iRZ 500 Series User manual

IRZ 500
VARIABLE SPEED DRIVE
«QUICK START»
INSTALLATION MANUAL
2019

IRZ 500 QUICK START
2
Contents
1 GENERAL PROVISIONS FOR WORK WITH THE PRODUCT....................................................................3
1.1 Safety measures ..........................................................................................................................3
1.2 Installation of VSD .......................................................................................................................3
1.3 Technical characteristics..............................................................................................................3
1.4 Description of VSD design ...........................................................................................................5
1.5 VSD operation at environment temperature variations .............................................................6
2. INTENDED USE....................................................................................................................................7
2.1 Operations with the drive controller...........................................................................................7
3 PROCEDURE OF DRIVE OPERATION ..................................................................................................13
3.1 Preparation of the drive ............................................................................................................13
3.2 Emergency actions.....................................................................................................................15
ANNEX А- IRZ-500 MENU STRUCTURE................................................................................................17
ANNEX B - RECOMMENDED IRZ-500 DRIVE CONNECTION DIAGRAM ................................................18

IRZ 500 QUICK START
3
1 GENERAL PROVISIONS FOR WORK WITH THE PRODUCT
1.1 Safety measures
1.1.1 All dismounting, installation, start and adjustment works shall be performed according to the
applicable “Safety Standards for Users of Electrical Installations” and “Maintenance Rules for
Users of Electrical Installations” and applicable departmental regulations.
1.1.2 Grounding and safety measures shall be performed according to requirements of applicable
“Rules for Electrical Equipment Installation”.
1.1.3 When installed in the place, the drive shall be grounded by a steel grounding conductor with
cross section not less than 75 mm2. The grounding conductor shall be connected to the drive’s
terminal for external protective conductor; the connection shall be a bolted or welded joint. The
joint shall be protected against corrosion.
ATTENTION! WHEN INSTALLING THE DRIVE, CHECK THAT THE 480V, 50
Hz 3-PHASE SUPPLY LINE AND LOAD LINE ARE CORRECTLY CONNECTED
TO THE DRIVE INPUT AND OUTPUT TERMINALS.
1.1.4 Before starting the drive, check and if necessary tighten the fastening of components,
conductors and contact connections of the main circuit.
ATTENTION! WHEN THE Q1 SWITCH IS IN OFF STATE, VOLTAGE REMAINS
ACROSS THE ХТ1, ХТ2, AND ХТ3 TERMINALS, AS WELL AS ACROSS
TERMINALS OF THE Q1, SF1, AND SF2 SWITCHES, RU1…RU3 OUTPUTS AND
ELECTRICAL ENERGY METER (WHEN INCLUDED)
1.1.4 Before to perform any works inside the drive:
-shut down power, and disconnect and ground the external leading-in cables.
-put up warning posters
1.2 Installation of VSD
1.2.1 The environment shall be inexplosive, free from current-conducting dust and have type II
atmosphere as per GOST 15150.
1.2.2 The unit shall be positioned vertically; the slant from the vertical shall not exceed 5 degrees.
1.2.3 It is not allowed to install the drive under an overhead power transmission line.
1.2.4 The drive must not be operated without proper grounding.
1.2.5 The drive shall be installed on a foundation or pedestal that prevents from flooding or snowdrift.
The drive shall be fixed to the foundation or pedestal with bolts using holes in the mounting frame.
1.2.6 Before the start of operation, be sure to familiarize yourself with the operating manual for the
IRZ-500 drive.
1.3 Technical characteristics
1.3.1 Characteristics of the various versions of the drive are given in table 1.1.

IRZ 500 QUICK START
4
Table 1.1
Name
Main circuit
rated current, А
Total output power
(at rated input
voltage of 480 V and
frequency of 50/60
Hz), kV·А
Recommended rated
power of the
connected motor (at
rated input voltage of
480 V and frequency
of 50/60 Hz), kW
Motor type
IRZ-510-хх-100
100
80
35
Induction
IRZ-510-хх-160
160
120
60
IRZ-511-хх-250
250
190
90
IRZ-512-хх-400
400
300
150
IRZ-513-хх-630
630
480
210
IRZ-514-хх-800
800
600
270
IRZ-515-хх-1000
1000
800
360
IRZ-516-хх-1200
1200
900
480
IRZ-517-хх-1400
1400
1100
540
IRZ -518-хх-1600
1600
1200
600
IRZ -540-хх-100
100
80
35
Induction or permanent
magnet
IRZ -540-хх-160
160
120
60
IRZ -541-хх-250
250
190
90
IRZ -542-хх-400
400
300
150
IRZ -543-хх-630
630
480
210
IRZ -544-хх-800
800
600
270
IRZ -545-хх-1000
1000
800
360
IRZ -551-хх-160
160
120
60
Permanent magnet
IRZ -551-хх-250
250
190
90
IRZ -552-хх-400
400
300
150
IRZ -553-хх-630
630
480
210
IRZ -554-хх-800
800
600
270
IRZ -555-хх-1000
1000
800
360

IRZ 500 QUICK START
5
1.4 Description of VSD design
1.4.1 The drive constitutes a metallic cabinet that can be accessed on two sides.
Functionally the drive consists of a power section and control system.
1.4.2 The connection of the drive to the power supply network and to the load is made inside the main
circuit I/O compartments located on the rear side of the cabinet.
1.4.3 On the rear side of the cabinet, there are also compartments for connection to a telemechanics
system and to the step-up transformer Y-point, and a compartment of the frequency inverter.
1.4.4 The operator’s panel is located inside a separate lockable compartment on the front side of the
cabinet.
1.4.5 Design and operation of the control system
1.4.5.1 The control system consists of control units and IRZ-500 drive controller (hereinafter referred to
as “controller”).
1.4.5.2 The operator’s panel includes the following controls and indicators:
- Incoming power circuit breaker;
- controller with a USB connector for connection of USB-flash devices;
- three-position switch of operation modes (see table 1.2);
- “~220 V, 50 Hz” receptacle for geophysical instruments;
- circuit breakers: Light, Receptacle, Controller, Heating, Venting, DHS (see figure 1.1);
- electrical energy meter (optional)
Figure 1.1 –Plate of automatic circuit breakers on the operator’s panel
Table 1.2
Position of
operation mode
switch
VSD operation
mode
Motor start/
shut-down via
START/STOP
buttons
Motor remote
start via RS485
interface
Motor auto-
restart
AUTO
Automatic control
mode
+
+
+ *
MANUAL
Manual control
mode
+
+ **
-
NO
Motor start blocking
mode
-
-
-
* - when there is no auto-restart blocking
** - when the relevant setting in the “Additional settings” menu is selected

IRZ 500 QUICK START
6
1.4.5.3 The plate (fig. 1.1) on the operator’s panel of the IRZ-500 drive is for understanding the purpose
of the automatic circuit breakers:
“220V, 10A” receptacle
To switch on the drive controller
To switch on the drive lighting circuit
To switch on the heating circuit
To switch on the fan circuit
To switch on the downhole sensor system power
circuit
1.5 VSD operation at environment temperature variations
1.5.1 A temperature control system is used to ensure operability of the drive within the given operating
temperatures range. This system ensures operating temperature inside the drive cabinet. Depending
on the heatsink temperature, the drive can be in several states in accordance with table 1.3.
Table 1.3
Drive temperature
Drive condition
below minus 20 °С
Heating of the drive and controller is turned on, the inverter and
controller are deactivated. Start is impossible.
from minus 20 °С to
minus 5 °С
Heating of the drive and controller is turned on. The controller and
inverter are activated. Start is possible.
from minus 5 °С to 45 °С
Heating and ventilation of the drive are turned off.
above 45 °С
Instrument compartment ventilation is turned on.
above 50 °С
Turning on the ventilation of the inverter compartment and sine filter
compartment
above 80 °С
Drive shutdown due to inverter overheating
above 150 °С (in sine
filter compartment)
Drive shutdown due to sine filter overheating

IRZ 500 QUICK START
7
2. INTENDED USE
2.1 Operations with the drive controller
Description of the main menu is given in Table 2.1.
Table 2.1
Menu item
Menu description
MAIN REAL-TIME PARAMETERS
Real-time condition of the drive, inverter and DHS
INPUT VOLTAGE PARAMETERS
View and edit of input voltage settings
MOTOR CONTROL POINTS AND
PROTECTION FUNCTIONS
View and edit of drive protection main settings and
parameters
DHS CONTROL POINTS AND
PROTECTION FUNCTIONS
View and edit of DHS settings and motor protections
INVERTER SETTINGS
View and edit of inverter operation settings (frequency,
acceleration and deceleration rates, motor start mode)
TECHNOLOGICAL SETTINGS
Settings for automatic intermittent mode of motor
operation, as well as the characteristics of additional
modes of drive operation
SETTINGS OF ADDITIONAL ANALOG
INPUTS
Settings to measure the input signal from each of the two
analog inputs
SETTINGS OF ADDITIONAL DIGITAL
INPUTS
Settings for operation with additional digital inputs of the
drive
NOTEBOOK
Characteristics of the field, pad, and well.
Technical parameters of the motor, ESP, step-up
transformer, drive and controller.
Statistics of operation, number of motor starts and
shutdowns
POWER ENERGY
Indications of active, reactive and total electrical energy
consumed by the motor and drive
ADDITIONAL SETTINGS
Adjusting parameters of information exchange of the drive
in the network and parameters of record in the history of
operation.
Clearing the event archive of the drive
Parameters for calculating step-up transformer secondary
voltage
PASSWORD SETTING
View and change of security profiles, passwords change
DATE AND TIME
Setting the current date and time
EVENT ARCHIVE
History of motor operation
DIAGNOSTICS
Condition of various modules
SERVICE MENU
Setup and reprogramming of individual drive modules

IRZ 500 QUICK START
8
2.1.2 "▲" and "▼" buttons are used to navigate between menu items and drive parameters, and to
adjust control points values ("▲" –increase, "▼" - decrease).
2.1.3 "ENTER" button is intended to select certain menu item and to approve correctness of the value
entered.
2.1.4 “ESC” button is intended to exit current menu item and cancel new control point value
2.1.5 It is also possible to access the PASSWORD SETTING menu from any section of the drive menu by
pressing the F3 button.
2.1.6 It is possible to view real-time parameters of the drive from any menu section by pressing F2.
2.1.7 F1 button is used to return to the previous menu item from the real-time parameters window.
2.1.8 As indicated in Table 2.2, the controller of the drive can be operated and configured on four access
levels.
2.1.9 The real-time parameters page displays the real-time status of the drive, inverter, and downhole
unit (DHS). Designations of possible states and their descriptions are given in Tables 2.3 - 2.6.

IRZ 500 QUICK START
9
Table 2.2 –List of security profiles with allowed actions
Allowed actions
Access level
OPERATOR
ELECTRICIAN
WORKS
FOREMAN
ADMINISTRA
TOR
Profile access password
No password
159
410
*
Control points (settings) review**
+
+
+
+
Control points change**
-
+
+
+
SERVICE MENU contents review
-
-
+
+
Full access to SERVICE MENU
-
-
-
+
Reset of history and statistics
counters
-
-
+
+
Change of password for the
ELECTRICIAN profile
-
+
+
+
Change of password for the
WORKS FOREMAN profile
-
-
+
+
Change of password for the
ASMINISTRATOR profile
-
-
-
+
* -only servicing specialists have password to the profile access
** - except for the SERVICE MENU section
Table 2.3 –Real-time parameters of the downhole sensor system
Message on the drive’s
display
Description
Message on the drive’s
display
Description
DHS status
Codes of downhole
sensor actual status
No. of instrument
counted from the
wellhead, 1-6
No. of the instrument
ESP intake pressure
ESP intake pressure
Ser. No.
Serial number
Motor oil temperature
Motor oil temperature
Type
Instrument type
Motor winding
temperature
Motor winding
temperature
Pin
Intake pressure
ESP intake temperature
Fluid temperature at the
ESP intake
Tin
Intake temperature
Vibration - X/Y/Z
Vibration along X/Y/Z
axis
Flowrate1
Flow rate
Frame
Counter of downhole
sensor system
responses
Flowrate2
Flow rate
Frame type
Frame type
Humidity
Humidity value

IRZ 500 QUICK START
10
Table 2.4 –Drive and frequency inverter actual status codes
Message on the drive’s
display
Status description
RUNNING
The motor has been started and is now operating; the rotor catch mode may
be active
PUSH
The motor is running, the PUSH mode is active
ROCKING
The motor is running, the ROCKING mode is active
SYNCHRONIZATION
The motor is running, the frequency synchronization mode is active
PID
The motor is running, the PID-regulation mode is active
JOGGLE
The motor is running, the JOGGLE deposits removal mode is active
F SMOOTH CHANGE
The motor is running, the mode of frequency change by software is active
Un SEARCH
The motor is running, the voltage optimization mode is active
I LIMIT
The motor is running, the current limiting mode is active
T LIMIT
The motor is running, the temperature limiting mode is active
STOP
The motor has been stopped
WAIT
The motor has been stopped and time is being counted till the start (at
operation with the timer in automatic mode or when time till automatic
restart after tripping is counted) or time is counted to the start after power
supply
START IS BLOCKED
The motor has been stopped, start is blocked either according to a setting or
after a remote stop command
MANY AUTORESTARTS
BLOCKING
The motor has been stopped, start is blocked due to achieving the limit
number of automatic restarts
Table 2.5 –List of messages on causes of drive starts and stops
Status designation
Event type
STOP
The motor has been stopped
Rinsul STOP
The motor has been stopped due to decrease of insulation
resistance below the control point or failure of the Rinsul control
circuit
Uab<NORM
The motor has been stopped due to decrease of Uab below the
normal value set by the control point
Ubc<NORM
The motor has been stopped due to decrease of Ubc below the
normal value set by the control point
Uca< NORM
The motor has been stopped due to decrease of Uca below the
normal value set by the control point
Uab>NORM
The motor has been stopped due to increase of Uab above the
normal value set by the control point
Ubc> NORM
The motor has been stopped due to increase of Ubc above the
normal value set by the control point
Uca> NORM
The motor has been stopped due to increase of Uca above the
normal value set by the control point

IRZ 500 QUICK START
11
Status designation
Event type
Uab-Ubc IMBALANCE
The motor has been stopped due to imbalance of Uab-Ubc voltage
Uab-Uca IMBALANCE
The motor has been stopped due to imbalance of Uab-Uca voltage
Ubc-Uca IMBALANCE
The motor has been stopped due to imbalance of Ubc-Uca voltage
UNDERLOAD
The motor has been stopped due to low current load
OVERLOAD
The motor has been stopped due to high current
Ia-Ib IMBALANCE
The motor has been stopped due to imbalance of Ia-Ib current
Ia-Ic IMBALANCE
The motor has been stopped due to imbalance of Ia-Ic current
Ib-Ic IMBALANCE
The motor has been stopped due to imbalance of Ib-Ic current
LOAD FACTOR
The motor has been stopped due to decrease of motor load factor
below the control point value
BACKSPIN
The motor has been stopped due to backspin of motor rotor at a
frequency above the control point value
DOOR IS OPEN
The motor has been stopped because the cabinet door was open
(I/O compartments, telemechanics compartment or transformer Y-
point compartment)
PHASE SEQUENCE
The motor has been stopped due to wrong phase sequence on the
input terminals of the drive
FLOW LINE PRESSURE TRANSDUCER
The motor has been stopped due to actuation of the high/low
pressure flow line transducer
STOP BUTTON
Manual stop of the motor by pressing the STOP button
START BUTTON
Manual start of the motor by pressing the START button
REMOTE STOP
Remote stop of the motor (by a command of the SCADA-system)
REMOTE START
Remote start of the motor (by a command of the SCADA-system)
OFF
Manual stop of the motor by putting the mode switch into the OFF
position
NO START CONFIRMATION
Confirmation of motor start is missing
NO STOP CONFIRMATION
Confirmation of motor stop is missing
START IS BLOCKED
Motor start was blocked when the predetermined number of
restarts was reached or when the predetermined number of manual
starts was reached
AUTOSTART
The motor has been automatically started by a time program
AUTOSTOP
The motor has been automatically stopped by a time program
AUTORESTART
Automatic restart of the motor after tripping
MOTOR WINDING TEMPEERATURE
Motor winding temperature is higher than allowed
MOTOR OIL TEMPERATURE
Motor oil temperature is higher than allowed
MOTOR X VIBRATION
X-vibration in the place of motor installation is higher than allowed
MOTOR Y VIBRATION
Y-vibration in the place of motor installation is higher than allowed
INTAKE PRESSURE
ESP intake pressure is lower than allowed
MOTOR OILPRESSURE
Motor oil pressure is lower than allowed

IRZ 500 QUICK START
12
Status designation
Event type
MISSING COMMUNICATION WITH
INVERTER
Motor cannot start because communication with the inverter
processor board via RS485 is missing
INVERTER POWER LOSS
Motor cannot start due to loss of supply voltage in the inverter
processor board
INVERTER HEATING
Motor start is blocked while the drive is heating
CATCH PROBLEM
Motor cannot start in the catch mode
AN.INPUT1>NORM
Signal at the analog input 1 is higher than the tolerance set by the
control point
AN.INPUT1<NORM
Signal at the analog input 1 is lower than the tolerance set by the
control point
AN.INPUT2>NORM
Signal at the analog input 2 is higher than the tolerance set by the
control point
AN.INPUT2<NORM
Signal at the analog input 2 is lower than the tolerance set by the
control point
NO ACCESS
The actual access level does not allow viewing / editing the selected
parameter / control point
HIGH INVERTER RADIATOR
TEMPERATURE
Inverter radiator temperature exceeds the allowed value
SC TO GROUND
Sum of motor currents is not zero
HIGH Udc
Inverter DC circuit voltage exceeds the allowed value
LOW Udc
Inverter DC circuit voltage is lower than the allowed value
Udc CIRCUIT FAILURE
Inverter DC circuit fault
UNSTABLE Udc
Inverter DC circuit voltage fluctuations are higher than allowed
INVERTER OUTPUT SC
Short circuit at the Inverter output or failure of the Inverter power
module
INVERTER OVERLOAD
Inverter output current exceeds the allowed value
INVERTER UNDERLOAD
Inverter load is much less than the nominal load (not related to
underload control points)
MISSING TEMPERATURE SENSOR
Fault of the inverter’s internal temperature sensor
TEMPERATURE SENSOR SC
Short circuit at the inverter’s temperature sensor output
LOW INVERTER RADIATOR
TEMPERATURE
Inverter’s radiator temperature is lower than the allowed value (-
10°С)
INVERTER CURRENTS IMBALANCE
Asymmetrical load of the inverter
INVERTER EXTERNAL ALARM
A signal of inverter external alarm is present
HIGH INVERTER TORQUE
The motor has been stopped due to too high load
INVERTER RS485 TIMEOUT
Time till inverter response to a RS485 signal has elapsed
Fout>Fmax
Inverter output frequency exceeds the maximum value set by the
control point

IRZ 500 QUICK START
13
Table 2.6 –Downhole sensor system actual state codes
Message on the drive’s
display
State description
NORM
All signals coming from DHS are normally received by the drive
MISSING COMMUNICATION
WITH I/F UNIT
Communication with the downhole sensor surface unit is missing
MISSING COMMUNICATION
WITH DH SENSOR
Communication between the downhole sensor and surface unit of the
downhole sensor system is missing
3 PROCEDURE OF DRIVE OPERATION
3.1 Preparation of the drive
3.1.1 After installation, mounting (clause 1.2.5) and drive grounding (cl. 1.1.3), perform connection of
the drive according to the scheme in Annex B.
3.1.2 If it is necessary to install or replace a DHS surface readout unit inside the drive, the installation
should be performed according to the procedure specified in the VSD Operation manual.
3.1.3 At the first start of the drive, it is recommended to set the factory settings. Then enter or correct
the required list of settings in accordance with Table 3.1.
Table 3.1
Group of settings
Control point name
Recommendations
“MOTOR CONTROL
POINTS AND
PROTECTION
FUNCTIONS”
Motor nominal current
As in the motor tech.
certificate (datasheet)
Motor nominal power factor
As in the motor tech.
certificate (datasheet)
Step-up transformer secondary voltage
Equal to the transformer
secondary winding voltage
Step-up transformer primary voltage
As in step-up transformer
technical certificate
(datasheet)
Insulation resistance setting
30 –50 kOhm
Backspin rotation protection
On
Motor underload setting
After reaching the set
frequency, wait for 10-15 mins
and set the value equal to 0.8
from the current loading value.
“NOTEBOOK”
Field ID number
Pad ID number
Well ID number
Motor nominal power
Motor nominal supply voltage
ESP capacity
ESP head
Running depth
Formation fluid density
Step-up transformer nominal power
Acc. to equipment data
“INPUT VOLTAGE
PARAMETERS”
Nominal voltage
460 V

IRZ 500 QUICK START
14
Group of settings
Control point name
Recommendations
“INVERTER SETTINGS”
Nominal frequency of motor
Max operating frequency of
ESP unit. The value should
correspond to the frequency
for which the Step-up
transformer secondary voltage
is calculated.
Nominal voltage of inverter
460 V
Set frequency
Required motor frequency in
Hz
Motor type
Asynchronous, permanent
magnet (synch., 6 pulse)
Number of pole pairs of PMM
Only for PMM
“DHS CONTROL
POINTS AND
PROTECTION
FUNCTIONS”
DHS Model
Acc. to the DHS used

IRZ 500 QUICK START
15
Table 3.2 –Drive settings at jammed ESP
Push start mode
Rocking start mode
“Motor start mode”
PUSH
“Motor start mode”
ROCKING
“Push frequency”
12 - 18 Hz
“Rocking frequency”
7 –15 Hz
“Number of pushes”
3 - 5
“Rocking torque boost”
10 –20 %
“Push voltage”
150 %
“Rocking duration”
3 –5 s
“Push duration”
1 –2 s
“Rocking acceleration rate”
25 Hz/s
“Rocking deceleration rate”
25 Hz/s
“Number of cycles”
3 - 5
3.2 Emergency actions
The procedure of work at emergency ESP stops and abnormal modes of operation is as follows:
3.2.1 In case of a tripping caused by the insulation resistance protection function:
3.1.4 Check operation capability of surface equipment in idle mode (check the real-time parameters
and protections).
3.1.5 Perform a test run of the drive in the manual control mode and monitor on the controller display
that frequency is increased to 5 Hz.
3.1.6 While monitoring the value of motor current on the drive’s display, increase the frequency with
the step of 5 Hz.
3.1.7 If at a frequency of 10 Hz the overload protection or protection at inverter output short circuit
activates, perform the following actions:
- check that the step-up transformer and motor are connected properly;
- if the connection is correct, disconnect the cables in the drive output compartment and press the
START button, set the output frequency to 50 Hz;
- if the overload protection or protection at inverter output short circuit is not activated with the
disconnected cable in the drive output compartment, then the step-up transformer, Motor or Cable
may be damaged;
- if the step-up transformer, cable and motor are in good condition, contact the manufacturer’s service
department.
3.1.8 If the overload protection or protection at inverter output short circuit activates at 15-35 Hz
frequency, then the ESP is probably jammed. It is necessary to enable push or rocking start mode and
repeat the start attempt. Recommended setting values are given in table 3.2.
3.1.9 If the attempt to start the jammed ESP makes no effect, it is necessary to flush the well.
3.1.10 After reaching the required frequency and after 20-30 minutes of operation at a constant
frequency, it is recommended to perform automatic voltage optimization with respect to current. To
do so, set the control point “AUTO.OPTIMIZATION Un” to “ON”.
3.1.11 When selecting the PSI pressure units of measurement, select “PSI”in the “Pressure
measurement” item of the “DHS control points and protections”/ “DHS settings”menu, and set “0,1”
in the “multiplier” item.

IRZ 500 QUICK START
16
Check the insulation resistance control protection function for normal operation.
If a downhole sensor system surface unit is not used, the DHS TYPE control point shall have the “NO”
value; in the TRANSFORMER Y compartment of the drive, the XS12 connector shall be connected to
VR210.
If a downhole sensor system surface unit is used (no matter if the downhole sensor itself is used or
not), make sure that the downhole sensor system surface unit is not damaged and the settings of
communication with the downhole sensor system are correct; in the TRANSFORMER Y compartment,
the XS12 connector shall be disconnected from the VR210 unit.
Disconnect the ends of the cable of the downhole ESP unit from step-up transformer output terminals,
measure the insulation resistance with a megohmmeter and make sure that motor windings have the
same insulation value, visually check condition of the cable coming from step-up transformer terminals
to the well mouth (for reflow or mechanical damage).
3.2.2 In case of tripping caused by frequency inverter or sine filter overheating protection function:
Check the status of the SF4 “VENTILLATION” circuit breaker –it shall be in “On” position.
Check the status of venting holes and filters, clean when necessary.
Reduce PWM frequency, but it should not be lower than 4 kHz.
3.2.3 In case of tripping caused by the overload protection (OLP) function:
Check the drive OLP function for correct operation.
Check supply voltage in the phases at the low and high sides of the step-up transformer.
Using a 1000 V megohmmeter: check insulation resistance in the “TRANSFORMER - MOTOR” system
and make sure that motor windings have the same insulation value. If insulation resistance is not less
than 0.5 МΩ, start the ESP unit. Measure currents in the phases using a clamp meter at the high and
low sides of the step-up transformer. Phases distortion in terms of voltage and current shall not exceed
5%.
Check the ESP system for normal operation. The delivery parameters and dynamic level may change
and water cut may increase.
If load current exceeds its nominal value, stop the ESP system. Increase or decrease step-up transformer
voltage (by switching tapping in one or two steps).
After load current decreases till its nominal value, set optimized value of step-up transformer voltage,
adjust OLP, ULP and load level.
If load current fails to decrease till its nominal value, start the unit in the “push” or “rocking” mode.
If the ESP unit fails to start, perform additional maintenance operations (rinsing and others) or pull out
the ESP system.
If it is decided to pull out the ESP system, shut down the unit, disconnect the cable from terminal
contacts of the step-up transformer.

IRZ 500 QUICK START
17
ANNEX А- IRZ-500 MENU STRUCTURE
INPUT VOLTAGE PARAMETERS
N ominal voltage
Time t o au torestart by voltage
N umber of autores tarts by volt age
H igh v oltage
Low vol tage
Voltages i mbalan ce
Voltage correction factor
Set defaults for voltage?
Motor n ominals
Overload OLP
Underload ULP
Current correction factors
Currents imbalan ce
Insulation resistance
Flow l ine pressure transducer FLPT
Phase sequenc e
Bac kspin rotation
Door blocking
Corr. factor cosf
Autores tart counters reset time
Reset autorestart counters?
Set defaults for motor protections?
Program operation
Program frequen cy change
Joggle (deposits removal)
Gas lock removal mode
Au to optimization of output voltage
Current limit mode
Temperature limit mode
Inverter radiato r temperature limit mode
Set frequenc y
Rotation direction
Motor start mode
Acceleration rate
Deceleration rate
Dynamic brake mode
U/F charac teristic
Start mo de
PI D-regulato r
Linear regulator
Minimum frequency
Maximum frequency
Motor type
Number of pole pairs of PMM
PMM start current
Frequ ency measurement units
Nomi nal frequenc y of motor
Nomi nal frequenc y of inverter
Motor roto r catc h
PWM frequen cy
Udc change compens ation
Avoiding mains voltage loss
D rive operation mo de
Set defaults for inverter?
DHS REAL-TIME
PARAMETERS
CONTROL POINTS
AND SETTINGS
REA L-TIME
PAR AMETERS
DHS STATUS
*c a n be a cc ess ed
in cas e of fau lt s
INVERTER F AULTS
SETTINGS OF AD DITIONAL DIGITAL INPUTS
Active status of external alarm
Protection at axternal alarm
Time to stop at ext. alarm
Ext. alarm protec.ac tivation delay after s tart
Type of restart for ext . alarm
Res tart delay at external alarm
Number of restarts at external alarm
Additional alarms
Field ID No.
Pad ID No.
Well ID. No.
Motor nomin al power
Motor nomin al supply voltage
ESP capac ity
ESP nom. head
ESP max. head
Wellhead pressure
Running dept h
Formation fluid density
Step-up transformer nominal power
Po wer li ne No.
Statistics cou nters
Drive equipment information
SETTINGS OF ADDITIONAL ANALOG INPUTS
Type of input signal
Settings of an alog input 1
Settings of an alog input 2 , 3 , 4
Set defaults of analog in puts?
Consumed energy
Electric meter settings
Archive writing settings
Drive network set tings
Remote st art in manu al mode
Step-up transformer sec. voltage calculation
ESP i ntake pressure
Motor oil pressure
Motor oil temperature
Motor winding temperature
Motor vibration
DHS communication protection
DHS protec . ac tivation delay after start
DHS settings
Set defaults for DHS?
SMART CONTROL MODES
*Optional
Au toadaptation mode
Au toadaptation per iod
Avoid ing ov erload
Avoid ing under load
Avoid ing mo tor overheat ing
Avoid ing invert er o verheating
Bot tomhole automatic drain ing
Deposits removal
Output voltage automati c optimization
Gas lock removal
Au toadaptation s ettings
Inverter real-ti me parameters
MOTOR CONTROL POINTS
AND PROTECTION FUNCTIONS
TECHNOLOGICAL SETTINGS AND PROTECTION FUNCTIONS
INVERTER SETTINGS
REAL-TIME PARAMETERS
"ESC"
"F2"
»
»
« »
« »
NOTEBOOK
POWER ENERGYADDITIONAL SETTINGS
PASSWORD SETTING
DATE AND TIME
EVENT ARCHIVE
DIAGNOSTICS
"ESC"
"F3"
DHS ADDITIONAL PARAMETERS
SERVICE MENUFACTORY SETTINGS
«
«
Driv e status Start/stop c ause
Uab out
Ubc ou t
Uca ou t
F
Backspin
Imbal U
Imbal I
Phas e seq.
Load
Motortype
Udc
Uab out
Ubc out
Uca out
Uab tranf
Ubc transf
Uca tran sf
Uinvert/transf
Ua
Ub
Uc
Iu
Iv
Iw
Tmicrocontr
Driv e status Start/sto p c ause
Mod e of operat ion
Timer
Ia
Ib
Ic
Rinsul
Door
Uab
Ubc
Uca
CosF
Pact
Tigbt
Uinvert/transf
(or drive operation mode)
DHS CONTROL POINTS
*c a n be ac ces se d
in cas e of fau l ts
DHS s tatus
ESP intake pressure
Mot or oil pressure
Motor oil temperature
Mot or wind. temperature
ESP intake temperature
Vibration - X
Vibration - Y
Vibration - Z
ESP discharge flow
Frame type
Frame
Time to autostart by voltage

IRZ 500 QUICK START
18
ANNEX B - RECOMMENDED IRZ-500 DRIVE CONNECTION DIAGRAM
* Optional

IRZ 500 QUICK START
19
Izhevskiy Radiozavod (IRZ) group of companies
19 Bazisnaya str., 426034 Izhevsk, Russia
Manufacturer: IRZ TEK, LLC.
Tel./fax.: +7(3412) 65-83-06
Tel.: +7(3412) 501-501
http:// www.irz.ru
E-mail: [email protected]
Signed for printing on 04.03.2018
This manual suits for next models
23
Table of contents
Other iRZ DC Drive manuals
Popular DC Drive manuals by other brands

SSD Drives
SSD Drives 590+ Series product manual

Leadshine
Leadshine DM556E user manual

Panasonic
Panasonic AJ-PCD35EJ operating instructions

Pacific Scientific
Pacific Scientific MA6410 Installation & hardware reference manual

Allen-Bradley
Allen-Bradley PowerFlex 6000T Hardware Service Manual

Hubbell
Hubbell Universal Cable Reel-Direct Drive UE18 Installation and maintenance instructions