LED Status Indication
LED A
(Green)
LED B
(Red)
The encoder module has 2 LEDs – LED A (Green) and LED B (Red).
LED A indicates power
LED B indicates a wiring fault condition.
The fault code is indicated on the drive display. Please see Error Code
Definitions. For transient faults, the LED will remain illuminated for 50ms to
notify a fault on the module.
Mechanical Installation
Option Module inserted into
Optidrive Option Module Port
(please see diagram opposite).
DO NOT use undue force in inserting
the option module into the options port.
Ensure the option module is fitted
securely before powering on the
Optidrive.
Remove terminal block header from
option module prior to tightening
connections. Replace when wiring is
completed. Tighten to Torque setting
provided in Specifications. 1 2 3 4 5 6
Compliance
Hereby, Invertek Drives Ltd declares that the Optidrive Encoder Interface.
Model Code: OPT-2-ENCOD-IN and OPT-2-ENCHT is in compliance
with Directive 2014/30/EU, 2014/35/EU, 2011/65/EU
The EU declaration of conformity is available on request from your Invertek
Drives Sales Partner.
User Guide
OPTIDRIVE Encoder Interface
Optidrive Encoder Interface Module User Guide | Version 2.00www.invertekdrives.com
Invertek Drives Ltd
Offa’s Dyke Business Park
Welshpool
Powys, UK
SY21 8JF
Ñ82-ENCOD-IN_V2.00PÓ
82-ENCOD-IN_V2.00
Compatibility
This Option is suitable for use on the following product ranges:
Optidrive P2 (ODP-2-.... Drives)
Optidrive Elevator (ODL-2-.... Drives)
Model Code
OPT-2-ENCOD-IN (5 Volt TTL Version)
OPT-2-ENCHT (8 – 30 Volt HTL Version)
Compatible Encoder Types
TTL Version : 5V TTL – A & B Channel with Compliment
HTL Version 24V HTL – A & B Channel with Compliment Note: +24V HTL
encoder requires external supply voltage
Specifications
Power Supply Output: 5V DC @ 200mA Max
Maximum Input Frequency: 500kHz
Environmental: 0◦C - +50◦C
Terminal Torque: 0.5Nm (4.5 Ib-in)
Warranty
Complete Warranty Terms and Conditions are available upon request from
your IDL Authorised Distributor.
Error Code Definitions
The following error codes are related to the encoder operation:
State Indication Indication
Communication loss No communication between the encoder module and the drive.
Please check the module is properly fitted into the slot.
Speed feedback error exceeds level set in P6-07 The estimated motor speed differs from the measured motor speed.
Check encoder connection, wire shielding, and values set in P6-07.
Encoder PPR motor speed mismatch The encoder used must have a PPR value of at least 60.
Motor nameplate RPM must be entered in P1-10.
Encoder Channel A Fault
Error normally caused by encoder wiring error.
Check encoder wiring and commissioning guidelines.
Encoder Channel B Fault
Encoder Channels A & B Faults

Optidrive Encoder Interface Module User Guide | Version 2.00www.invertekdrives.com
Electrical Installation
Overall Shielded twisted paired
cable to be used
Shield should be connected to
Ground (PE) both Ends
Connection Examples
5V TTL Encoder – OPT-2-ENCOD-IN
123456
Minimum
distance
500mm
Encoder
NOTE Do not connect the
encoder cable shield to 0V of
the drive or encoder module.
24V HTL Encoder – OPT-2-ENCHT
123456
Minimum
distance
500mm
Encoder
External
24V supply
+_123456
Minimum
distance
500mm
Encoder
Alternatively (to External supply) the drives on-board 24V supply can
be used (T1 (24V) and T7 (0V)) – Ensure total current consumption
from T1 does not exceed 100mA.
NOTE 0V of encoder must also be connected to drive 0V (T7).
NOTE Do not connect the encoder cable shield to 0V of the drive or
encoder module.
Option Module Connections
Pin Function
1 A Channel (A)
2 A Channel Inverse (/A)
3 B Channel (B)
4 B Channel Inverse (/B)
5 +5V DC Output
6 0 Volt
1 2 3 4 5 6
Operation
Parameter Settings
When operating with an encoder, the following parameter settings are
required as a minimum:
P1-09: Motor rated frequency (found on the motor nameplate).
P1-10: Motor rated speed (found on the motor nameplate).
P6-06: Encoder PPR value (enter value for the connected encoder).
Closed Loop Vector speed provides full torque holding capability at zero
speed and enhanced operation at frequencies below 1Hz. The drive,
encoder module and encoder should be connected according to the
voltage rating of the encoder as shown in the wiring diagrams. The encoder
cable should be an overall shielded type, with the shield bonded to earth at
both ends.
Commissioning
When commissioning, the Optidrive should firstly be commissioned in
Encoder less Vector Speed Control (P6-05 = 0), and a speed / polarity
check should then be made to ensure that the sign of the feedback signal
matches that of the speed reference in the drive.
The steps below show the suggested commissioning sequence, assuming the
encoder is correctly connected to the Optidrive.
1) Enter the following parameters from the motor nameplate:
P1-07 – Motor Rated Voltage
P1-08 – Motor Rated Current
P1-09 – Motor Rated Frequency
P1-10 – Motor Rated Speed
2) To enable access to the advanced parameters required, set P1-14 = 201
3) Select Vector Speed Control Mode by setting P4-01 = 0
4) Carry out an Auto-tune by setting P4-02 = 1
5) Once the Auto-tune is completed, the Optidrive should be run in the
forward direction with a low speed reference (e.g. 2 – 5Hz). Ensure the
motor operates correctly and smoothly.
6) Check the Encoder Feedback value in P0-58. With the Optidrive
running in the forward direction, the value should be positive, and stable
with variation of + / - 5% maximum. If the value in this parameter is
positive, the encoder wiring is correct. If the value is negative, the speed
feedback is inverted. To correct this, reverse the A and B signal channels
from the encoder.
7) Varying the drive output speed should then result in the value of P0-58
changing to reflect the change of the actual motor speed. If this is not the
case, check the wiring of the whole system.
8) If the above check is passed, the feedback control function can be
enabled by setting P6-05 to 1.
123456