IOTA D-48-T User manual

D-48-T
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and 48VDC emergency sources by turning off the A.C. branch circuit,
48VDC system, and by disconnecting the unit connector.
3. DO NOT USE OUTDOORS. The D-48-T is for use with grounded, UL Listed, indoor fixtures except in
heated air outlets or hazardous locations.
4. The D-48-T requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
5. Do not mount near gas or electric heaters.
6. The D-48-T should be mounted in locations and at heights where it will not readily be subjected to tamper-
ing by unauthorized personnel.
7. The D-48-T will cold strike and operate
one
2´ through 5´ instant start, rapid start, U shape or circline, T8
through T12 fluorescent lamps, including energy saving and long 4 pin compacts. The D-48-T operates the
lamp at full light output.
8. The D-48-T is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts
with one lamp operating in the emergency mode.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
10. Do not use this equipment for other than intended use.
11. Install in accordance with the National Electrical Code and local regulations.
12. Installation and servicing should be performed by qualified personnel.
13. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility
before final installation.
SAVE THESE INSTRUCTIONS
Page 2
BLACK
A.C. BALLAST
HOT A.C. LINE
(COMM) WHT
➀
WHITE
➀
Select proper voltage lead.Cap unused lead.
(120V) BLK
(277V) ORG
TEST SWITCH
COMMON
WALL SWITCH
INSTALLATION INSTRUCTIONS
CAUTION: Before installing,make certain the A.C.power is off and the D-48-T unit connector is disconnected.
1. LAMPSOPERATED
The D-48-T can be used with most 2´-5´ lamps. If you have any questions regarding specific lamps, contact
CustomerService.
2. MOUNTINGTHE D-48-T
Remove the ballast channel cover.Mount theD-48-T in the ballast channel at least 1/2″away from the A.C.ballast(s).
When the D-48-T is remote mounted, the remote distance can not exceed 1/2of the distance from ballast to lamp
specified by the A.C.ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no more
than 25′remote distance, then the D-48-T should not exceed 121/2′.Under no circumstances should
the D-48-T exceed a distance of 50′from the lamp.
3. WIRING
Refertothewiringdiagramsonthebackpagefortheappropriatewiringoflamp(s)andballast.Installinaccordance
withtheNationalElectricalCodeand local regulations.Foradditional wiring diagramsconsultCustomer Service.
4. WIRINGTHE D-48-T
A. The D-48-T and A.C. ballast
must
be on the same branch circuit.
B. The D-48-T requires an
unswitched
A.C. power source of either 120 or 277 volts. Select the proper voltage
lead and cap the unused lead.
C. When the D-48-T is used with a switched fixture, the A.C. input to the D-48-T must be connected ahead of the
fixture switch. Refer to
Illustration 1
for switched and unswitched fixture wiring diagrams.
Illustration 1
Switched Fixture
BLACK A.C. BALLAST
HOT A.C. LINE
(COMM) WHT
➀
WHITE
➀
Select proper voltage lead.Cap unused lead.
(120V) BLK
(277V) ORG
TEST SWITCH
COMMON
Unswitched Fixture
D-48-T D-48-T
Page 3
5. LABELS
Attach the appropriate labels adjacent to the Test Switch if required.Annotate Re-lamping label for lamp type and
wattage.The Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone
attempting to service the fixture.
6. COMPLETINGINSTALLATION
When installation is complete, switch the A.C. power on and the 48VDC system power on and join the D-48-T
unit connector.
OPERATION
Normal Mode – A.C.power is present.The A.C.ballast operates the fluorescent lamp(s) as intended.The D-48-T is in
the standby mode.
Emergency Mode –The A.C.power fails.The D-48-T senses the A.C.power failure and automatically switches to the
Emergency Mode
.When the A.C.power is restored, the D-48-T switches the system back to the
Standby Mode
.See
page 1 of the Instruction Manual.
TESTING & MAINTENANCE
The D-48-T is a maintenance free unit, however, periodic inspection and testing is required, NFPA 101.Life Safety Code,
outlinesthe following schedule.
Monthly – Conduct a 30 second discharge test. One lamp should operate at full output.
Annually – Conduct a full 11/2hour discharge test.The unit should operate as intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.
Page 4
TYPICAL WIRING DIAGRAMS
For wiring diagrams of ballasts not shown, consult our Customer Service.
Rev.062706
68337-001
1. ONE LAMP RAPID START BALLAST
2.TWO LAMP RAPID START BALLAST
3.TWO LAMP RAPID START BALLAST
4. THREE LAMP RAPID START BALLAST
5. ONE LAMP INSTANT START BALLAST
6. TWO LAMP INSTANT START BALLAST
7. THREE LAMP INSTANT START BALLAST
8. FOUR LAMP INSTANT START BALLAST
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE
BLUE
RED
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➀
➁
➁
➀
A.C.
Ballast
VIOLET
BROWN
+ –
48VDC
EMERGENCY
BALLAST
VIOLET
BROWN
+ –
48VDC
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE
BLUE
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➀
➁
EMERGENCY
BALLAST
VIOLET
BROWN
+ –
48VDC
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE/WHT
BLUE/WHT
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast
BLUE
BLUE
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➀
➁
EMERGENCY
BALLAST
VIOLET
BROWN
+ –
48VDC
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BLUE BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➀
➁
➂
➁
➀
A.C.
Ballast
➂
RED
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
EMERGENCY
BALLAST
VIOLET
BROWN
+ –
48VDC
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BLUE
BLUE
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast
➂
➀
➁
➂
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
EMERGENCY
BALLAST
VIOLET
BROWN
+ –
48VDC
➀
➁
➂
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BLUE
BLUE
BLUE
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast ➂
EMERGENCY
BALLAST
VIOLET
BROWN
+ –
48VDC
➀
➁
➂
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE RED
RED
BLUE
BLUE
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast
➂EMERGENCY
BALLAST
D-48-T
D-48-T
D-48-T
D-48-T
D-48-T
D-48-T
D-48-T
48VDC +
–
ORG
BLK
WHT
BLUE
BLU/WHT
RED/WHT
RED
YELLOW
CONNECTION
➀
➁
➀
48VDC +
–
ORG
BLK
WHT
BLUE
BLU/WHT
RED/WHT
RED
YELLOW
CONNECTION
➀
➁
➀
➀
CAP ALL UNUSED LEADS
MATE CONNECTOR FOR DC OPERATION
➁
LAMP
LAMP
EMERGENCY
BALLAST
EMERGENCY
BALLAST
9. DC OPERATION ONLY
D-48-T
D-48-T
VIOLET
BROWN
+ –
48VDC
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE
BLUE
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➀
➁
EMERGENCY
BALLAST
D-48-T

Other IOTA Controllers manuals

IOTA IQ-TURBO User manual

IOTA

IOTA IQ-TURBO User manual

IOTA ILB-CP-HE User manual

IOTA

IOTA ILB-CP-HE User manual

IOTA 924 Series User manual

IOTA

IOTA 924 Series User manual

IOTA IQ-AGM User manual

IOTA

IOTA IQ-AGM User manual

IOTA ETS-STEP User manual

IOTA

IOTA ETS-STEP User manual

Popular Controllers manuals by other brands

Fuji Electric MICREX-SX series user manual

Fuji Electric

Fuji Electric MICREX-SX series user manual

Emerson Fisher FIELDVUE DVC6000 HW2 instruction manual

Emerson

Emerson Fisher FIELDVUE DVC6000 HW2 instruction manual

Accurex Temperature Interlock Installation, operation and maintenance manual

Accurex

Accurex Temperature Interlock Installation, operation and maintenance manual

Eltako FSSA-230V instruction manual

Eltako

Eltako FSSA-230V instruction manual

Geco GC202 Installation, operating and maintenance manual

Geco

Geco GC202 Installation, operating and maintenance manual

Savant SSC-W485 Quick reference guide

Savant

Savant SSC-W485 Quick reference guide

Nortech CRC200+ Quick installation guide

Nortech

Nortech CRC200+ Quick installation guide

Mitsubishi Electric FX3U-1PSU-5V installation manual

Mitsubishi Electric

Mitsubishi Electric FX3U-1PSU-5V installation manual

National Instruments IC-3120 Getting started guide

National Instruments

National Instruments IC-3120 Getting started guide

omal automation AE 10 instruction manual

omal automation

omal automation AE 10 instruction manual

SpaNet SV4 troubleshooting guide

SpaNet

SpaNet SV4 troubleshooting guide

SLV Elektronik EASY LIM PRO RF 350mA operating manual

SLV Elektronik

SLV Elektronik EASY LIM PRO RF 350mA operating manual

StetSom SX2 Alcance Control user manual

StetSom

StetSom SX2 Alcance Control user manual

gefran SIEIDrive AVy Series Quick start up guide

gefran

gefran SIEIDrive AVy Series Quick start up guide

Zmotion XPLC864E manual

Zmotion

Zmotion XPLC864E manual

Vents RS-1-0,5 manual

Vents

Vents RS-1-0,5 manual

Trinamic TMCM-342 manual

Trinamic

Trinamic TMCM-342 manual

Zamel RNK-02 quick guide

Zamel

Zamel RNK-02 quick guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.