ALIGNMENT PROCEDURE
The alignment between the emitting and the receiving units is necessary to obtain the correct functioning
of the light curtain.
The alignment is perfect if the optic axes of the first and the last emitting unit’s beams coincide with the optic
axes of the corresponding elements of the receiving unit. Two yellow LED indicators (HIGH ALIGN, LOW
ALIGN) facilitate the alignment procedure.
Correct alignment procedure
When the mechanical installation and the electrical connections have been effected –as explained inthe
previous paragraphs –it is possible to carry-out the alignment of the safety light curtain, according to the
following procedure:
•Disconnect the power supply to the light curtain.
•Press the TEST/START button and keep it pressed (open the contact).
•Re-connect the power supply.
•Release the TEST/START button.
•Check the green LED on the bottom of the TX unit (POWER ON) and the yellow LED (NORMAL
OPERATION); if they are ON, the unit is running correctly.
•Verify that one of the following conditions is present on the RX unit:
1. Red LED (SAFE) ON: non-alignment condition.
2. Green LED (NORMAL OPERATION) ON: light curtain already aligned condition; in this case also the
two yellow LEDs will be ON (HIGH ALIGN, LOW ALIGN).
•Continue with the following steps to change from condition 1 to condition 2:
A Keep the receiving unit in a steady position and set the transmission unit until the yellow LED on
the bottom (LOW ALIGN) is ON. This condition shows the effective alignment of the first lower
beam.
B Rotate the transmission unit until the upper yellow LED (HIGH ALIGN) is ON; in this condition red
LED (SAFE) must turn off and green LED (NORMAL OPERATION) must turn ON.
Note: ensure that the green LED (NORMAL OPERATION) modo is ON and steady.
C Delimit the area in which the green LED (NORMAL OPERATION) is steady through some micro
adjustments - for the first and then for the second unit - then place both units in the centre of this
area.
•Fix the two units firmly using pins and brackets.
•Disconnect the power supply to the light curtain.
•Re-connect the power supply.
Verify that the green LED is ON on the RX unit (condition where the beams are free, NORMAL OPERATION)
and verify that, if even one single beam is obscured, the green LED turns OFF and the red LED turns ON
(condition where an object has been detected, SAFE).