Invertek optidrive cp2 User manual

AC Variable Speed Drive
0.75kW –250kW / 1HP –350HP
200 –480 Volt 1 & 3 Phase
Advanced User Guide
Revision 2.00

Optidrive P2 Advanced User Guide Rev 2.00
2
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
This Document is for use with version 1.30 Firmware.
Advanced User Guide Revision 1.20
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date
information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any
contract.
Revision History
Revision
Note
1.00
First Release
1.10
Updated to include V1.20 Firmware changes
Added comms info
Added additional technical specification
Updated parameter descriptions
1.20
Major updated to include V2.00 firmware changes
Additional sections added
Extensive revisions to parameter descriptions, ranges, default values and descritpions
Revised Technical data and explanations
iTHD table added
Motor Performance Data Added
Added Standby Consumption
Added 600 Volt data
Added DC Bus Voltage Thresholds
2.00
Updated to reflect V2.00 firmware enhancements
This user guide is intended to provide technical information and explanation of the operation and parameters of the Optidrive P2 product
range. The information contained withn is intended to reflect the latest available firmware functionality at the time of release. This user guide
must be read in conjunction with the Optidrive P2 User Guide included with each product, and in particular, all relevant safety information and
warnings. The information is intended to reflect the product as accurately as possible, however Invertek Drives accepts no liability for
information contained herein.
This document is intended for persons who are already familiar with the installation, mounting, start-up and operation of the equipment and
the hazards involved. The reader should be trained and in the operation of electrical equipment, and heave the necessary authority to
energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety procedures. In addition, they should
be trained in the proper care and use of protective equipment in accordance with established safety procedures.

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
3
Optidrive P2 Parameter Set Overview
1
1. Optidrive P2 Parameter Set Overview.......................................................................................... 4
1.1. About this section ............................................................................................................................................................... 4
1.2. Parameter Structure Overview ........................................................................................................................................... 4
1.3. Parameter Descriptions ...................................................................................................................................................... 5
1.4. Parameter Group 9 –Programmable Logic Functions ...................................................................................................... 22
1.5. Parameter Group 0 –Monitoring Parameters (Read Only) .............................................................................................. 26
1.6. P6-28 Value Selection ....................................................................................................................................................... 29
1.7. Control Terminal Connections .......................................................................................................................................... 30
2. Drive Model Specific Parameter Variations ................................................................................ 34
2.1. Available Effective Switching Frequency Options ............................................................................................................. 34
2.2. V/F Mode Voltage Boost Setting Options ......................................................................................................................... 35
3. Embedded Firmware Functions.................................................................................................. 36
3.1. 24 Hour Time Clock ........................................................................................................................................................... 36
4. Fieldbus Interface Support......................................................................................................... 37
4.1. Fieldbus Interface Options ................................................................................................................................................ 37
4.2. Fieldbus Support Overview ............................................................................................................................................... 37
4.3. Simple Drive Control ......................................................................................................................................................... 37
4.4. Drive Control Word Definition :- ....................................................................................................................................... 38
4.5. Drive Status Word Definition ............................................................................................................................................ 38
4.6. Parameter Access Overview ............................................................................................................................................. 38
4.7. Parameter Access Tables .................................................................................................................................................. 40
5. Diagnostic and Fault Messages .................................................................................................. 58
6. Rated Temperatures and De-rating curves ................................................................................. 59
6.1. Thermal Management ...................................................................................................................................................... 59
6.2. De-rating Curves Explained ............................................................................................................................................... 59
6.3. Size 2, 200-240V................................................................................................................................................................ 60
6.4. Size 2, 380-480V................................................................................................................................................................ 62
6.5. Size 3, 200-240V & 380 –480V ......................................................................................................................................... 64
6.6. Size 4, 200 –240V & 380-480V, ........................................................................................................................................ 66
6.7. Size 5, 200 –240V & 380-480V, ........................................................................................................................................ 67
6.8. Size 6, 200 –240V & 380-480V, ........................................................................................................................................ 68
6.9. Size 7, 200 –240V & 380-480V, ........................................................................................................................................ 69
7. Immunity Tests ......................................................................................................................... 70
7.1. Electrostatic Discharge (ESD) ............................................................................................................................................ 70
7.2. Electrical Fast Transient Burst (EFT/B) .............................................................................................................................. 70
7.3. Surge ................................................................................................................................................................................. 70
7.4. Dielectric strength (Flash) ................................................................................................................................................. 70
8. General Technical and Performance Data................................................................................... 71
8.1. Electrical Data ................................................................................................................................................................... 71
8.2. Input Output Current Ratings ........................................................................................................................................... 71
8.3. Standby Power Consumption............................................................................................................................................ 74
8.4. DC Bus Discharge Time...................................................................................................................................................... 74
8.5. Earth Leakage Current (Touch Current) ............................................................................................................................ 75
8.6. Digital & Analog I/O .......................................................................................................................................................... 76
8.7. Environmental Data .......................................................................................................................................................... 77
8.8. Response Times ................................................................................................................................................................ 77
8.9. Motor Control Performance ............................................................................................................................................. 77
8.10. Output Current Limit......................................................................................................................................................... 78
8.11. Under / Over Voltage Trip Levels ...................................................................................................................................... 79

Optidrive P2 Advanced User Guide Rev 2.00
4
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
1. Optidrive P2 Parameter Set Overview
1.1. About this section
This document provides a list of the available parameters, and a description of their respective functions, for the Optidrive P2.
1.2. Parameter Structure Overview
The parameter set is arranged in Groups according to the following structure
Parameter Group
Range
Name
Access Level
Access Type
Group 0
P0-01 to P0-50
Basic Monitoring
Extended
Read Only
P0-51 to P0-80
Advanced Monitoring
Advanced
Read Only
Group 1
P1-01 to P1-14
Quick Start Menu
Basic
Read / Write
Group 2
P2-01 to P2-40
Extended Parameters
Extended
Read / Write
Group 3
P3-01 to P3-12
PID Controller
Extended
Read / Write
Group 4
P4-01 to P4-12
Motor Control
Extended
Read / Write
Group 5
P5-01 to P5-10
Communications
Extended
Read / Write
Group 6
P6-01 to P6-30
Advanced Functions
Advanced
Read / Write
Group 7
P7-01 to P7-10
Advanced Motor Data
Advanced
Read / Write
Group 8
P8-01 to P8-10
Application Specific Group
Advanced
Read / Write
Group 9
P9-01 to P9-30
Programmable Logic
Advanced
Read / Write
Access to all parameter groups is controlled by setting P1-14 as follows
P1-14 = P2-40 (Factory setting: 101) Allows Extended Parameter Access
P1-14 = P6-30 (Factory Setting: 201) Allows Advanced Parameter Access

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
5
Optidrive P2 Parameter Set Overview
1
1.3. Parameter Descriptions
1.3.1. Parameter Group 1 –Basic Parameters
Par.
Name
Minimum
Maximum
Default
Units
P1-01
Maximum Frequency / Speed Limit
P1-02
500.0 / 30000
50.0 (60.0)
Hz / Rpm
Maximum output frequency or motor speed limit –Hz or rpm.
If P1-10 > 0, the value entered / displayed is in Rpm
The value which may be entered by the user is limited by the lower of the following :-
5 x P1-09 value
P2-24 / 16
P1-02
Minimum Frequency / Speed Limit
0.0
P1-01
0.0
Hz / Rpm
Minimum speed limit –Hz or rpm.
If P1-10 >0, the value entered / displayed is in Rpm
P1-03
Acceleration Ramp Time
See Below
5.0
Seconds
Acceleration ramp time from 0 to base speed (P-1-09) in seconds.
Note
For Optidrive P2 units Frame Sizes 2 and 3, the parameter range is adjustable between 0.00 and 600.0 seconds
For Optidrive P2 units Frame Sizes 4 and above, the parameter range is adjustable between 0.0 and 6000.0 seconds
P1-04
Deceleration Ramp Time
See Below
5.0
Seconds
Deceleration ramp time from base speed (P1-09) to standstill in seconds. When set to zero, fastest possible ramp time without trip is
activated
Note
For Optidrive P2 units Frame Sizes 2 and 3, the parameter range is adjustable between 0.00 and 600.0 seconds
For Optidrive P2 units Frame Sizes 4 and above, the parameter range is adjustable between 0.0 and 6000.0 seconds
P1-05
Stop Mode
0
4
0
-
This parameter has several functions :-
- To enable / disable the brake chopper during deceleration
- To select the stopping mode (Ramp or Coast)
- To enable the AC Flux Braking function
0 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P1-04 as described
above. In this mode, the drive brake transistor is disabled.
1 : Coast to Stop. When the enable signal is removed, the drive output is immediately disabled, and the motor will coast (freewheel) to
stop. If the load can continue to rotate due to inertia, and the drive may possibly be re-enabled whilst the motor is still rotating, the
spin start function (P2-26) should be enabled. In this mode, the drive brake transistor is disabled.
2 : Ramp To Stop, Brake Chopper Enabled. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by
P1-04 as described above. The brake chopper is also enabled in this mode.
3 : Coast to Stop, Brake Chopper Enabled. When the enable signal is removed, the drive output is immediately disabled, and the
motor will coast (freewheel) to stop. If the load can continue to rotate due to inertia, and the drive may possibly be re-enabled whilst
the motor is still rotating, the spin start function (P2-26) should be enabled. The drive brake chopper is enabled in this mode, however
it will only activate when required during a change in the drive frequency setpoint, and will not activate when stopping.
4 : AC Flux Braking. AC Flux braking provides improved braking torque during stopping and dceceleration. In this mode, the brake
chopper is disabled, however braking torque is improved.
P1-06
Energy Optimiser
0
1
0
-
Only active when enhanced V/F motor control mode is selected (P4-01 = 2).
0 : Disabled
1 : Enabled. When enabled, the Energy Optimiser attempts to reduce the overall energy consumed by the drive and motor when
operating at constant speeds and light loads. The output voltage applied to the motor is reduced. The Energy Optimiser is intended for
applications where the drive may operate for some periods of time with constant speed and light motor load, whether constant or
variable torque.
P1-07
Motor Rated Voltage
0
See Below
See Below
Volts
This parameter should be set to the rated (nameplate) voltage of the motor (Volts)
The factory default setting of this parameter is drive model dependent as follows :-
All kw & HP models intended for 200 –240 volt operation (e.g. ODP-2-x2xxx-xxF4x) : Factory setting = 230 Volts, Maximum 250 Volts
All kW models intended for 380 –480 volt operation (e.g. ODP-2-x4xxx-3KFxN) : Factory setting = 400 Volts, Maximum 500 Volts
All HP models intended for 380 –480 volt operation (e.g. ODP-2-x4xxx-3HFxN) : Factory setting = 460 Volts, Maximum 500 Volts
When this parameter is set to the motor nameplate voltage, the output voltage from the drive is controlled automatically and
maintained at the correct level wherever possible regardless of variations in supply voltage or DC Bus Voltage.
When P1-07 = 0, the voltage compensation function of the inverter is disabled. The output voltage applied to the motor will increase
or decrease with changes in the DC Bus voltage.
Note
The RMS output voltage from the inverter can never exceed the incoming supply voltage.
P1-08
Motor Rated Current
-
-
See Below
Amps
This parameter should be set to the rated (nameplate) current of the motor.
The factory default setting of this parameter is the set to the maximum continuously available output current of the drive

Optidrive P2 Advanced User Guide Rev 2.00
6
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
P1-09
Motor Rated Frequency
10
500
60 (60)
Hz
This parameter should be set to the rated (nameplate) frequency of the motor.
The factory default setting of this parameter is drive model dependent as follows :-
All kW models (e.g. ODP-2-xxxxx-xKFxx) : Factory setting = 50Hz
All HP models (e.g. ODP-2-xxxxx-xHFxx) : Factory setting = 60 Hz
P1-10
Motor Rated Speed
0
30000
0
Rpm
This parameter can optionally be set to the rated (nameplate) rpm of the motor. When set to the default value of zero, all speed
related parameters are displayed in Hz, and the slip compensation for the motor is disabled. Entering the value from the motor
nameplate enables the slip compensation function, and the Optidrive display will now show motor speed in estimated rpm. All speed
related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in Rpm.
Note
When the drive is operated with the optional Encoder Feedback Interface, this parameter must be set to the correct nameplate Rpm of
the connected motor.
P1-11
V/F Mode Voltage Boost
0.0
See Below
See Below
%
This parameter is effective only when operating in V/F Mode (P4-01 = 2).
Voltage boost is used to increase the applied motor voltage at low output frequencies, in order to improve low speed and starting
torque. Excessive voltage boost levels may result in increased motor current and temperature, and force ventilation of the motor may
be required.
An automatic setting () is also possible, whereby the Optidrive will automatically adjust this parameter based on the motor
parameters measured during an autotune.
The factory default and maximum limit for this parameter are drive model dependent, refer to section 0 for further information
P1-12
Primary Command Source Mode
0
6
0
-
0 : Terminal Control. The drive responds directly to signals applied to the control terminals.
1 : Uni-directional Keypad Control 1)2)3) The drive can be controlled in the forward direction only using an external or remote Keypad
2 : Bi-directional Keypad Control 4) The drive can be controlled in the forward and reverse directions using an external or remote
Keypad. Pressing the keypad START button toggles between forward and reverse.
3 : PID Control. The output frequency is controlled by the internal PID controller.
4 : Fieldbus Control. Control via Modbus RTU if no fieldbus interface option is present, otherwise control is from the fieldbus option
module interface
5 : Slave Mode. The drive acts as a Slave to a connected Optidrive operating in Master Mode
6 : CAN bus Control. Control via CAN bus connected to the RJ45 serial interface connector
Note
1) When operating with P1-12 = 1 or 2, the drive will not operate the motor unless the enable signal is present (e.g. Control
Terminals 1 & 2 are linked together), regardless of the setting of P2-37. If P2-37 > = 4, the drive will start when the link is
closed between terminals 1 & 2, and will not require the keypad start button to be pressed. If P2-37 < 4, the Start Button
must be pressed to operate the drive after the link is closed between terminals 1 & 2.
2) The motor direction of rotation may still be controlled by signals applied to the digital inputs, dependent on the setting of
P1-13, e.g. the motor can still be controlled in both forward and reverse directions if required, however the Reverse direction
function of the Start key is disabled.
3) When operating in this mode and utilising a setting of P1-13 that allows preset speeds to be also selected from the drive
digital inputs, setting a negative value in the preset speed parameter will cause the drive to reverse the direction of motor
rotation.
4) When P1-12 = 2, the direction of motor rotation may be changed by any of the following :-
a. Pressing the keypad Start button
b. A Reverse Digital Input, dependent on the setting of P1-13
c. Selecting a Negative Preset Speed
It is important to ensure that a combination of the above used incorrectly does not result in unexpected operation.
P1-13
Digital Inputs Function Select
0
21
1
-
Defines the function of the digital inputs depending on the control mode setting in
P1-12. See section 1.7 on page 30 for further information.
P1-14
Extended Menu Access Code
0
30000
0
-
Parameter Access Control. The following settings are applicable :
P1-14 = P2-40 (Factory Setting = 101) : Allows access to Parameter Groups 0 –5
P1-14 = P6-30 (Factory Setting = 201) : Allows Access to all drive parameters

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
7
Optidrive P2 Parameter Set Overview
1
1.3.2. Parameter Group 2 - Extended parameters
Par.
Name
Minimum
Maximum
Default
Units
P2-01
Preset / Jog Frequency / Speed 1
-P1-01
P1-01
5.0
Hz / Rpm
P2-02
Preset / Jog Frequency / Speed 2
-P1-01
P1-01
10.0
Hz / Rpm
P2-03
Preset / Jog Frequency / Speed 3
-P1-01
P1-01
25.0
Hz / Rpm
P2-04
Preset / Jog Frequency / Speed 4
-P1-01
P1-01
50.0 (60.0)
Hz / Rpm
P2-05
Preset / Jog Frequency / Speed 5
-P1-01
P1-01
0.0
Hz / Rpm
P2-06
Preset / Jog Frequency / Speed 6
-P1-01
P1-01
0.0
Hz / Rpm
P2-07
Preset / Jog Frequency / Speed 7
-P1-01
P1-01
0.0
Hz / Rpm
P2-08
Preset / Jog Frequency / Speed 8
-P1-01
P1-01
0.0
Hz / Rpm
Preset Speeds / Frequencies which may be selected by the digital inputs dependent on the setting of P1-13 (Refer to section 1.7 on
page 30).
If P1-10 = 0, the values are entered as Hz. If P1-10 > 0, the values are entered as Rpm.
Setting a negative value will reverse the direction of motor rotation.
P2-09
Skip Frequency Centre Point
0.0
P1-01
0.0
Hz
P2-10
Skip Frequency Band Width
0.0
P1-01
0.0
Hz
The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency which
causes mechanical resonance in a particular machine. Parameter P2-09 defines the centre point of the skip frequency band, and is
used conjunction with P2-10. The Optidrive output frequency will ramp through the defined band at the rates set by the acceleration
and deceleration ramps currently in use, and will not hold any output frequency within the defined band. If the frequency reference
applied to the drive is within the band, the Optidrive output frequency will remain at the upper or lower limit of the band.
P2-11
Analog Output 1 (Terminal 8) Function Select
0
12
8
-
Digital Output Mode. Logic 1 = +24V DC (20mA Max)
0 : Drive Enabled (Running). Logic 1 when the Optidrive is enabled (Running)
1 : Drive Healthy. Logic 1 When no Fault condition exists on the drive and the STO input is closed.
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency and the drive is enabled.
Hysterisis is applied, defined by P6-04.
3 : Output Frequency > 0.0. Logic 1 when the motor runs above zero speed. Hysterisis is applied, defined by P6-04.
4 : Output Frequency >= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Motor Torque >= Limit. Logic when the motor torque exceeds the adjustable limit
7: Analog Input 2 Signal Level >= Limit. Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
Note : When using settings 4 –7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the value
programmed in P2-17.
Analog Output Mode
8 : Output Frequency (Motor Speed). 0 to P-01
9 : Output (Motor) Current. 0 to 200% of P1-08
10 : Motor Torque. 0 to 200% of motor rated torque
11 : Output (Motor) Power. 0 to 200% of drive rated power
12 : PID Controller Output. 0 –100% of PID Controller Output
P2-12
Analog Output 1 (Terminal 8) Format
-
-
-
= 0 to10V.
= 10 to 0V,
= 0 to 20mA
= 20 to 0mA
= 4 to 20mA
= 20 to 4mA

Optidrive P2 Advanced User Guide Rev 2.00
8
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P2-13
Analog Output 2 (Terminal 11) Function Select
0
12
9
-
Digital Output Mode. Logic 1 = +24V DC
0 : Drive Enabled (Running). Logic 1 when the Optidrive is enabled (Running)
1 : Drive Healthy. Logic 1 When no Fault condition exists on the drive
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency. Hysterisis is applied, defined by
P6-04.
3 : Output Frequency > 0.0. Logic 1 when the motor runs above zero speed. Hysterisis is applied, defined by P6-04.
4 : Output Frequency >= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Output Toque >= Limit. Logic when the motor torque exceeds the adjustable limit
7: Analog Input 2 Signal Level >= Limit. Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
Note : When using settings 4 –7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the value
programmed in P2-17.
Analog Output Mode
8 : Output Frequency (Motor Speed). 0 to P-01
9 : Output (Motor) Current. 0 to 200% of P1-08
10 : Motor Torque. 0 to 200% of motor rated torque
11 : Output (Motor) Power. 0 to 200% of drive rated power
12 : PID Controller Output. 0 –100% of PID Controller Output
P2-14
Analog Output 2 (Terminal 11) Format
-
-
-
= 0 to10V.
= 10 to 0V,
= 0 to 20mA
= 20to 0mA
= 4 to 20mA
= 20 to 4mA
P2-15
User Relay 1 Output (Terminals 14, 15 & 16) Function
select
0
14
1
-
Selects the function assigned to Relay Output 1. The relay has three output terminals, Logic 1 indicates the relay is active, and
therefore terminals 14 and 15 will be closed together.
0: Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2: At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency. Hysterisis is applied, defined by
P6-04.
3 : Output Frequency > 0.0 Hz. Logic 1 when the drive output frequency to the motor is exceeds 0.0Hz. Hysterisis is applied, defined by
P6-04.
4: Output Frequency >= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5: Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit
6: Output Torque >= Limit. Logic 1 when the motor torque exceeds the adjustable limit
7: Analog Input 2 Signal Level >= Limit. 1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
8 : No Function
9 : No Function
10 : Service Due. Logic 1 when the user settable maintenance time (P6-24) has expired. This allows the user to set a service interval
time, for example in the even where a machine requires a defiend service time interval for maintenance, the drive can provide visual
indication of the maintenance interval.
11 : Drive Ready to Run. Defined as not in inhibit mode, hardware enable present, not in mains loss condition and no trip.
12 : Drive Tripped. Logic 1 when the drive has tripped and the display shows a fault.
13 : STO Status. Logic 1 when the STO inputs are present, and the drive is not in inhibit state
Note : When using settings 4 –7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the value
programmed in P2-17.
14 : PID Error >= Limit. Logic 1 when the PID Error exceeds the adjustable threshold
P2-16
Adjustable Threshold 1 Upper Limit (Analog Output 1 /
Relay Output 1)
P2-17
200.0
100.0
%
P2-17
Adjustable Threshold 1 Lower Limit (Analog Output 1 /
Relay Output 1)
0.0
P2-16
0.0
%
Used in conjunction with some settings of Parameters P2-11 & P2-15.

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
9
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P2-18
User Relay 2 Output (Terminals 17 & 18) Function select
0
14
0
-
Selects the function assigned to Relay Output 2. The relay has two output terminals, Logic 1 indicates the relay is active, and therefore
terminals 17 and 18 will be linked together.
0: Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2: At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency. Hysterisis is applied, defined by
P6-04.
3 : Output Frequency > 0.0 Hz. Logic 1 when the drive output frequency to the motor is exceeds 0.0Hz. Hysterisis is applied, defined by
P6-04.
4: Output Frequency >= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5: Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit
6: Output Torque >= Limit. Logic 1 when the motor torque exceeds the adjustable limit
7: Analog Input 2 Signal Level >= Limit. 1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
8 : Hoist Brake Control. When P2-18 = 8, the Optidrive is set to ‘Hoist Mode Operation’, and output relay 2 must be used to control the
motor holding brake.
9 : No Function
10 : Service Due. Logic 1 when the user settable maintenance time (P6-24) has expired. This allows the user to set a service interval
time, for example in the even where a machine requires a defiend service time interval for maintenance, the drive can provide visual
indication of the maintenance interval.
11 : Drive Ready to Run. Defined as not in inhibit mode, hardware enable present, not in mains loss condition and no trip.
12 : Drive Tripped. Logic 1 when the drive has tripped and the display shows a fault.
13 : STO Status. Logic 1 when the STO inputs are present, and the drive is not in inhibit state
Note : When using settings 4 –7, parameters P2-19 and P2-20 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-19, and return to Logic 0 when the signal falls below the value
programmed in P2-20.
14 : PID Error >= Limit. Logic 1 when the PID Error exceeds the adjustable threshold
P2-19
Adjustable Threshold 1 Upper Limit (Analog Output 2 /
Relay Output 2)
P2-20
200.0
100.0
%
P2-20
Adjustable Threshold 1 Lower Limit (Analog Output 2 /
Relay Output 2)
0.0
P2-19
0.0
%
Used in conjunction with some settings of Parameters P2-13 & P2-18.
P2-21
Display Scaling Factor
-30.000
30.000
0.000
-
P2-22
Display Scaling Source
0
3
0
-
P2-21 & P2-22 allow the user to program the Optidrive to display an alternative output unit scaled from an existing parameter, e.g. to
display conveyer speed in metres per second based on the output frequency. This function is disabled if P2-21 is set to 0.
If P2-21 is set >0, the variable selected in P2-22 is multiplied by the factor entered in P2-21, and can be displayed whilst the drive is
running. The display will show a ‘’ on the left hand side to indicate the customer scaled units.
P2-22 Setting Options :-
0 : Motor Speed
1 : Motor Current
2 : Analog Input 2
3 : P0-80 Value
P2-23
Zero Speed Holding Time
0.0
60.0
0.2
Seconds
Determines the time for which the drive output frequency is held at zero when stopping, before the drive output is disabled. This can
be utilised to ensure the motor has come to a complete standstill before the drive switches off, or to allow time for a holding brake to
engage. It is not intended to provide a continuous output holding torque for prolonged periods.
When operating in V/F mode, the output voltage and hence current will be dependent on the setting of P1-11.
When operating in Vector Mode, the output voltage and current are automatically controlled by the vector algorithm.
P2-24
Effective Switching Frequency
See Below
kHz
Effective power stage switching frequency. The range of settings available and factory default parameter setting depend on the drive
power and voltage rating, refer to section 2.1. Higher frequencies reduce the audible ‘ringing’ noise from the motor, and improve the
output current waveform, at the expense of increased drive heat losses.
P2-25
Fast Deceleration Ramp Time (Fast Stop)
0.00
240.0
0.00
Seconds
This parameter allows an alternative deceleration ramp down time to be programmed into the Optidrive, which can be selected by
digital inputs (dependent on the setting of P1-13) or selected automatically in the case of a mains power loss if P2-38 = 2.
When set to 0.00, the drive output will be immediately disabled, and the load will coast to stop.

Optidrive P2 Advanced User Guide Rev 2.00
10
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P2-26
Spin Start Enable
0
2
0
-
0 : Disabled
1 : Enabled. When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control
the motor from its current speed. This can be useful for high inertia loads, or fans which may spin due to air movement even when the
drive is not enabled. A short delay may be observed when starting motors which are not already rotating. The spin start will detect the
motor direction of rotation, and will automatically operate and control the motor from that point, including reversing the direction of
motor rotation where required.
2 : Enabled on Fault, Brown Out or Coast. As setting one, however the Spin Start function activates only following any event that may
have caused an uncontrolled stop of the motor previously.
Note
The Spin Start function cannot detect motors which are rotating at speeds above the maximum speed limit parameter (P1-01) setting
of the drive.
P2-27
Standby Mode Timer
0.0
250.0
0.0
Seconds
This parameter defines time period, whereby if the drive operates continuously at minimum frequency / speed for at least the set time
period, the Optidrive output will be disabled, and the display will show .The function is disabled if P2-27 = 0.0.
If the speed demand rises above minimum, the drive will immediately restart automatically.
P2-28
Slave Speed Scaling Control
0
3
0
-
Active in Slave mode (P1-12=5) only. The Master speed reference can be multiplied by a preset scaling factor or adjusted using an
analog trim or offset.
0 : Disabled. No scaling or offset is applied.
1 : Actual Speed = Master Speed x P2-29
2 : Actual Speed = (Master Speed x P2-29) + Analog Input 1 Reference. Analog Input 1 Full Scale 100.0% = P1-01
3 : Actual Speed = (Master Speed x P2-29) x Analog Input 1 Reference. Analog input 1 full scale = 200.0% (unsigned/absolute)
P2-29
Slave Speed Scaling Factor
-500.0
500.0
100.0
%
Used in conjunction with P2-28.
P2-30
Analog Input 1 (Terminal 6) Format
-
-
-
= 0 to 10 Volt Signal (Uni-polar)
= 10 to 0 Volt Signal (Uni-polar)
= -10 to +10 Volt Signal (Bi-polar)
= 0 to 20mA Signal
= 4 to 20mA Signal, the Optidrive will trip and show the fault code if the signal level falls below 3mA
= 4 to 20mA Signal. In the event that the signal falls below 3mA, the Optidrive will ramp operate at Preset Speed 4.
= 20 to 4mA Signal, the Optidrive will trip and show the fault code if the signal level falls below 3mA
= 20 to 4mA Signal. In the event that the signal falls below 3mA, the Optidrive will ramp operate at Preset Speed 4.
P2-31
Analog Input 1 Scaling
0.0
2000.0
100.0
%
Scales the analog input by this factor. See parameter description below for further information.
P2-32
Analog Input 1 Offset
-500.0
500.0
0.0
%
Sets an offset, as a percentage of the full scale range of the input, which is applied to the analog input signal.
Analog Input Scaling and Offset are applied to the Analog Input Signal as follows :-
Result (%) = (Analog Input Level (%) –Analog Input Offset (%)) x Analog Input Scaling (%)
The resultant value for Analog Input 1 can be displayed in P0-01.
E.g. If the analog Input Signal format is 0 –10 Volts, Offset = 20.0%, Scaling = 50.0%
An analog input signal level of 7 Volts gives the following result :-
Analog Input Level (%) = 7 / 10 = 70.0%
Result = (70.0 –20.0)% X 50.0%) = 25.0%
P2-33
Analog Input 2 (Terminal 10) Format
-
-
-
= 0 to 10 Volt Signal (Uni-polar)
= 10 to 0 Volt Signal (Uni-polar)
= Motor PTC Thermistor Input. The drive will trip if the resistance is greater than 2.5kΩ
= 0 to 20mA Signal
= 4 to 20mA Signal, the Optidrive will trip and show the fault code if the signal level falls below 3mA
= 4 to 20mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA
= 20 to 4mA Signal, the Optidrive will trip and show the fault code if the signal level falls below 3mA
= 20 to 4mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA
P2-34
Analog Input 2 Scaling
0.0
2000.0
100.0
%
Scales the analog input by this factor. See parameter description below for further information.
P2-35
Analog Input 2 Offset
-500.0
500.0
0.0
%
Sets an offset, as a percentage of the full scale range of the input, which is applied to the analog input signal
Analog Input Scaling and Offset are applied to the Analog Input Signal as follows :-
Result (%) = (Analog Input Level (%) –Analog Input Offset (%)) x Analog Input Scaling (%)
The resultant value for Analog Input 2 can be displayed in P0-02.
E.g. If the analog Input Signal format is 0 –10 Volts, Offset = 20.0%, Scaling = 50.0%
An analog input signal level of 7 Volts gives the following result :-
Analog Input Level (%) = 7 / 10 = 70.0%
Result = (70.0 –20.0)% X 50.0%) = 25.0%

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
11
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P2-36
Start Mode Select / Automatic Restart
-
-
-
Defines the behaviour of the drive relating to the enable digital input and also configures the Automatic Restart function.
: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a power
on or reset to start the drive (e.g. Edge Triggered).
: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed before power on.
to : Following a trip, the drive will make up to 5 attempts to restart at intervals defined by P6-03 (default 20 seconds).
The drive must be powered down or reset manually to reset the counter. The numbers of restart attempts are counted, and if the
drive fails to start on the final attempt, the drive will fault with, and will require the user to manually reset the fault.
P2-37
Keypad / Fieldbus Starting Control
0
7
1
-
This parameter controls the starting behaviour of the drive when operating in Keypad Mode or Fieldbus Mode (selected by P1-12).
Settings 0 to 3 are active in Keypad Mode only (P1-12 = 1 or 2), and define the speed at which the drive will initially operate following
the pressing of the keypad Start button.
0 : Minimum Speed, Keypad Start. Following a stop and restart, the drive will always initially run at the minimum speed set in P1-02.
This applies even if the drive is re-enabled whilst still decelerating the motor from the previous stop command.
1 : Previous Operating Speed, Keypad Start. Following a stop and restart, the drive will return to the last keypad setpoint speed used
prior to stopping.
2 : Current Running Speed. Where the Optidrive is configured for multiple speed references, when switched to keypad mode by a
digital input, the drive will continue to operate at the last operating speed. This setting can be used for ‘Bumpless’ changeover
between automatic and manual operating modes of the drive, e.g. typically Hand / Auto control or Local / Remote control.
3 : Preset Speed 8, Keypad Start. Following a stop and restart, the Optidrive will always initially run at Preset Speed 8 (P2-08)
4 : Minimum Speed, Terminal Start. Following a stop and restart, the drive will always initially run at the minimum speed P1-02. The
drive starting is controlled from the digital inputs, based on the setting of P1-13.
5 : Previous Operating Speed, Terminal Start. Following a stop and restart, the drive will return to the last keypad setpoint speed used
prior to stopping. The drive starting is controlled from the digital inputs, based on the setting of P1-13.
6 : Current Running Speed, Terminal Start. Where the Optidrive is configured for multiple speed references (typically Hand / Auto
control or Local / Remote control), when switched to keypad mode by a digital input, the drive will continue to operate at the last
operating speed. The drive starting is controlled from the digital inputs, based on the setting of P1-13.
7 : Preset Speed 8, Terminal Start. Following a stop and restart, the Optidrive will always initially run at Preset Speed 8 (P2-08). The
drive starting is controlled from the digital inputs, based on the setting of P1-13.
P2-38
Mains Loss Ride Through / Stop Control
0
3
0
-
Controls the behaviour of the drive in response to a loss of mains power supply whilst the drive is enabled.
0 : Mains Loss Ride Through. The Optidrive will attempt to continue operating by recovering energy from the motor and connected
load. Providing that the mains loss period is short (e.g. a ‘Brown Out’), the drive enable control remains applied and that sufficient
energy can be recovered before the drive control electronics power off, the drive will automatically maintain motor operation (with
reduced output speed depending on the load), and recover back to the normal operating point on return of mains power.
Where the mains power supply is lost for a longer period (e.g. a ‘Black Out’) and there is insufficient kinetic energy available from the
load to maintain the drive electronic power supply, the restarting behaviour of the drive on return of the power supply will be
controlled by P2-36.
1 : Coast To Stop. On a loss of mains power supply, either ‘Brown Out’ or ‘Black Out’, the Optidrive will immediately disable the output
to the motor, allowing the load to coast or free wheel. When using this setting with high inertia loads, which may still be rotating when
the mains power returns, the Spin Start function (P2-26) should be enabled.
2 : Fast Ramp To Stop. On a loss of mains power supply, either ‘Brown Out’ or ‘Black Out’, the Optidrive will attempt to decelerate the
load to standstill at the rate programmed in the Fast deceleration time (P2-25), by recovering energy from the load. As the speed of
the load approaches zero, if the mains power supply has not been restored, the drive control electronics may power down shortly
before the load reaches a complete standstill. If the power returns whilst the drive is still decelerating the load, and the run signal is
maintained, the drive will resume operation and accelerate the load back to the operating speed.
3 : DC Power Supply. This option should be used where the drive is powered via the DC Bus terminals only, and no AC supply is
present.
P2-39
Parameter Access Lock
0
1
0
-
0 : Unlocked. All parameters can be accessed and changed
1 : Locked. Parameter values can be displayed, but cannot be changed
P2-40
Extended Parameter Access Code Definition
0
9999
101
-
Defines the access code which must be entered in P1-14 to access parameter groups above Group 1.

Optidrive P2 Advanced User Guide Rev 2.00
12
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
1.3.3. Parameter Group 3 –PID Control
Par.
Name
Minimum
Maximum
Default
Units
P3-01
PID Proportional Gain
0.1
30.0
1.0
-
PID Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in response to small changes in
the feedback signal. Too high a value can cause instability
P3-02
PID Integral Time Constant
0.0
30.0
1.0
Seconds
PID Controller Integral Time. Larger values provide a more damped response for systems where the overall process responds slowly
P3-03
PID Differential Time Constant
0.00
1.00
0.00
Seconds
PID Differential Time Constant
P3-04
PID Operating Mode
0
1
0
-
0 : Direct Operation. Use this mode if an increase in the motor speed should result in an increase in the feedback signal
1 : Inverse Operation. Use this mode if an increase in the motor speed should result in a decrease in the feedback signal
P3-05
PID Reference (Setpoint) Source Select
0
2
0
-
Selects the source for the PID Reference / Setpoint
0 : Digital Preset Setpoint. P3-06 is used
1 : Analog Input 1 Setpoint
2 : Analog Input 2 Setpoint
P3-06
PID Digital Reference (Setpoint)
0.0
100.0
0.0
%
When P3-05 = 0, this parameter sets the preset digital reference (setpoint) used for the PID Controller
P3-07
PID Controller Output Upper Limit
P3-08
100.0
100.0
%
Limits the maximum value output from the PID controller
P3-08
PID Controller Output Lower Limit
0.0
P3-07
0.0
%
Limits the minimum output from the PID controller
P3-09
PID Output Limit Control
0
3
0
-
0 : Digital Output Limits. The output range of the PID controller is limited by the values of P3-07 & P3-08
1 : Analog Input 1 Provides a Variable Upper Limit. The output range of the PID controller is limited by the values of P3-08 & the signal
applied to Analog Input 1
2 : Analog Input 1 Provides a Variable Lower Limit. The output range of the PID controller is limited by the signal applied to Analog
Input 1 & the value of P3-07
3 : PID output Added to Analog Input 1 Value. The output value from the PID Controller is added to the speed reference applied to the
Analog Input 1
P3-10
PID Feedback Signal Source Select
0
5
0
-
0 : Analog Input 2
1 : Analog Input 1
2 : Motor Current. The feedback value is scaled such that 100.0% = P1-08
3 : DC bus voltage. The feedback is scaled such that 100.0% = 1000 Volts
4 : Differential : Analog input 1 –Analog input 2. PID Feedback = P0-01 –P0-02, limited to 0.0 minimum value
5 : Largest Value : Analog Input 1 or Analog Input 2.
P3-11
Maximum PID Error to Enable Ramps
0.0
25.0
0.0
%
Defines a threshold PID error level, whereby if the difference between the setpoint and feedback values is less than the set threshold,
the internal ramp times of the drive are disabled. Where a greater PID error exists, the ramp times are enabled to limit the rate of
change of motor speed on large PID errors, and react quickly to small errors.
Setting to 0.0 means that the drive ramps are always enabled. This parameter is intended to allow the user to disable the drive internal
ramps where a fast reaction to the PID control is required, however by only disabling the ramps when a small PID error exists, the risk
of possible over current or over voltage trips being generated are reduced.
P3-12
PID Feedback Value Display Scaling Factor
0.000
50.000
0.000
-
Applies a scaling factor to the displayed PID feedback, allowing the user to display the actual signal level from a transducer, e.g. 0 –10
Bar etc. The value is displayed with an ‘r’ prefix, to one decimal place.
P3-13
PID Error Wake Up Level
0.0
100.0
5.0
%
Sets a programmable level whereby if the drive enters standby motor whilst operating under PID control, the difference between the
setpoint and the selected feedback signal increase beyond this threshold before the drive will return to normal operation.
P3-18
PID Reset Control
0
1
0
-
This parameter is used to control the reset behaviour of the PID controller.
0 : Continuous Run. In this mode, the PID controller operates continuously, regardless of the operating state of the drive. This can
result in the output of the PID controller integrating up to the maximum limit prior to the drive being enabled.
1 : Reset On Disable. In this mode, the PID controller output is reset to zero when the drive is disabled, and restarts when the drive is
enabled.

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
13
Optidrive P2 Parameter Set Overview
1
1.3.4. Parameter Group 4 –High Performance Motor Control
Par.
Name
Minimum
Maximum
Default
Units
Incorrect adjustment of parameters in menu group 4 can cause unexpected behaviour of the motor and any connected machinery.
It is recommended that these parameters are only adjusted by experienced users.
P4-01
Motor Control Mode
0
6
2
-
Selects the motor control method. An autotune must be performed if setting 0 or 1 is used.
0 : IM Motor Vector Speed Control with Torque Limit. Suitable for use with AC induction motors, Vector Speed Control Mode provides
greater low speed torque, and improved motor speed regulation with respect to load changes. The drive primarily operates in Speed
Control Mode, where the motor speed is controlled by the chosen setpoint source. When the output torque level approaches the
maximum limit, the drive will reduce the motor speed in attempt to reduce the torque demand required. The factory parameter
settings allow a fixed maximum torque limit of 200% set in parameter P4-07. Alternative torque limit settings and variable torque
limits may be selected using P4-06 and P4-07.
1 : IM Motor Vector Torque Control with Speed Limit. Suitable for use with AC induction motors, when Vector Torque Control Mode is
selected, the drive primarily operates in Torque Control Mode, where the motor attempt to generate the output torque level required
by the torque setpoint source. This will generally cause the motor to accelerate in speed. When the output speed approaches the
maximum limit, the drive will not accelerate beyond this point. The speed limit source should be selected by using P1-12 and P1-13,
and the torque reference source should be set in P4-06.
2 : Speed Control (Enhanced V/F). This operating mode is suitable for general purpose operation of standard induction motors.
3 : PM Motor Vector Speed Control. Equivalent to setting 0, but intended for operation of Permanent Magnet motors.
4 : PM Motor Vector Torque Control. Equivalent to setting 1, but intended for operation of Permanent Magnet motors.
5 : BLDC Motor Speed Control. For operation of Brushless DC Motors.
6 : SynRel Motor Speed Control. For operation of Synchronous Reluctance Motors.
Note
Options 3 to 6 are only available when Advanced Parameter Access has been set.
P4-02
Motor Parameter Auto-tune Enable
0
1
0
-
When set to 1, the drive immediately carries out an autotune to measure the motor parameters for optimum control and efficiency.
Following completion of the autotune, the parameter automatically returns to 0.
Note
All motor nameplate data should be programmed into the drive, e.g. P1-07, P1-08, P1-09 and P4-05 prior to starting the autotune
Whilst the autotune does not require the motor to rotate, it may still cause some movement of the motor shaft,
thereby it is important to ensure that the motor and load are safe to operate prior to starting the autotune.
The autotune does not require the load to be removed from the motor, however the motor brake should be
released providing it is safe to do so.
P4-03
Vector Speed Controller Proportional Gain
0.1
400.0
50.0
%
Sets the proportional gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes (P4-
01 = 0 or 1). Higher values provide better output frequency regulation and response. Too high a value can cause the speed to
overshoot the setpoint during acceleration, and may also cause speed instability and possibly over current trips. For applications
requiring best possible performance, the value should be adjusted to suit the connected load by gradually increasing the value and
monitoring the actual output speed of the load until the required dynamic behaviour is achieved with little or no overshoot of the
target speed during acceleration and deceleration.
In general, higher friction loads can tolerate higher values of proportional gain, and high inertia, low friction loads may require the gain
to be reduced.
P4-04
Vector Speed Controller Integral Time Constant
0.000
2.000
0.100
Seconds
Sets the integral time for the speed controller. Smaller values provide a faster response in reaction to motor load changes, at the risk
of introducing instability. For best dynamic performance, the value should be adjusted to suit the connected load.
P4-05
Motor Power Factor Cos Ø
0.00
0.99
-
-
When operating in Vector Speed or Vector Torque motor control modes, this parameter must be set to the motor nameplate power
factor before an autotune is carried out.
P4-06
Torque Control Reference / Limit Source
0
5
0
-
When P4-01 = 0, this parameter defines the source for the maximum output torque limit.
When P4-01 = 1, this parameter defines the source for the torque reference (setpoint).
0 : Fixed Digital. The torque controller reference / limit is set in P4-07
1 : Analog Input 1. The output torque is controlled based on the signal applied to Analog Input 1, whereby 100% input signal level will
result in the drive output torque being limited by the value set in P4-07.
2 : Analog Input 2. The output torque is controlled based on the signal applied to Analog Input 2, whereby 100% input signal level will
result in the drive output torque being limited by the value set in P4-07.
3 : Fieldbus. The output torque is controlled based on the signal from the communications Fieldbus, whereby 100% input signal level
will result in the motor output torque being set or limited to motor rated torque.
4 : Master. The output torque is controlled based on the signal from the Master when operating in Master / Slave mode.
5 : PID Controller Output. The output torque is controlled based on the output of the PID controller, whereby 100% input signal level
will result in the drive output torque being limited by the value set in P4-07.
P4-07
Maximum Motoring Torque Limit
P4-08
500.0
150.0
%
When operating in Vector Speed or Vector Torque motor control modes (P4-01 = 0 or 1), this parameter defines the maximum torque
limit or reference used by the drive in conjunction with P4-06.

Optidrive P2 Advanced User Guide Rev 2.00
14
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P4-08
Minimum Motoring Torque Limit
0.0
P4-07
0.0
%
Active only in Vector Speed or Vector Torque motor control modes (P4-01 = 0 or 1). Sets a minimum torque limit, whereby the when
the Optidrive is enabled, it will always attempt to maintain this torque on the motor at all times whilst operating.
NOTE : This parameter should be used with extreme care, as the drive output frequency will increase to achieve the torque level,
and may exceed the selected speed reference
P4-09
Generator Mode Maximum Torque Limit (Maximum
Regenerative Torque)
0.0
500.0
100.0
%
Active only in Vector Speed or Vector Torque motor control modes. Sets the maximum regenerating torque allowed by the Optidrive
P4-10
V/F Characteristic Adjustment Frequency
0.0
100.0
0.0
%
Entered as a percentage value of P1-09.
When operating in V/F mode (P4-01 = 2), this parameter in conjunction with P4-11 sets a frequency point at which the voltage set in
P4-11 is applied to the motor. Care must be taken to avoid overheating and damaging the motor when using this feature.
P4-11
V/F Characteristic Adjustment Voltage
0.0
100.0
0.0
%
Entered as a percentage of P1-07. Used in conjunction with parameter P4-10
P4-12
Motor Thermal Memory Retention
0
1
0
-
0 : Disabled. The present value of the motor overload accumulator is not stored during power off.
1 : Enabled. The value of the motor thermal overload accumulator is stored during power off.
Whilst the motor is being operated, the drive continuously monitors the output current over a time period, to determine the likely
operating temperature of the motor. If the motor operates at high current for a period of time, the drive may trip to protect the motor
and prevent damage. When this function is disabled (default setting), removing the power supply from the drive will result in the
thermal overload value for the motor being reset to zero, hence the motor could potentially be operated and damaged. By enabling
this parameter, even if the mains power is removed from the drive, the value is retained, and reused at the next power on, in order to
avoid the risk of damage to the motor.
P4-13
Output Phase Sequence
0
1
0
-
0 : U, V, W.
1 : U, W, V. Direction of motor rotation when operating in a forward direction will be reversed.
Note:
When an encoder is used, it may be necessary to reverse the encoder connections for correct operation if this parameter is changed.

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
15
Optidrive P2 Parameter Set Overview
1
1.3.5. Parameter Group 5 –Communication Parameters
Par.
Name
Minimum
Maximum
Default
Units
P5-01
Drive Fieldbus Address
0
63
1
-
Sets the fieldbus address for the Optidrive
P5-02
CAN Open Baud Rate
125
1000
500
kbps
Sets the baud rate when CAN Open communications are used
P5-03
Modbus RTU Baud Rate
9.6
115.2
115.2
kbps
Sets the baud rate when Modbus RTU communications are used
P5-04
Modbus Data Format
-
-
-
-
Sets the expected Modbus telegram data format as follows
: No Parity, 1 stop bit
: No parity, 2 stop bits
: Odd parity, 1 stop bit
: Even parity, 1 stop bit
P5-05
Communications Loss Timeout
0.0
5.0
2.0
Seconds
Sets the watchdog time period for the communications channel for fieldbus systems where the drive must monitor for loss of
communications with the network master, e.g. Modbus RTU. If a valid telegram is not received by the Optidrive within this time
period, the drive will assume a loss of communications has occurred and react as selected below. Setting to zero disables the
function.
P5-06
Communications Loss Action
0
3
0
-
Controls the behaviour of the drive following a loss of communications as determined by the above parameter setting.
0 : Trip & Coast To Stop
1 : Ramp to Stop Then Trip
2 : Ramp to Stop Only (No Trip)
3 : Run at Preset Speed 8
P5-07
Fieldbus Ramp Control
0
1
0
-
Selects whether the acceleration and deceleration ramps are control directly via the Fieldbus, or by internal drive parameters P1-03
and P1-04.
0 : Disabled. Ramps are control from internal drive parameters
1 : Enabled. Ramps are controlled directly by the Fieldbus
P5-08
Fieldbus Process Data Output Word 4 Select
0
7
0
-
When using an optional fieldbus interface, this parameter configures the parameter source for the 4th process data word transferred
from the drive to the network master during cyclic communication.
0 : Output Torque –0 to 2000 = 0 to 200.0%
1 : Output Power –Output power in kW to two decimal places, e.g. 400 = 4.00kW
2 : Digital Input Status –Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
3 : Analog Input 2 Signal Level –0 to 1000 = 0 to 100.0%
4 : Drive Heatsink Temperature –0 to 100 = 0 to 100°C
5 : User Register 1
6 : User Register 2
7 : P0-80 Value
P5-12
Fieldbus Process Data Output Word 3 Select
0
7
0
-
When using an optional fieldbus interface, this parameter configures the parameter source for the 3rd process data word transferred
from the drive to the network master during cyclic communications
0 : Motor current –Output current to 1 decimal place, e.g. 100 = 10.0 Amps
1 : Power (x.xx kW) Output power in kW to two decimal places, e.g. 400 = 4.00kW
2 : Digital input status –Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
3 : Analog Input 2 Signal Level - 0 to 1000 = 0 to 100.0%
4 : Drive Heatsink Temperature –0 to 100 = 0 to 100°C
5 : User register 1 –User Defined Register 1 Value
6 : User register 2–User Defined Register 1 Value
7 : P0-80 value –User Selected data value –see section 0
P5-13
Fieldbus Process Data Input Word 4 Select
0
1
0
-
When using an optional fieldbus interface, this parameter configures destination for the 4th process data word received by the drive
from the network master during cyclic communications
0 : Fieldbus Ramp Control –This option must be selected if the drive acceleration and deceleration ramps are to be controlled from
the fieldbus. P5-07 must also be set to 1 to enable this function.
1 : User register 4 –The value received by the drive in PDI 4 is transferred to User Register 4. This option allows the function of the
process data word to be defined in Parameter Group 9. In this case, User Register 4 should not be written to within any Function
Block code, although the value can be read. Refer to section 1.4 for further information.

Optidrive P2 Advanced User Guide Rev 2.00
16
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
P5-14
Fieldbus Process Data Input Word 3 Select
0
2
0
-
When using an optional fieldbus interface, this parameter configures destination for the 3rd process data word received by the drive
from the network master during cyclic communications
0 : Torque limit/reference –This option must be selected if the drive output torque limit / setpoint is to be controlled from the
fieldbus. This also requires setting P4-06 = 3.
1 : User PID reference register –This option allows the setpoint to the PID controller to be received from the Fieldbus. In order for
this option to be used, P9-38 must be set to 1, and the PID User setpoint must not be utilised within any Function Block Code.
2 : User register 3 -The value received by the drive in PDI 3 is transferred to User Register 3. This option allows the function of the
process data word to be defined in Parameter Group 9. In this case, User Register 3 should not be written to within any Function
Block code, although the value can be read. Refer to section 1.4 for further information.
P5-15
Modbus Response Delay
0
16
0
Chr
Allows the user to configure an additional delay between the drive receiving a request via the Modbus RTU interface, and
transmitting a reply. The value entered represents the delay in addition to the minimum delay permissible according to the Modbus
RTU specification, and is expressed as the number of additional characters.

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
17
Optidrive P2 Parameter Set Overview
1
1.3.6. Parameter Group 6 –Advanced Functions
Par.
Name
Minimum
Maximum
Default
Units
P6-01
Enable Firmware Upgrade
0
3
0
-
Enables the firmware upgrade mode, allowing the User Interface firmware and/or the Power Stage Control firmware to be upgraded.
Options are:
0 : Disabled
1 : Upgrade User Interface and Power Stage Control firmware
2 : Upgrade User Interface firmware only
3 : Upgrade Power Stage Control firmware only
NOTE
This parameter should not be adjusted by the User. The firmware upgrade process is carried out fully automatically using Optitools
Studio PC software.
P6-02
Automatic Thermal Management Minimum Switching
Frequency
4
Model
Dependent
4
kHz
This parameter defines the minimum effective switching frequency which the drive will use.
During operation, the drive measures the power module temperature and will switch automatically to a lower switching frequency if
the temperature reaches a pre-defined limit. This parameter determines the lowest frequency that can be used. In the event that the
power module temperature continues to increase, the drive will trip on over temperature.
P6-03
Auto Reset Time Delay
1
60
20
s
Sets the delay time which will elapse between consecutive drive reset attempts when Auto Reset is enabled in P2-36
P6-04
Relay Output Hysteresis Control
0.0
25.0
0.3
-
This parameter works in conjunction with P2-11 and P2-13 = 2 or 3 to set a band around the target speed (P2-11 = 2) or zero speed
(P2-11 = 3). When the speed is within this band, the drive is considered to be at target speed or Zero speed. This function is used to
prevent “chatter” on the relay output if the operating speed coincides with the level at which the digital / relay output changes state.
e.g. if P2-13 = 3, P1-01 = 50Hz and P6-04 = 5%, the relay contacts close above 2.5Hz
P6-05
Encoder Speed Feedback Enable
0
1
0
-
0 : Disabled
1 : Enabled. Setting to 1 enables encoder control mode of operation, which requires an optional encoder feedback interface. For
correct operation, ensure that the encoder has been properly fitted to the motor and its wiring is connected to the encoder feedback
module in accordance with the Encoder Feedback Interface User Guide. Before enabling this parameter, ensure that the sense of
rotation is correct by using parameter P0-57 (encoder feedback speed) while running in V/f mode. The sign in P0-57 should match that
of the speed reference.
P6-06
Encoder PPR
0
65535
0
-
When using the optional encoder feedback interface (OPT-2-ENCOD), this parameter should be set to the number of Pulses Per
Revolution for the connected encoder. This value has to be set correctly to guarantee proper operation of the drive when Encoder
feedback mode is enabled (P6-05 = 1). Improper setting of this parameter could cause the loss of control of the drive and / or a trip. If
set to zero, encoder feedback will be disabled.
P6-07
Speed Error Trip Level
0.0
100.0
5.0
%
When operating in vector mode, this parameter defines the maximum permissible error between the commanded motor speed and
the esitamed or measured motor speed. This provides protection against overspeeding or loss of motor control. If the speed error
exceeds this limit, the drive will trip. When set to zero, this protection is disabled.
P6-08
Maximum Speed Reference Frequency
0
20
0
kHz
When the motor speed reference is to be controlled by a frequency input signal (connected to Digital input 3), this parameter is used
to define the input frequency which corresponds to the maximum motor speed (set in P1-01). This maximum frequency that can be
set in this parameter must be in the range 5kHz to 20kHz.
When set to 0, this function is disabled.
P6-09
Speed Droop Control
0.0
25.0
0.0
%
This parameter only applies when the drive is in vector speed control mode. (P4-01=0, 3, 4,5, 6) When set to zero, the speed droop
control function is disabled. If P6-09 > 0, this parameter effectively defines a slip speed at motor rated output torque.
The droop speed is the percentage value of P1-09. Depending on the motor load condition, the reference speed will be reduced by a
certain droop value before goes into speed controller, calculated as shown below:
Droop speed = P6-09 * P1-09
Droop value = Droop speed * ( Motor real torque / Motor rated torque)
Speed controller input = Speed reference –Droop value
Droop control can be used to provide a small reduction in motor speed in proportion to the applied load. This can be especially useful
where multiple motors drive a common load, and the load should be shared evenly between the motors.
The real time droop value may be viewed in P0-62.
P6-10
Enable Function Block Program Operation
0
1
0
-
0 : Function Block Program Disabled.
1 : Function Block Prgram Enabled. This parameter must be set to 1 to enable any Function Block Program loaded into the drive to
operate. When set to 0, the Function Block Program will be disabled.
P6-11
Speed Holding Time on Enable
0
250
0
s
Defines a time period for which the drive will run at Preset Speed 7 (P2-07) when the Enable signal is applied to the drive. The preset
speed can be any value from minimum to maximum frequency and in either direction. This function can be useful in applications
requiring controlled start-up behaviour regardless of the normal system operation, and allows the user to program the drive to always
start at the same frequency, with the same direction of rotation for a specified time period before returning to normal operation.

Optidrive P2 Advanced User Guide Rev 2.00
18
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P6-12
Speed Holding / DC Injection Time on Disable
0
250
0
s
When P6-18 = 0, defines a time period for which the drive will run at Preset Speed 8 (P2-08) following removal of the Enable signal,
before ramping to stop.
Note
Setting this parameter > 0 will result in the drive continuing to operate for the set time at the preset speed after the enable signal has
been removed. It is important to ensure this method of operation is safe prior to using this function.
When P6-18 > 0 and Hoist Mode is not enabled (P2-18 ≠ 8), a DC Current, which may be adjusted using P6-18 is injected into the motor
for the time set by this parameter when stopping, which can be useful to ensure the motor has completely stopped.
P6-13
Hoist Mode : Brake Release Time
0.0
5.0
0.2
s
Sets the time for which the drive will hold at the Brake Release Speed (set in P2-07 - Preset Speed 7) to allow the motor brake to
release.
P6-14
Hoist Mode : Brake Apply Time
0.0
5.0
0.3 –0.5
s
Sets the time for which the drive will hold at the Brake Apply Speed (set in P2-08 - Preset Speed 8) to allow the motor brake to engage.
For vertical hoist applications this value should not be set below the time required for the brake to engage (brake response time, as
specified by the brake manufacturer). The minimum time is 0.1s.
P6-15
Hoist Mode : Brake Release Torque Threshold (Torque
Prove)
0.0
200.0
8.0
%
Sets the torque level, as a % of the nominal motor torque, which must be generated prior to the drive Output Relay 2 closing to signal
the motor holding brake to release. This is used to ensure the motor is connected and that sufficient torque has been generated to
prevent the load dropping on release of the mechanical brake. The torque threshold function is not active in V/f mode.
P6-16
Hoist Mode : Torque Threshold Timeout
0.0
25.0
5.0
s
Sets the time for which, following a start command, the drive will attempt to apply enough torque to the motor to reach the hoist
torque probe level (P6-15). Should the torque probe level not be reached within the set time the drive will trip.
P6-17
Maximum Torque Limit Timeout
0.0
25.0
0.0
Hz/Rpm
Sets the maximum time allowed for the motor to be operating at the motor/generator torque limit (P4-07/P4-09) before tripping. This
parameter is enabled only for vector control operation.
P6-18
DC Injection Braking Current
0.0
100.0
0.0
%
Defines the DC current level as a percentage of motor rated current (P1-08) that is applied to the motor when a stop command is
received and the DC Injection function is activated.
P6-19
Brake Resistor Resistance Value
See Below
200
See Below
Ohms
Sets the brake resistor value in Ohms. This value is used for the brake resistor thermal protection.
P6-20
Brake Resistor Power Rating
0.00
200.00
See Below
kW
Sets the brake resistor power in kW, with a resolution of 0.1kW. This value is used for the brake resistor thermal protection.
The thermal protection allows 10 x P6-20 for 5 seconds within a 50 second period, or 50 x P6-20 for 1 second within 50s.
P6-21
Brake Chopper under Temperature Duty Cycle
0.0
20.0
2.0
%
This parameter defines the duty cycle applied to the brake chopper whilst the drive is in an under temperature trip state. A brake
resistor can be mounted to the drive heat sink, and used to maintain the drive temperature above the minimum operating
temperature. This parameter should be used with extreme care, as incorrect adjustment may result in exceeding the rated power
capacity of the resistor. External thermal protection for the resistor should always be used to avoid this risk.
P6-22
Cooling Fan Runtime Counter Reset
0
1
0
-
0 : No Function
1 : Reset. Setting to 1 resets the internal Fan run-time counter to zero (as displayed in Index 1 of P0-35).
P6-23
Energy Consumption (kWh) Meter Reset
0
1
0
-
0 : No Function
1 : Reset . Setting to 1 resets internal kWh meter to zero (as displayed in Index 1 of P0-26 and Index 1 of P0-27).
P6-24
Maintenance Time Interval
0
60000
0
Hours
Allows the user to define a maintenance interval period for the application. This defines the total number of run time hours which
must elapse before the service indicator is displayed. This may be viewed on the drive OLED display, may be programmed to a relay
output, and also sets a bit in the drive status word.
When P6-25 is set to 1, the internal service interval counter is set to this value
P6-25
Maintenance Time Reset
0
1
0
-
When this parameter is set to 1, the internal service interval counter is set to the value defined in P6-24
P6-26
Analog Output 1 Scaling
0.0
500.0
100.0
%
Defines the scaling factor as a % used for Analog Output 1
P6-27
Analog Output 1 Offset
-500.0
500.0
0.0
%
Defines the offset as a % used for Analog Output 1
P6-28
P0-80 Display Value Index
0
200
0
-
This parameter defines the index of the internal variable, the value of which will be displayed in P0-80.
This is usually used in conjunction with the Function Block Program. Refer to section 1.6 for further information.
P6-29
Save User Parameters as Default
0
2
0
-
0 : No Function
1 : Save Parameters. Setting this parameter to 1 saves the present drive parameter settings to the User Default Parameters Memory.
Following this, if the User carries out a 3-button default parameter command (UP, DOWN and STOP), the parameter saved at this time
will be restored.
2 : Erase Parameters. Setting 2 clears the User Default Parameters Memory.

Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
19
Optidrive P2 Parameter Set Overview
1
Par.
Name
Minimum
Maximum
Default
Units
P6-30
Advanced Parameter Access Code Definition
0
9999
201
-
Defines the access code which must be entered into P1-14 to allow access to the Advanced Parameters.
1.3.7. Parameter Group 7 –Motor Data
The following parameters are used internally by the drive to provide optimum possible motor control. Incorrect setting of the
parameters can result in poor performance and unexpected behaviour of the motor. Adjustments should only be carried out by
experienced users who fully understand the functions of the parameters.
Par.
Name
Minimum
Maximum
Default
Units
P7-01
Motor Stator Resistance (Rs)
-
-
-
Ohms
Motor stator resistance value measured during the autotune.
P7-02
Motor Rotor Resistance (Rr)
-
-
-
Ohms
For induction motors: phase to phase rotor resistance value in ohms.
P7-03
Motor Stator Inductance (Lsd)
-
-
-
H
For induction motors: phase stator inductance value.
For permanent magnet motors: phase d-axis stator inductance in Henry (H).
P7-04
Motor Magnetising Current (Id rms)
0.0
-
-
A
For induction motors: magnetizing / no load current. Before Auto-tune, this value is approximated to 60% of motor rated current (P1-
08), assuming a motor power factor of 0.8.
P7-05
Motor Leakage Coefficient (Sigma)
-
-
-
-
For induction motors: motor leakage inductance coefficient
P7-06
Motor Stator Inductance : PM Motors (Lsq)
0
-
-
-
For permanent magnet motors: phase d-axis stator inductance in Henry (H).
P7-07
Enhanced Generator Mode
0
1
0
-
Valid in vector control mode only, provides improved performance and control of the motor when operating in regenerative mode at
low speed.
P7-08
Motor Parameter Adaptation Enable
0
1
0
-
0 : Disabled
1 : Enabled. For Induction motors only and effective in vector control mode (P4-01 = 0 or 1), allows the stator resistance to be adapted
during normal operation to compensate for increase in the moror temperature.
P7-09
Over Voltage Current Limit
0.0
100.0
5.0
%
Effective in vector speed control mode only, and will come into function once the drive DC bus voltage increases above a preset limit.
This voltage limit is set internally just below the over voltage trip level. This parameter will effectively limit the output torque current
in order to prevent a large current flowing back to the drive, which may cause an Over-voltage trip. A small value in this parameter will
limit the motor control torque when the drive DC bus voltage exceeds the preset limit. A higher value may cause a significant
distortion in the motor current, which may cause an aggressive, rough motor behaviour.
P7-10
System Inertia Constant
0
600
10
-
System Load Inertia to Motor Inertia Ratio entered as H = (JTot / JMot). This value can normally be left at the default value (10) and is
used by the drive control algorithms as a feed-forward control variable to provide optimum torque current to accelerate the load.
Hence accurate setting of the inertia ratio will produce a better system response and dynamic behaviour.
P7-11
Pulse Width Minimum Limit
0
500
-
-
This parameter is used to limit the minimum output pulse width, which can be used for long motor cable applications. Increasing the
value of this parameter will reduce the risk of over-current trips, but will also reduce the maximum available output motor voltage.
P7-12
V/F Mode / PM Mode Magnetising Period
0
5000
-
ms
Defines the delay time between the output stage enabling at 0.0Hz prior to the output frequency beginning to ramp to accelerate the
motor. In V/F mode, this allows time for the motor to correctly magnetise, and avoids possible over current trips that may occur if the
output frequency begins to ramp before the motor flux has stabilised.
In IM vector mode, this function is automatically handled through the vector control algorithm.
In PM and BLDC modes, this time is again used, and provides the same function, allowing alignment of the rotor flux prior to
accelerating the motor, and again can help avoid over current trips.
P7-13
Vector Speed Control Derivative Gain
0.0
400.0
0.0
%
Sets the differential gain (%) for the speed controller in vector mode operation.
P7-14
Low Frequency Torque Boost
0.0
100.0
0.0
%
Effective in all motor control modes, except V/F mode (P4-01 = 2), but primarily intended for use with synchronous motors.
Allows a boost current to be applied at start-up and low frequency (limit defined by P7-15), as a percentage of the motor rated current
(P1-08). Injecting some additional current into the motor at low speed helps to ensure that the rotor alignment is maintained,
imrpoving operation of the motor at lower speeds.
In order to determine the correct setting, run the drive at the lowest frequency required by the application and increase boost levels
to provide both required torque and smooth operation whilst avoiding excessive current levels which may cause nuisance tripping.
P7-15
Torque Boost Frequency Limit
0.0
50.0
0.0
%
Frequency range for applied boost current (P7-14) as a % of motor rated frequency (P1-09). This sets the frequency cut-off point above
which boost current is no longer applied to the motor.

Optidrive P2 Advanced User Guide Rev 2.00
20
www.invertekdrives.com
Optidrive P2 Parameter Set Overview
1
P7-16
PM Motor Signal Injection Enable
0
3
0
-
Enables signal injection for use with PM motors. A high frequency signal is injected into the motor at a level defined by P7-17. The
information derived from this signal is then used to determine the motor speed more accurately when operating at low or zero speed,
improving operation without the need for a feedback encoder.
0: Disabled
1: Enabled During Magnetizing Period
2: Enabled During Low Speed Operation
3: Enabled During Magnetizing Period and Low Speed Operation
P7-17
PM Motor Signal Injection Level
0.0
100
0
%
Sets the signal level used during the signal injection function in P7-17. If the value is too high, the drive may trip with over current.
P7-18
Over Modulation Enable
0
1
0
-
0: Disabled
1 : Enabled. When enabled, over modulation provides a small increase in the available output voltage from the drive, which can assist
in applications where the supply voltage is too low to provide the required motor voltage, resulting in an increased motor current.
Table of contents