bolt M6×80
Square hole sealing plate(Wi-Fi Function selection)
User manual
Wifi-Plug(optional)
No
1
2
3
4
5
6
7
8
9
1
1
4
1
2pairs
4
1
1
1
Qty
Please check the following table, to see whether all the parts are included in the package:
1
6 7
2 3 4 5
8 9
Serial number Description
A
B
C
D
E
Inverter
Metering device
PV strings
Power grid
Family load
Application of inverter in photovoltaic power system
ABC D
E
- 01 - - 02 -

2. Safety warnings and instructions
2.1 Safety signs
Warning:
Improper use of the inverter will cause electric shock and burn. During installation and
maintenance,please strictly follow the instructions in this manual. Please read the user
manual carefully before using the inverter. And please keep the instructions properly for
afterwards use.
Safety signs are used to emphasize potential safety risk and important safety
information. The manual includes below things:
2.2 Safety instructions
Safety warning——Indifference of the signs in the manual may cause
injury or even death.
Shock Hazard:
Shock warning sign——Incorrect follow of this sign may get shocked.
Safety Hint:
Prudent operation——Incorrect follow of the safety operation hints in
this manual may cause inverter defective.
High Temperature Hazard:
Inverter’s local temperature may exceed 80℃ while under operating.
Please do not touch the inverter’s surface.
Warning:
Electrical installation of the inverter must conform to the safety
operation rules of the country or local area.
Warning:
Inverter is non-isolated topology structure, hence must insure DC
input and AC output are electrical isolated before operating the
inverter. Strictly prohibit ground the positive and negative poles of
the PV string. Otherwise it will damage the inverter.
Shock Hazard:
Prohibit disassembling inverter case. There existing shock hazard,
may cause serious injury or death, please ask qualified person to
maintenance.
Shock Hazard:
When PV module is exposed to sunlight, The output will generate
DC voltage.Prohibit touching to avoid shock hazard.
Shock Hazard:
After disconnecting the input and output of the inverter,it takes at
least 5 minutes for the inverter to completely release the residual
energy and wait for at least 5 minutes before it can be overhauled.
High Temperature Hazard:
Inverter’s local temperature may exceed 80℃ while under
operating. Please do not touch the inverter’s surface.
- 03 - - 04 -

2.3 Notes for using
3.2 Status Indicator
3. Operation Interface
3.1Interface View
1. Inverter should be installed and maintained by qualified person under local standard
regulations.
2. It must disconnect the AC side first, then disconnect DC side before doing installation
and maintenance, after disconnecting, please wait at least 5 mins to avoid get shocked.
3. Local temperature of the inverter may exceed 80 ℃ while under operating.Do not
touch to avoid get injured.
4. All electrical installation must accord with local electrical standards, and after obtaining
the permission of the local power supply department, the professionals can connect the
inverter to the grid.
5. Please take appropriate anti-static measure.
Pic 3.1 Panel
6. Please install where children can not touch.
8. Don t insert and remove AC and DC terminals when the inverter is in normal
operation.
9. The DC input voltage of the inverter must not exceed the maximum input voltage of
the model.
The inverter panel has 4 indicators, the left one is DC output indicator(green),indicates
normal DC input power status. Beside is the AC indicator(green),indicates normal AC
connecting status. Next is the operating indicator(green) indicates normal output. The
right indicator is alarm(red), indicates alarming.
7. When starting the inverter, first close the closed-circuit grid-side switch and close the
DC input terminal; when closing the inverter, disconnect the grid-side switch first and
then disconnect the DC-side switch.
The three phase string power inverter is designed and tested under related safety regulations.
It can ensure the personal safety of the user. But as an electric device, it may cause shock or
injury by incorrect operation. Please operate the unit under below requirements:
- 05 - - 06 -
ACDC AlarmNormal
’

3.3 Buttons
4.1 Select installation location
4. Product installation
There are four buttons on the inverter panel:above is up and increase button (UP),
below is down and decrease button (DOWN), left is ESC button (ESC), right is
Enter button (ENTER). The following functions can be achieved by the four
buttons:
● Page turning (use UP and DOWN button)
● Modify adjustable parameters (use ESC and ENTER button)
Pic4.1 Recommended installation place
After receiving the inverter and preparing to install it, please select a suitable location,
should consider below factors:
● Ventilation—Must insure the air ventilation of the installation location, improper
installation may cause overheating and effect the working efficiency and lifespan.
● Sun-shade—Expose the inverter to sunshine will cause it overheating and effect the
working efficiency.
● Avoid rain and snow—Even if the inverter has IP65 protection,we still recommend.
installing the inverter at the ventilate place where can avoid rain and snow. It can help
extend the lifespan of the inverter.
3.4 LCD Display
NITOX-12,15,20,25KW-3Ph-5G Three-phase string inverters use a dot matrix display, mainly
contains the following:
● Inverter operation status and information;
● Operating information;
● Warning message and malfunction display.
Explanation
Inverter detects DC input
Low DC input voltage
Grid Connected
Grid Unavailable
Under normal operating
Stop operating
Detected faults or report faults
Under normal operating
Indicator status
●DC
●AC
● NORMAL
● ALARM
on
off
on
off
on
off
on
off
- 07 - - 08 -

● Please select the wall with certain bearing capacity.
● When doing the installation, vertical slope cannot exceed +/-15°.Make sure no lateral
tilt. Otherwise it will affect the function of the heat sink. Cause the output power lower
than expected.
● If install more than one inverter, must leave at least 500mm gap between each inverter.
And each inverter must be at least 500mm above and below. And must install the inverter
at the place where children cannot touch. Please see pic 4.3.
● Consider whether the installation environment is helpful to see the inverter LCD
display and indicator status clearly.
● Must offer a ventilate environment if inverter is installed in the airtight house.
Safety Hints:
Do not place or store any items next to the inverter. Pic4.3 Installation Gap
Pic4.4 Inverter Installation
The inverter is designed according to the wall mounted type installation, please use the
wall mounted (the brick wall of the expansion bolt) when installing.
4.2 Inverter Installation
Pic4.2 Installation Angle
Anchoring
Mounting bracket
M4*14 Stainless steel screws
Inverter
≤15°
≥500mm
≥500mm
- 09 - - 10 -

Inverter should be vertically installed, as shown in pic 4.5,installation procedure show
below:
1. Position the bolts on the appropriate wall according to the bolt positions on the
mounting shelves and mark the holes. On the brick wall, the installation must be suitable
for the expansion bolt installation.
2.Ensure that the position of the installation holes on the wall (A, B, C, D) are the same
position of installation (Picture 4.5), and the mounting level is guaranteed.
3. Hang the inverter to the top of the mounting rack and then use the M4 screw in the
accessory to lock E and F (Picture 4.6) to ensure that the inverter will not move.
NITROX-12,15,20,25KW-3Ph-5G inverter has considered the convenience of the
electrical connection while designing. we design fast connection for both DC and AC ,all
electrical connections conform to the related standards of the country .
In order to safe connection, the electrical connection must follow below steps:
1. Switch AC off
2. Switch DC off
3. Connect the inverter to solar panels
Pic4.5 Inverter hanging plate installation
Pic4.6 Mounting of inverter
5.1 DC input terminal connection
5 Electrical Connection
- 11 - - 12 -

a). Make sure that the polarity of the output voltage of the solar panel is consistent with the
polarity identified by the inverter.
b). Connect DC positive and negative to the inverter input terminal. Figure 5.1 is shown in
figure 5.2.
c).Making DC connection line Strip off the DC wire about 7mm, disassemble the
connector cap nut(see pic5.3).
2). Insert the contact pin into the connector housing until it locks in place. Screw the cap
nut onto the connector housing. Torque to 2.5-3Nm(as shown in pic 5.5).
3).Finally insert the DC connector into the positive and negative input of the inverter,
shown as figure 5.6
1). Crimping metal terminals with crimping pliers as shown in 5.4.
Pic 5.5 connector with cap nut screwed on
Sheet 5.1 Specs of AC cable
Pic 5.6 DC input connection
Pic 5.3 Disassemble the connector cap nut
Pic 5.4 Crimp the contact pin to the wire
2
Traverse area(mm )
Cable type Range
4.0(12AWG) 5.5-9.0
Recommended
size
Outside diameter
of cable(mm)
4.0-6.0
(12-10AWG)
Industry generic PV
cable
(model;PV1-F)
Pic 5.1 DC “+ ”connector (MC4) Pic 5.2 DC“-”connector (MC4)
7mm
7mm
- 13 - - 14 -

NOTE:
Sunlight shines on the panels will generate voltage, high voltage in series
may cause danger to life. Therefore, before connecting the DC input line,
the solar panel needs to be blocked by the opaque material and ensure that
the DC switch is 'OFF', otherwise, the high voltage of the inverter may lead
to life-threatening conditions.
Do not close the DC switch after the DC terminal is connected. Connect the AC terminal
to the AC side of the inverter, the AC side is equipped with three-phase AC terminals that
can be conveniently connected. Flexible cords are recommended for easy installation. The
specifications are as shown in sheet 5.2
1. Matching socket 2.Sleeve 3.Sealing core 4.Sealing nut
Pic 5.7 AC connector structure
The AC output connector is divided into three parts: matching socket, sleeve and sealing
sleeve, as shown in Picture 5.7, the steps are as follows:
Step 1 Remove the cable sealing ring and sleeve in sequence from the AC connector.
Step 2 Use strippers to strip the protective sheet and insulation layer of the AC cable
to the right length, as shown in Picture 5.8.
Step 3: Insert the cable (L1, L2, L3, PE) into the sealing sleeve and sleeve.
Step 4 Use the hexagon screwdriver, loosen the bolts of the socket in turn, and insert
each cable core into the corresponding jack, and set each screw. The connection hole
of AC connection terminal labeling is shown in Picture 5.9.
Warning:
Prohibit using a single circuit breaker for multiple inverters , prohibit the
connection of load between inverter circuit breakers.
Table 5.2 Cable information
Warning:
Be careful to distinguish the L1, L2,L3 and PE of the AC cables.
Outside cable(3+PE)20m Outside cable(3+PE)20m
5.2 DC input terminal connection
Specification
Model NITROX-12,15KW-3Ph-5G
30A/400V
NITROX-20KW/25KW-3Ph-5G
40A/400V
DiaCable item Cable
CSA
Cable
outer
dia
15~18mm2.5mm 6mm
AWG Dia Cable
CSA
10mm10 2.5mm
Cable
outer
dia
AWG
15~18mm 8
2 2
Breaker
Max cable
length
1
2
34
Pic 5.8 Strip AC cable
8~15mm
40mm
- 15 - - 16 -

Good grounding is good for resisting surge voltage surge and improving EMI performance.
Therefore, before connecting AC, DC, and communication cables, you need to ground
the cable firstly. For a single system, just ground the PE cable; For multiple machine
systems, all PE cables of the inverter need to be connected to the same grounding copper
platoon to ensure the equipotential connection. The installation of the shell ground wire
is shown as Picture 5.11.
Inverter has the function of wireless remote monitoring. The inverter with Wifi function
is equipped with Wifi Plug to connect the inverter and network. Wifi Plug's operation,
installation, Internet access, APP downloading and other processes are detailed in the
instructions. Picture 5.12 is the Internet monitoring solution.
5.3 The connection of the ground line
5.4 Inverter monitoring connection
Step 5 Set the sleeve and sealing ring in place
Step 6 Connect the terminals to the inverter as shown in picture 5.10.
Warning:
Inverter has built-in leakage current detection circuit, If an external
leakage current protection device is connected,its operating current
must be greater than 300mA or higher, otherwise 1inverter may not
work properly.
Pic 5.10 AC input connection
Pic 5.9 AC Connector Hole Pattern
Pic 5.11 The installation of the shell ground wire
Safety Hint:
The AC cable line L1 is connected to socket 1; L2 is connected to socket 2;
L3 is connected to socket 3, the PE line is connected to the earth , and does
not involve N wire connections, please do not insert N lines into the socket
of N.
- 17 - - 18 -

When the inverter is out of the factory, the installation location of Wifi
plug is sealed by a sealed plate as shown in Figure 5.13.When installing the Wifi
Plug, remove the sealing plate, replace it with the sealing plate with square hole in
the accessories, and tighten the screws. Insert the Wifi Plug into the interface and
fix it with a screw. The configuration of the WiFi Plug needs to be performed after
various electrical connections have been completed and the inverter DC power on.
When the inverter is on the DC power, it is determined whether the WiFi Plug is
normally electrified (The LED light shines out of the shell).
For the configuration of Wi-Fi Plug,please refer to illustrations of the Wi-Fi Plug.
5.4.1 Installation of Wi-Fi Plug
5.4.2 Configuration of Wi-Fi Plug
Pic 5.12 Internet monitoring solution
Pic 5.13 Wifi Plug installation diagram
PC
Router
WIFI
GPRS
Web Server
Phone
- 19 - - 20 -

6. Startup and Shutdown
6.1 Start up the inverter
6.2 Inverter Shutdown
Before starting the inverter, make sure that the inverter can meet the following conditions,
otherwise it may result in fire or damage to the inverter. In this case,we do not undertake
any responsibility. At the same time, to optimize the system configuration, it is
recommended that the two inputs be connected to the same number of photovoltaic
modules.
When start up the three phase string inverter, should fellow below steps:
1. First switch on the AC breaker.
2. Turn on the dc switch of the photovoltaic module, and if the panel provides
sufficient starting voltage and power, the inverter will start.
3. When the ac voltage and dc voltage are normal, the inverter start-up is ready
to begin. The inverter will first check the internal parameters and the grid parameters,
while the liquid crystal will show that the inverter is self-checking.
4. If the parameter is within acceptable range, the inverter will generate the normal
grid. NORMAL indicator light is on.
Must follow below steps while Shutting down the inverter:
1. Switch off the AC breaker.
2. Wait for 30 seconds, turn off the dc switch (if any), or simply disconnect the dc
input connector. The inverter will close the LCD and all leds within two minutes.
a). The maximum open voltage of each set of photovoltaic modules shall not exceed
600VDC under any conditions.
b). Each input of the inverter must use the same type of photovoltaic module in series.
c). Total output power of pv shall not exceed the maximum input power of inverter,
each photovoltaic modules shall not exceed the rated power of each channel.
d). The short circuit current of each series of photovoltaic modules cannot be greater
than 10A at any time.
- 21 - - 22 -
7. Limiter function (Optional)
When you are reading this, we believe that you have completed the connection
according to the requirements of chapter 5, if you has been running your inverter at
this time, and you want to use the limiter function, please turn off AC and DC switch
of the inverter, and wait for 5 minutes until the inverter completely discharged.
In order to make it easier for you to use the limiter function of the NITROX-12,
15,20,25KW-3Ph-5G, we have specifically given the wiring diagram, as shown in Picture
7.1 Limiter function wiring diagram
The NITROX 12,15,20,25KW-3Ph-5G inverter has external limitier function. This function
is optional. It can collect counter-current power to control the output power of the inverter,
so that the power of inverter and load can be offset, and the excess power will not be fed back
to the grid. If you purchase the inverter with limiter function, a external limiter and three
current senors will be included in the package which is necessary for the function.The external
limiter is shwn as Pic 7.1.You can see corresponding line mark next to the green interface.
The green terminals on the left are the interface of three-phase AC line (L1, L2, L3) and N
Line (N), and the the right are the interface between three sets of current sensor and one set
of control terminals. Limiter will collect voltage and current from these interfaces and send
control signals to the inverter.
Pic 7.1 Limiter view
- 19 - - 20 -
L1 L1(L)L1(K)L2(L)L2(K)L3(L)L3(K) + -L2 L3 N

- 23 - - 24 -
Pic7.3 Clamp Senor
Pic7.4 Clamp Senor internal arrow
(3)After you finish the installation in process 1 and 2, connect the N line (N) to the N
terminal of the limiter and tighten the line.
(4)Connect the control line. There are two numbers 1 and 2 on the interface of limiter,
and the same on the waterproof terminal of the inverter. Twist the waterproof terminal
and connect the red line to number 1 and black line to number 2 shown as the picture.
After that connect the terminal to the interface of the limiter. The other side of the line
should be connected to the control terminal.
L
K
7.2, the red lines connected to the utility grid called wire (L), blue line shows the zero line
(N), yellow green line shows the ground wire (PE). We recommend installing an AC
switch between the inverter outlet and the utility grid, the specs of the AC switchis
determined by the load capacity.
The AC switch we recommend to connect to the inverter output refer to Table 5.2.
7.2 Connect the limiter to inverter
The limiter will measure the voltage and current of three phases separately, and this
manual only introduces the installation steps of one phase, the other two phases are
the same. The specific installation steps are as follows:
(1)Connect limiter to the grid. Connected to the grid is to measure the voltage of grid.
Before connect to the grid, please turn off the switch to avoid the risk of electric shock.
Choose one wire from the bottom of the three-phase DC switch. (any phase of U,V,W)
to connect with L1 terminal, then tighten the line with a screwdriver.
(2)Connect limiter to clamp senor. Clamp senor can measure the current of the AC
side, it should be connected to the front side of the load (domestic appliance ect.) to
achieve this function. Only when the limiter collects the voltage and current of the
same phase can it judge the power of the phase. So the clamp senor should be
connected to the same phase as the before. Open the side buckle of the clamp senor,
then clamp the senor to the AC line on the DC switch, the arrow direction on the senor
should towards that of the load. The clamp senor has two lines (shown as below), and
the white line corresponds to K terminal, black line corresponds to L terminal. Connect
the white line to the L1(L) and L1(K) terminal refer to the line mark of the limiter and
tighten the line with screwdriver. This is the whole installation process of one phase.
U
V
L1(L)
Solar panels
Load
Distribution Box
Limiter
Control signal
L1(K)
L2(L)
L2(K)
L3(L)
L3(K)
L1
L2
L3
N
W
N
Control signal
Pic 7.2 Wiring diagram

- 25 - - 26 -
Pic7.8 Limiter function setting interface
Turn on the anti-backflow function of the inverter refer to the manual , then turn on the
Limiter's power supply, next close the DC switch, and last turn on the inverter.
Press the button of the limiter to the setting interface. Long press the button to switch
the anti-backflow mode. Limiter has two anti-backfolw modes, the minimum mode
and the average mode. In the minimum mode, limiter will control the power of the
inverter according to the phase with the lowest power to ensure that no reverse current
will occur in each phase. In average mode, limiter controls the output of the inverter
according to the average of the total power of the three-phase load, which may cause
single backflow. The controller is produced in the minimum mode to ensure no anti-
backflow happens to the customers.
7.3 Debugging Limiter
MENU》Setup》Run Param
OK Cancel
ActiveP 0%
Reactive 0%
PF -1.000
Fun_ISO OFF
Fun_RCD OFF
SelfCheck OS
Island OFF
Fun_GFDI OFF
Limiter OFF
PowerWH
Factor 0.00
MPPT Num 0
Pic7.5 Waterproof terminal
Pic7.6 Connect limiter to inverter
Pic7.7 Connect terminal to inverter
1 2
limiter
+ -
1
2

Pic8.1 The initial interface
Pic8.2 PV input and DC current information
Press UP or Down you can check inverter DC voltage, DC current, AC voltage, AC
current, inverter temperature, software version information.
You can check the PV information, the number of strings input, MPPT voltage
and MPPT current.
From the initial interface, you can check the current working state and product current
power, today's power generation, total power generation of inverter.And can view
today's power generation trend, the ID number of the inverter and the current power
model of the inverter through the graph.
8.1 The initial interface
During normal operation, the LCD shows the current status of the inverter, including the
current power, total generation, a bar chart of power operation and inverter ID,etc. Press
the Up button and the Down button to see the current DC voltage, DC current, AC
voltage, AC current, inverter radiator temperature, software version number and wifi
connection state of the inverter.
8. General Operation
System param
Running param
Protection param
Comm param
E-Month
E-Day
E-Year
E-History
Test Data
Start
Statistics
Fault Record
ON/OFF
Setup
LCD main menu
AC output data
Temp and
interface
DC input data
Power:
Day :
Total :
State :
Standby 0
0W P - 1 Kw
0 Wh
0 MWh
6 12 18 24
ID:1601012001
0.0Kw SN-01 2019-05-10 08:00:00
PV1 V : 0G.0V I : 0.0A
PV2 V : 0G.0V I : 0.0A
RUN Input
- 27 - - 28 -

Pic8.3 AC running state information
Pic8.4 Temperature and software version
You can check the three phase voltage, current, and grid frequency.
You can check the inverter inside temp, LCD software Ver137 and inverter software
Ver1400. There are two black spot in the bottom right corner. The first flash means
inverter is communicating with LCD. The second flash means LCD is communicating
with wifi plug.
There are four sub menu in the Main Menu.
8.1.1 Main Menu
8.2 Statistics information
Ua : 234.5V Ia : 0.0A
Ub : 234.5V Ia : 0.0A
Uc : 234.5V
Grid Freq : 50.00Hz
Ia : 0.0A
RUN Grid
Pic8.5 Main Menu
Pic8.6 PV input and DC current information
There are five sub menu in the statistics.
You can check the PV information, the number of strings input, MPPT voltage
and MPPT current.
Statistics 《
Fault Record
ON/OFF
Setup
MENU
E-Day E-History
E-Month
E-Month
Test Data 《
MENU》Statistics
Inside Temp. : 25.5℃
Ver0142 Ver1400
RUN Temperature
- 29 - - 30 -

Pic8.7 E-Day Pic8.10 E-History
Pic8.8 E-Month
Pic8.9 E-Year
Pic8.11Test Data
PV1
PV2
HV
GFD
DiL
AVL
126
1k2
: 19186
: 19198
: 19152
: 9119
36:
: -2
: 287
: 6
1k3
1k4
1k5
1k6
vHV
BSn
ofA
ofB
: 11126
: 11140
: 16666
: 2927
ofC
138
139
140
: 2057
: 2248
137 : 2145
: 1497
: 0
: 24362
: 12218
: 2065
: 2653
<2015-2024>
MENU》Statistics》E-History
15
5KWh
16 17 18 19 20 21 22 23 24
2019-04 1-10 20 31 <>
MENU》Statistics》E-Month
01
10MWh
02 03 04 05 06 07 08 09 10
<2019>
MENU》Statistics》E-Year
01
200KWh
02 03 04 05 06 07 08 09 10 11 12
This information is for technician’s reference.
8.3 Fault Record
Only can keep four fault record in the menu include time, customer can deal with it
depends on the error code.
<2019-05-11>
MENU》Statistics》E-Day
0
10MWh
6 12 18 24
- 31 - - 32 -

Pic8.12 Fault Record
MENU》Fault Record
Fault : F352019-05-05 08:38
F352019-05-05 08:37
F352019-04-24 18:47
F352019-04-24 17:54
F352019-04-24 17:53
1
2
3
4
History :
Pic8.13 ON/OFF setting
MENU》ON/OFF
Turn ON
Turn OFF 《
Pic8.14 ON set
MENU》ON/OFF》Turn ON
Turn ON
OK 《
Cancel
Pic8.15 OFF set
MENU》ON/OFF》Turn OFF
Turn OFF
OK 《
Cancel
8.4 ON/OFF setting
Into each submenu through cursor.
8.5 Parameter setting
Setting include system param, run param, protect param, comm.. param. All of these
information for maintenance reference.
- 33 - - 34 -

Pic8.16 setting
Pic8.19 lauguage set
MENU》Setup
System Param 《
Run Param
ParamProtect
ParamComm.
Pic8.17 System Param
MENU》Setup》System Param
Time Set 《
Language Set
Display Set
Factory data reset
Pic8.18 System Param
Time Set
2019-05-11 09:36:30
OK Cancel
Lauguage Set
简体中文
English 《
Pic8.21 Factory data reset set
Display Set
Brightness Delay 《
Delay time 05S
OK Cancel
Factory data reset
Confirm to reset 《
Cancel
8.5.1 System Param
8.5.1.1 Time set
System Param includes time set, language set, display set and factory date reset.
8.5.1.2 Language set
8.5.1.3 Display Set
8.5.1.4 Factory data reset
Pic8.20 Display set
- 35 - - 36 -
This manual suits for next models
7
Table of contents
Other Inverex Inverter manuals
Popular Inverter manuals by other brands

ring
ring PowerSourceProRINV1100 instruction manual

INVT
INVT iMars MG Series Operation manual

Epever
Epever Sunshine Solar IP350-Plus user manual

Morningstar
Morningstar SureSine 150 Installation and operation manual

Helios
Helios RM-PSW5KVA Series instruction manual

Chicago Electric
Chicago Electric Power Systems 97047 Set up and operating instructions