IPAS DaliControl gc16 Service manual

Operating and mounting instructions
DaliControl gc16 Order number: 4101-145-11
IPAS GmbH / Rev.1.1
1/4
General use
The IPAS DALI Gateway DaliControl gc16 is a device used to control ECGs with a DALI interface (in accordance with EN 62386) via the
KNX installation bus. The device transforms switch and dim commands from the connected KNX system into DALI telegrams and status
information from the DALI bus into KNX telegrams.
The DaliControl gc16 is a so-called category 1 device (according to EN 62386-103). This means the device must only be used in DALI
segments with connected ECGs and not with other DALI control devices within the segment (no multi-master operation). The required
power supply for the up to 64 connected ECGs comes directly from the DaliControl gc16. An additional DALI power supply is not required
and not permitted.
The device comes in a 4TE wide DIN Rail casing so it can be directly integrated into the mains distribution box.
In addition to the pure gateway function, the DaliControl gc16 also offers numerous
additional functions
•Addressing of up to 16 DALI groups
•Flexible DALI commissioning concept in the ETS5
•Coloured light control with the help of device type 8 ECGs
•Coloured light control depending on ECG sub-type:
Colour temperature(DT-8 Sub-Type Tc)
XY colour (DT-8 Sub-Type XY)
RGB (DT-8 Sub-Type RGBWAF)
HSV (DT-8 Sub-Type RGBWAF)
RGBW (DT-8 Sub-Type RGBWAF)
The DT-8 sub-type PrimaryN is not supported.
•Support of time scheduling programmes to control groups according to values
and/or colour.
•Different operating modes such as permanent mode, night-time mode or stair-
case mode
•Integrated operating hours counter for each group with an alarm for when the
maximum life-span has been reached
•Individual fault recognition with objects for each light/ECG
•Complex fault analysis at group/device level with number of faults and fault rate calculation
•Fault threshold monitoring with individually configurable threshold values
•Scene module for extensive scene programming
•“Quick exchange function“ for easy replacement of individual faulty ECGs
•Manual control of group and broadcast telegrams via control buttons on the device (see application program description for operating
instructions)
•Signalling of a fault status via LEDs on the device (see application program description)
DALI devices for individual battery emergency lights of device type DT-1 can be read by DaliControl gc16 and switched and controlled via
DALI telegrams. However, DALI commands to start and export test results are not supported. We recommend using the DaliControl e64
for DT-1 devices.
The special surface for the configuration of DALI segmentes is designed as DCA (Device Control App) for the ETS5.
Please remember to install the corresponding etsapp in addition to the product database knxprod. The etsapp is available for download on
the IPAS website or from Konnex.
Device types and accessories
At present the following DaliControl device types are available:
DaliControl gc16 Order number: 4101-145-11
DaliControl e64 Order number: 4101-145-01

Operating and mounting instructions
DaliControl gc16 Order number: 4101-145-11
IPAS GmbH / Rev.1.1
2/4
Scope o delivery
The following individual components are included in the delivery of the DaliControl gc16 device:
•Complete device with connected bus connector
•1x heat shrinkable tubing 1.2 x 2cm for additional insulation of the bus cable
•Operating and mounting instructions
•Delivered in break-proof individual packaging
Application programs
At present the following application programs are available for the DaliControl gc16 device:
DaliControl gc16-01-0110
For function of the application program see application program description.
Installation advice
•Risk of death by electric shock
•The device is intended for interior installation in dry rooms.
•The device must only be installed and commissioned by an accredited electrical engineer.
•Please follow country-specific safety and accident prevention rules as well as all current KNX guidelines.
•Please follow country-specific rules and regulations for the planning and construction of installations, especially with regard to emergen-
cy lighting systems.
•For the installation, the device must be switched to zero potential.
•Do not open the device! Faulty devices must be returned to the manufacturer.
Technical data
Power supply
•Operating voltage 110 to 240 V, 50 to 60Hz AC or DC
•Maximum power consumption 9W, average power consumption 5W
•Bus power supply via KNX bus line, SELV 24V, ca. 5mA
Connectors
•Mains connector L N PE: Screw connector 3x 1- 2.5mm² single or threaded core
•DALI-Bus D+, D- : Screw connector 2x 1-2.5 mm² single or threaded core
•Bus line: Bus connector KNX, screwless 0.6…0.8mm, single core
Control elements
•Programming button to toggle between normal and addressing mode of the KNX
•1 x button Man. to activate manual mode
•8x buttons to toggle between groups in manual mode and to execute broadcast and service functions
•
Display elements
•LED red: Indicates normal/addressing mode
•LED red/green/blue: Indicates manual mode and error message
•8x LED red: Indicates group status and error messages
DALI-Bus output
•Connection of up to 64 ECGs in accordance with EN 62386
•DALI voltage ca. 16 VDC, short circuit proof max. 250mA, basic insulation (no SELV)
•Category-1 device (in accordance with EN 62386-103). No other control devices (DALI-Master) must be used.

Operating and mounting instructions
DaliControl gc16 Order number: 4101-145-11
IPAS GmbH / Rev.1.1
3/4
•Additional DALI power supply is not required or permitted.
Mechanical data
•DaliControl e64 casing: Plastic ABS – V0
•Dimensions REG casing 4TE:
Width: 72mm
Height: 55mm
Length: 86mm
•Weight: ca. 150 g
•Mounting: 35mm DIN rail
Electrical safety
•Pollution class: 2
•Protection type (in accordance with EN 60529): IP20
•Protection type (in accordance with IEC 1140) I
•Overvoltage category: III
•KNX bus: SELV DC 24 V
•DALI bus: 16V DC, 250mA basic insulation (no SELV)
EMC requirements
Complies with EN40428, EN61000-6-2 and EN61000-6-3
Environmental conditions
•Weather resistance: EN60721-3-3 class 3k5
•Environmental conditions during operation: -5°C to +45°C
•Storage temperature -25°C bis +70°C
•Rel. humidity (non condensing): 5 % to 93 %
Certification
KNX certified
CE-signage
According to EMC guidelines (residential and commercial buildings), low voltage guidelines

Operating and mounting instructions
DaliControl gc16 Order number: 4101-145-11
IPAS GmbH / Rev.1.1
4/4
Location and unction o display and control elements
The device connectors as well as the programming button and programming LED that are required for KNX commissioning, are only ac-
cessible in the distribution box when the cover is removed.
The buttons required to activate manual control and to operate groups and commands as well as the status and control LEDs are accessi-
ble when the cover is closed.
A1: Mains connection
A2: DALI output
A3: KNX bus connector
A4: Programming button normal/addressing mode
A5: Programming LED to display normal/addressing mode
A6: Operating button/signal LED RGB manual mode
A7: 8x operating button/signal LED red group control/status,
broadcast and service functions
You must always follow the pin assignment as labelled on the casing!
Mounting and wiring
As an REG device the DaliControl gc16 is suitable for mounting in distribution boxes on 35 mm DIN rails. To mount the device it must be
angled to slide onto the DIN rail from above and then locked into place with a downward movement. Please make sure that the security
latch at the bottom side of the device snaps into place and that the device is firmly attached to the rail.
To dismount the device, the security latch can be pulled downwards with a suitable tool and then the device can be removed from the rail.
After the device has been inserted, the cable for the DALI bus should be attached to the upper left connector first. In accordance with EN
62386, the DALI control lines can be carried in a 5-wired cable together with the power supply (simple basic insulation is sufficient). How-
ever, please make sure that these are labelled clearly. For the entire DALI installation of a segment, a maximum cable length of 300m
must not be exceeded. (Recommended cross-sectional area 1.5mm²).
The power supply is connected to the top left-hand side connector in the order indicated on the casing.
To connect the KNX cable, a standard bus connector is plugged into the respective entry on the device. Attention: Please make sure
that there is double basic insulation between the KNX installation and the power supply. To do so, please insulate the wires of
the KNX cable up to the bus connector with the enclosed shrinkable tubing.
Once the connection is complete and the power supply is turned on, you can start commissioning the DALI segment and programming
with ETS. For all further processes, please see the application program description.
Table of contents
Other IPAS Gateway manuals
Popular Gateway manuals by other brands

Planet
Planet Content Security Gateway CS-500 user manual

NetComm Wireless
NetComm Wireless NF18ACV Setup guide

NetComm Wireless
NetComm Wireless NF18ACV user guide

Wifx
Wifx Lorix One user manual

ZyXEL Communications
ZyXEL Communications USG-100@USG-200 - V2.20 ED 2 manual

RTA
RTA 460ESMS-NNA1 Product user guide