Islandaire EZ Series Installation and operation manual

EZ Series NY
42” x 16” Flat Top PTAC/PTHP
Perfect t for Replacing Existing 42” x 16” Flat Top Units and
for New Construction Projects
Engineering Manual
MANUFACTURER OF QUALITY AIR CONDITIONING AND HEATING PRODUCTS
6140204 Rev. 03/11/21

EZ REPLACEMENT GUIDE
Original Model
Case
Height
Case
Width
Our
Model Original Model
Case
Height
Case
Width
Our
Model
Amana® Keeprite®
PT 42 x 16 Series 16 42 42 Climette 18 5/16 32 CS
PB 26 x 16 Series 16 26 26 Seasonall 18 5/16 32 CS
American Air Filter® Lennox®
Enersaver Type 16 16 37 1/2 16 PTEIA Series 22 1/4 38 PT
Type 16 Hydronic 16 41 1/2 16 McQuay®
Nelsonaire Series 25 16 36 1/2 25 C/EC 27 3/8 54 1/2 EC
American Standard® EB Series 22 30 5/8 EB
TW Series Type 41 16 36 1/2 41 J/EJ Series 14 30 JA
Type 40 Remotaire(SR) 16 1/2 37 40 K, EK and RK Series 13 15/16 36 KF
Applied Comfort® Type EA, ES and RS 16 3/8 44 7/8 ED
DM/DMQ 18 5/16 32 CS Type NE 16 42 NE
SC Series 16 40 SC Mueller®
SC Series 16 36 RM Climatrol 16 48 UN
Carrier® Remington®
51PH Wallmate 18 15/16 32 CS J/EJ Series 14 30 JA
Cartaret® K, EK and RK Series 13 15/16 36 KF
Type 45 16 1/2 37 45 Type 41 16 36 1/2 41
Chromalox® Type 45 16 1/2 37 45
Space Command 16 1/2 45 1/8 CH Simonaire®
CAM (2 section) 15 35 1/2 CX SSK 16 42 RT
Chrysler® 15 1/2 36 CY SSEZ 16 42 RT
Climate Master® SSCT 16 42 RT
Climate Master Series 700AD 16 36 AD Singer®
Climate Master Series 701 16 40 1/2 C7 C/EC 27 3/8 54 1/2 EC
Climate Master
Series 702, 703 & 704 16 36 CM EB 22 30 5/8 EB
Dunham Bush® J/EJ Series 14 30 JA
New Port III 25 52 N3 K, EK and RK Series 13 15/16 36 KF
New Port IV 25 52 N4 Type 41 16 36 1/2 41
Embassy® Type 45 16 1/2 37 45
Weathertwin 16 36 RM Type EA, ES and RS 16 3/8 44 7/8 ED
Fedders® Slant Fin®
Maxizone Series 16 1/4 27 MX JK 16 42 JK
Unizone 16 48 UN CC Monterrey 16 42 CC
Friedrich® Monterrey 17 1/2 36 FM
Climate Master Series 700AD 16 36 AD Suburban Dynaline®
Climate Master Series 701 16 40 1/2 C7 Gas Unit 16 42 GS
Climate Master Series
702, 703 & 704 16 36 CM TPI®
ET Series 20 28 ET Ra-Matic 16 36 RM
TE Series 16 42 TE Weil-Mclain
Vert-I-Pak 32 23 VP ClimateMaster Series 700AD 16 36 AD
General Electric® Climate Master Series 702,
703 & 704 16 36 CM
Zoneline 16 42 42 Westinghouse®
AJ Series 16 26 26 RB Series 15 38 1/2 RB
AZ Vertical 31 23 1/4 VP Worthington® 16 48 UN
Heil Quaker® Zoneaire®
SEA Series 14 1/2 35 7/8 HQ CHP Series 18 5/16 32 CS
SHA Series 14 1/2 35 7/8 HQ CSM Series 18 5/16 32 CS
Series C 18 5/16 32 CS Zoneaire‚ RM Series 16 36 RM
Ice-Cap / Ice Air® Zoneaire‚ SC Series 16 40 SC
RSK Series 16 36 RK Custom Products
RSCT Series 16 42 RT
RSWL Series 13 1/4 56 1/2 WL
ITT Nesbitt® Vertical Units, Fan Coils, and other related HVAC products.
(Consult with Factory)
Challenger Series 16 1/4 42 1/4 NC If you don’t see the unit you’re looking for in the above list,
please call us about having a unit custom designed for you.
Roomate Series - N - - CY
Modular Roomate (MW) - - NR
Islandaire reserves the right to make changes in design and construction at any time without notice.

1
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Table of Contents
EZ REPLACEMENT GUIDE............................................. B
TABLE OF CONTENTS .....................................................1
Our Company................................................................................ 2
e Perfect Fit................................................................................ 2
New Construction......................................................................... 3
Retrot/Replacement.................................................................... 3
APPLICATIONS.................................................................3
Application Considerations ......................................................... 4
Guaranteed Quality....................................................................... 4
Quiet Operation ............................................................................ 4
Durable Construction................................................................... 5
Superior Corrosion Protection.................................................... 5
PRODUCT OVERVIEW EZNY ......................................5
STANDARD CHASSIS OVERVIEW .................................6
Standard Chassis: .......................................................................... 6
Accessories Overview ................................................................... 6
STANDARD CHASSIS FEATURES AND BENEFITS......7
OPTIONS AND ACCESSORIES......................................10
Replacement Guide..................................................................... 11
ORDERING DATA ...........................................................11
Model Nomenclature.................................................................. 11
PERFORMANCE DATA...................................................12
Performance Data........................................................................ 12
Electrical....................................................................................... 12
Hydronic Heat Option Performance Data............................... 13
DIMENSIONAL DRAWINGS..........................................14
PANEL/CURTAIN/WINDOW WALL APPLICATION..15
BLOCK WALL APPLICATION .......................................16
Wall Sleeve and Room Enclosure Selection (Panel Wall) ...... 16
Wall Sleeve and Room Enclosure Selection (Block Wall)...... 17
Installation Notes ........................................................................ 17
INSTALLATION DATA....................................................17
Installation Checklist .................................................................. 18
Framing ........................................................................................ 18
Electrical Outlet Location .......................................................... 18
Condensate Drain Kit................................................................. 19
External Drain Installation ........................................................ 19
CONDENSATE DRAIN KIT............................................19
Internal Drain Installation ......................................................... 20
Wall Sleeve.................................................................................... 21
Wall Sleeve Installation............................................................... 21
WALL SLEEVE INSTALLATION.....................................21
REAR GRILLE INSTALLATION.....................................22
Standard Rear Grille ................................................................... 22
Architectural Rear Grille............................................................ 23
HYDRONIC COIL............................................................26
Hydronic Coil Orientation......................................................... 26
HYDRONIC COIL INSTALLATION ..............................27
HYDRONIC COIL PIPING .............................................28
CHASSIS INSTALLATION ..............................................29
ROOM ENCLOSURE ASSEMBLY...................................30
ROOM ENCLOSURE INSTALLATION..........................31
MAINTENANCE ..............................................................32
Air Intake Filter ........................................................................... 32
Routine Maintenance.................................................................. 32
Lateral Duct Kit........................................................................... 33
WIRING DIAGRAMS ......................................................34
SYSTEM CONTROLS AND MANAGEMENT................36
USER INTERFACES................................................................... 36
Remote Control ........................................................................... 36
Digital Control Panel .................................................................. 36
Wall ermostats......................................................................... 36
Front Desk Control..................................................................... 36
System Management Soware................................................... 37
Fan Cycle Control........................................................................ 37
Hydronic Heat Fan Lockout Kit................................................ 37
Room Freeze Prevention ............................................................ 37
High Temperature Compressor Protection ............................. 37
Valve Controls.............................................................................. 37
Low Temperature Compressor Protection............................... 37
Custom Operation and Continual Room Temperature
Monitoring .................................................................................. 37
Diagnostic Soware .................................................................... 37
CONTROL PANEL ...........................................................38
Digital Control Panel - Control panel ...................................... 38
Power Control.............................................................................. 38
Display .......................................................................................... 38
Mode Control - Cool, Fan, and Heat........................................ 38
Fan Speed Control - Low, High, and Auto............................... 39
Temperature Controls................................................................. 39
OPERATIONAL PRACTICES .................................................. 39
REMOTE THERMOSTATS..............................................40
Remote Wall Mounted ermostats......................................... 40
Remote ermostat Control...................................................... 40
Wireless Wall ermostat .......................................................... 40
Energy Saving Options ............................................................... 40
REMOTE THERMOSTAT INTERFACE .........................41
CONTROL BOARD..........................................................42
Set Temperature Limiting .......................................................... 43
TEMPERATURE LIMITING ...........................................43
ERROR CODES ................................................................44
Diagnostic & Error Codes.......................................................... 44
Heating/Cooling Chassis............................................................ 45
PERFORMANCE SPECIFICATIONS EZNY.................45
Hydronic Heat ............................................................................. 46
Control module ........................................................................... 46
Inputs and outputs ...................................................................... 47
Wall Sleeve.................................................................................... 47
Outside Air Louvers.................................................................... 47
Room Enclosure .......................................................................... 47
Fresh Air Damper ....................................................................... 47
Filtration....................................................................................... 47
START UP AND MAINTENANCE..................................48
START UP CHECKLIST............................................................ 48
ROUTINE MAINTENANCE.................................................... 48
TYPICAL WARRANTY ...................................................49

2
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Our Company
Islandaire is the fastest growing specialty air conditioning and heating
manufacturer in the country. Founded in 1992 by Robert Hansen, it has
grown into a multi-million dollar company in just a few short years. Islan-
daire builds a full complement of high quality thru-the-wall replacement
air conditioners and heat pumps, water source heat pumps, and gas units
in St. James, New York. Each model ts perfectly into the existing original
wall sleeve assembly, thereby saving both time and money during installa-
tions.
Our Engineering, Production, Sales and Customer Service departments
have been fully integrated to provide the maximum degree of user satis-
faction. We at Islandaire feel that this team approach to manufacturing
produces a superior overall product and assures a larger degree of ex-
ibility in design and production scheduling to meet tight prototyping or
construction timetables.
The Perfect Fit
ru-wall air conditioners were developed in the late 1950’s. Over the
next forty years many companies engineered, manufactured and installed
a variety of dierent units throughout the United States and Canada.
Today, a number of these companies are no longer in business or have
discontinued their line of thru-wall air conditioners and no longer carry
replacement parts.
Islandaire oers replacement air conditioners and heat pumps that are
interchangeable with units no longer available from the original manu-
facturer. Our units are engineered to t perfectly within the existing wall
sleeve, thereby reducing installation time and expense. ey are manufac-
tured at our modern 75,000 square foot plant on Long Island in New York.
ank you for considering our products,
e Islandaire Team

3
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Applications
For new construction, or as a replacement, our
packaged terminal air conditioning (PTAC) units
provide year-round comfort control for hotels,
motels, apartments, dormitories, shops, nursing
homes, assisted living centers, satellite oces, room
additions and other applications that require eco-
nomical heating and cooling.
Individually controlled PTAC units are ideal for
rooms that are not occupied during vacancies,
holidays, weekends or nights. Individual units allow
tenants to choose the degree of comfort and operat-
ing economy.
ermostat and fan controls are built into the
digital touch-pad, plus all units have the exibility
to convert to a wall thermostat control, or interface
into energy management systems. Whether you are
designing a new structure or replacing PTAC units
in an existing building, Islandaire will meet your
needs.
New Construction
e Islandaire EZNY Packaged Terminal Air Con-
ditioning (PTAC) unit is designed to meet the needs
of the architect, engineer, and contractor. For unit
installation, Islandaire’s expert support network will
assist in all applicable aspects of the construction
project, from preparing a budget to start-up.
ADVANTAGES FOR NEW CONSTRUCTION
• Design Flexibility For e Architect Engineer
• Super-quiet performance, indoors and out
• No bulky duct system
• No separate equipment room
• No water towers or additional cooling equip-
ment
• Less sensitivity or building orientation
• Optional architectural grille to permit custom
exterior appearance
• Lower Operating Costs and Reliable Comfort
for the Occupant
Islandaire helps lower utility costs with energy e-
cient units that exceed industry standards. Energy
savings are achieved in both heating and cooling
environments through ecient mechanical design
and onboard electronic logic. Separate indoor and
outdoor fans provide lower operating costs. Energy
management soware is built into the unit’s stan-
dard digital controls.
ese units may also qualify for electrical power
company rebates. (Consult your local utility pro-
vider for rebate opportunities.)
Retrofit/Replacement
Islandaire PTAC units are engineered to t perfectly
within most existing wall sleeves, thereby reduc-
ing installation time and expense. ere is no time
wasted on redesigning an existing wall opening or
removing an old wall sleeve. Just slide the old chas-
sis out and replace with a new one from Islandaire.
EZ Quick connections to the control box simplify
electrical hook-up, and our slide-out chassis eases
installation into the wall sleeve. Rapid servicing
reduces downtime: complete chassis can be replaced
in minutes without disrupting other occupants.

4
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Applications (cont.)
Application
Considerations
It is important for air conditioning systems to
be properly sized for each application in order to
achieve desired temperature and humidity levels. It
is strongly recommended that a professional engi-
neer match the PTAC units with the building struc-
ture and climate.
e following application considerations are all
important in choosing the proper PTAC system for
the building structure.
UNDERSIZING
If a PTAC unit is undersized (cooling capacity is
less than required capacity for an application), the
unit will not be able to cool the space down to the
desired temperature during very hot days.
OVERSIZING
If a PTAC unit is oversized (cooling capacity is
greater than required capacity for the specic appli-
cation), the unit will cool the space down to the
desired temperature too quickly creating a cool, yet
excessively humid, space.
AIR INFILTRATION
Excessive air inltration can intensify problems
associated with undersizing or oversizing a PTAC
unit. is can be the cause of insucient cooling,
dehumidication, or heating. Sources of air inltra-
tion include vents, gaps around windows and doors,
and improperly sealed oors, ceiling or wall joints.
Guaranteed Quality
Each Islandaire unit is designed to operate quietly
and eciently and is backed by the best warranty
program available. e EZNY Unit is warranted
for 12 months parts and labor, plus an additional
second through 5th year sealed system part only
warranty.
Whether it is an exact replacement unit or a new
construction project, Islandaire is the smart choice
for all your air conditioning and heating needs.
Quiet Operation
e cross-ow tangential fan wheel design used in
our EZNY units provides whisper quiet operation
while delivering maximum airow required for
proper air circulation. Separate indoor and outdoor
fan motors further reduce operating sound levels
and costs.
e galvanized 18 gauge construction of the chas-
sis and enclosure minimizes vibration for quieter
operation. Vibration isolators on the rotary com-
pressor keep it running smoothly and quietly. e
unit bulkhead is fully insulated to decrease outdoor
sound transmission.
e compressor is isolated to minimize vibration
and sound transmission for quiet operation.

5
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Product Overview (EZNY)
Durable Construction
• Islandaire PTAC/PTHP units are built with
durable, quality components designed for con-
tinuous operation in all environments.
• Our wall sleeves are constructed of thick
18-gauge steel with a tough baked-on nish
for maximum durability.
• e outdoor fan motor is totally enclosed,
preventing damage from moisture and debris
introduced by extreme weather conditions.
Both indoor and outdoor fan motors are per-
manently lubricated for extended life.
• Electrical components are located on the
indoor side of the wall protecting them from
driving rain and humidity.
• e compressor is a reliable, high eciency
design rotary compressor. It is hermetically
sealed and designed for continuous operation.
• Wall sleeves and enclosures are 18 gauge
galvanized with baked on powder coat nish.
ere are many available color options.
• Rugged decorator style extruded aluminum
discharge grille with matching integral control
door.
Superior Corrosion
Protection
Application of air conditioning equipment in a cor-
rosive environment requires special consideration.
e corrosive nature of salt water vapor, chlorine
and acid vapor, demands a unit that can withstand
these environments. Any metal portion that is
exposed to a corrosive vapor must be specially
treated.
All Islandaire PTAC units have special corrosion
protection that can help dramatically extend the life
of the unit. Listed below are just some of the com-
ponents that feature corrosion protections:
• Wall Sleeve – e entire wall sleeve is con-
structed of 18-gauge galvanized steel. Treated
inside and outside with a baked-on based
powder coat paint to protect it from the cor-
rosive eects of salt spray.
• Base Pan – Base pan is constructed of
18-gauge galvanized steel and has a corro-
sion resistant coating to protect it from the
elements. Treated inside and outside with a
baked-on based powder coat paint to protect
it from the corrosive eects of salt spray.
• Condenser Coil – Protective coating applied
to the coil to prevent corrosion and weather-
ing. e coils’ header plates are constructed
using aluminum to prevent corrosion.
• Condenser Fan Blade – Constructed of strong
engineering plastic that has excellent dimen-
sional stability over a wide range of service
temperatures.
• Condenser Fan Motor – Specially coated by
the manufacturer.
• Compressor – Protective coating applied by
the manufacturer on the exterior to enhance
equipment life and performance.
• Outdoor Louver – Made of aluminum, etched
and anodized for maximum corrosion protec-
tion. Available in stamped or architectural
styles. Can be painted in a wide choice of
colors.

6
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Standard Chassis Overview
Standard Chassis:
Islandaire manufactures the EZNY loaded with
standard features that other manufacturers oen
consider optional.
• Industry standard 42” wide by 16” high
• Two fan motors for quiet operation and
improved performance
• Tangential evaporator blower wheel for quiet
operation
• Hand held remote control
• Fully insulated rewall to prevent outdoor
sound transmission
• Venturi shroud to improve air ow
COMPRESSOR
SLINGER FAN
BLADE
VENTURI
SHROUD
TANGENTIAL EVAPORATOR
BLOWER WHEEL
RETURN AIR
FILTER
ELECTRONIC
COMPONENTS HYDRONIC
NC/NO SWITCH DIGITAL TOUCHPAD
CONTROL / DIAGNOSTICS
SLOPED
BASEPAN
Accessories Overview
DISCHARGE GRILLE
HYDRONIC COIL
REMOVABLE
FRONT PANEL
ROOM ENCLOSURE
OUTSIDE AIR LOUVER
WALL SLEEVE

7
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Standard Chassis Features and Benefits
Compressor
Isolated rotary compressor design for continuous ecient,
reliable and quiet operation.
High Capacity Heat Transfer
Surfaces
Finned/tube coils incorporate state-of-the-art technology.
Unique design provides high eciency and low air pressure
drops. Allows for easy cleaning during scheduled mainte-
nance.
Sloped Coil Design
Sloped coil design allows the unit to intake air from the bot-
tom of the enclosure and reduce the amount of room required
for installation
Electrical Components
Protected from the elements and easily accessed for service
Positive condensate removal
Positive condensate removal is achieved with a sloped base
pan design, which prevents condensate build-up and overow.
Tangential Blower Wheel
• Creates extremely quiet indoor operating environment
• Generates a balanced and constant airow into the
room
Slinger Fan
• Curved fan blades increase airow across the outside coil
• Creates a quiet operating environment outside of building
• Slinger ring eciently removes condensate and
increases cooling
Venturi Shroud
• Works with the fan to maximize air ow and increase
eciency
• Removes easily for quick access when cleaning con-
denser coil
Corrosion protection treatment
shields the EZNY unit from corrosive
environments and extends the life of
the unit especially in coastal locations.
Note

8
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Standard Chassis Features and Benefits (cont.)
NC/NO Switch
Built in Normally Open/Normally Closed switch takes
the guesswork out of ordering a unit. With the ick
of a switch, the unit can be changed from NC to NO
hydronic valve operation.
Top Mounted Hydronic
Coil
• Steam or hot water coil assemblies available
• Le-hand or right-hand piping conguration avail-
able for exible hydronic/steam piping connection
• Equipped with a protective sheet metal cover to
prevent damage during shipping, installation and
construction
• Field reversible le & right piping
Return Air Filter
• Easily removable from the unit for cleaning
• Filters the circulated air inside the room
• Keeps the system clean and working eciently
• Clean lters increase life of the system components
Digital Touchpad Control
• Reliable and easy to operate
• Continuous or cycle indoor fan operation
• Works with hand held remote control and/or wall thermostat
• Easy to read LED diagnostics
- Sensors in the unit continually monitor the indoor coil, outdoor coil, and
outdoor air conditions. If abnormal conditions are detected, an error code
is displayed, removing the guess work in troubleshooting a unit.
Motorized Fresh Air Damper (optional)
e optional motorized fresh air damper eortlessly allows you to add fresh air into the room. When the
Fresh Air switch is in the ON position, the damper door opens and allows fresh air to be drawn in from
outside. When the damper door switch is in the OFF position, the damper door is closed and does not
allow outdoor air to enter.

9
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Wall Sleeve
• 18 Gauge galvanized steel with a powder coated paint for maximum protection
• Custom wall sleeve depths available.
• Panel/curtain/window wall sleeves available as an option
• Brick stop ange and support legs available as an option
• e rst manufacturer to design and fabricate with a drip edge
and built-in pitch combined
Exterior Louver/Grilles
• Heavy-duty, architectural, extruded aluminum to resist
weathering
• Custom colors available (Ask for our color chart sheet)
• Recessed available
• Stamped exterior grilles available
Room Enclosure
• 18 Gauge galvanized steel with powder-coated paint for maximum protection
• Custom depths available. (See “Wall Sleeve and Room Enclosure Selection (Panel
Wall)” on page 16 for size.)
• Custom colors available (ask for our color chart sheet)
• Removable front panel for easy access
• Custom discharge grilles available; Anodized aluminum or
black also available
• Custom adjustable kick plates are available with various color
options
• Sturdy aluminum discharge grille with hinged control door
Standard Chassis Features and Benefits (cont.)

10
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Lateral Duct
• Allows the air from one PTAC unit to be
shared by an adjacent room
• e kit mounts to the top of the unit and can
be congured for either right or le discharge
Options and Accessories
Condensate Drain Kit
• Attaches to wall sleeve base pan to control condensate removal
• Can be adapted for le or right side exterior drainage or
internal drain connection
Remote Control
Part Number 6040694
• Ability to control PTAC from anywhere in the room
• Large full function display
• Operates on two AA batteries
Wall Thermostats
• Wired programmable and non-programmable digital
wall thermostats available
• Wireless digital wall thermostats available
• Master-slave option available

11
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Ordering Data
Model Nomenclature
Replacement Guide
MANUFACTURER MODEL
WALL OPENING DIMENSION DISCHARGE HEAT TYPE
16 ¼” X 42 ¼”ANGLE FLAT HYDRONIC
AC
AMANA PTC • • •
CLIMATE MASTER PTP • • •
LG • • •
MC QUAY
PDE • • • •
PSE • • •
MQE • • • •
SINGER NE • • •
TRANE PTE • • •
COMPONENT
COOLING CAPACITY
SYSTEM TYPE
HYDRONIC OPTIONS
FUNCTIONAL
OPTIONS
POWER MANAGE-
MENT OPTIONS
IDENTITY CODE
RETURN DISCHARGE OPTIONS
NY 12EZ A 2G1S 4 6A A
MODEL TYPE
NY- ISLANDAIRE 42” X 16” (HYDRONIC)
VOLTAGE / LINE CORD
HEATING OPTIONS ROOM CONTROLS
POWER
MANAGEMENT
CODES
EZ - Cooling Chassis
07 - 7,500 BTU
09 - 9,500 BTU
12 - 12,000 BTU
16 - 15,000 BTU
A - Std. Chassis R410A
1 - 115v, 20 Amps
2 - 230v, 20 Amps
3 - 230v, 30 Amps
4 - 230v, Hard Wire
5 - 115v, 15 Amps
6 - 115v, Hard Wire
9 - 230v, 15 Amps
A - 208v, 15 Amps
B - 208v, 20 Amps
C - 208v, 30 Amps
D - 208v, Hard Wire
A - None Cooling Only
F - Hyd. Fan Cycle W/T-Stat (115v - 277v)
G - Hyd. With Aquastat (115v - 277v)
H - Hyd. W/2.5 kW B.U. Heat (208v - 277v)
I - Hyd. W/3.6 kW B.U. Heat (208v - 277v)
Z - Hyd. W/1.3 kW B.U. Heat (115v)
1 - None
2 - 24v NC Valve
6 - 24v NO Valve
A - Line Volt NO/NC Switch
B - 24v NO/NC Switch
E - Wireless Thermostat (type must be specied
when placing order)
F - Wall Thermostat Interface, Master
G - Wall Thermostat Interface, Slave
N - Wall Thermostat Interface, Std. Elect. Cntrls
S - Std. Electronic Controls (Unit Mounted)
A - None
B - Motorized Fresh Air
Damper
D - Indoor Freeze Protect
FUNCTIONAL
OPTIONS CODES
A - None
C - Energy Mgt. N/O
D - Energy Mgt. N/C
0 - Special
6 - Standard
4 - Front/Bottom Ret./Top Dis.
A - A
B - B
L - BD
2 - D
A - A
P - C
T - D

12
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Performance Data
Performance Data
EZ07 EZ09 EZ12 EZ16
Volts 115 230 208 115 230 208 115 230 208 230 208
BTUH Cooling 7,600 7,200 7,000 9,700 9,500 9,300 12,000 12,000 11,800 15,000 14,800
Amps Cool 5.61 2.63 2.80 7.56 3.69 3.92 9.94 4.97 5.30 6.21 6.78
Watts Cool 645 605 583 870 848 816 1,143 1,143 1,103 1,429 1,410
EER 11.8 11.9 12.0 11.2 11.2 11.4 10.5 10.5 10.7 10.5 10.5
CFM High Cool 360 375 340 360 375 340 360 375 340 375 340
CFM Low Cool/Heat 260 260 240 260 260 240 260 260 240 260 240
Noise Indoor/Outdoor (DBA) 45/69 45/69 45/69 45/69 45/69 45/69 45/69 45/69 45/69 45/69 45/69
Refrigerant (Type) R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Shipping Weight (LB) 132 132 132 132 132 132 137 137 137 143 143
STC (Unit O)* 26 26 26 26 26 26 26 26 26 26 26
Where applicable, cooling capacities are specified at conditions of 95 °F DB/75 °F WB outdoor and 80 °F DB/67 °F WB indoor and heating capacities
are specified at conditions of 47 °F WB outdoor and 70 °F DB/60 °F WB indoor in accordance with AHRI 310/380 and CSA C744 standards. Wattage,
Amperage, EER, and COP listings include compressor, evaporator motor and condenser fan motor.
Electrical
EZ07, EZ09, EZ12, EZ16
LINE VOLTAGE 115 208/230 208/230 208/230
MAXIMUM AMPERAGE 16 12 16 24
WALL SOCKET
CONFIGURATION
RECEPTACLE NUMBER NEMA 5-20R NEMA 6-15R NEMA 6-20R NEMA 6-30R
ELECTRICAL HEAT OPTIONS N/A 2.5 3.6 4.2 - 5.0

13
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Performance data (cont.)
Hydronic Heat Option Performance Data
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
2 20137 17182 20524 17182 19602 16491
3 20512 17505 20905 17505 19967 16803
4 20867 17813 21267 17813 20314 17099
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
2 33651 27535 34371 27535 32444 26181
3 34207 28069 35032 28069 33069 26690
4 34819 28577 35659 28577 33662 27174
208 VacSteam
Pressure
(psig)
High-Capacity Hydronic Coil (P/N 6030390) Heang Capacity (Btuh) - Steam
Models EZ07, EZ09, EZ12 Models EZ07, EZ09, EZ12, EZ16 Models EZ07, EZ09, EZ12, EZ16
115 Vac 230 Vac
Steam
Pressure
(psig)
Standard Hydronic Coil (P/N's 6030245, 6030261) Heang Capacity (Btuh) - Steam
Models EZ07, EZ09, EZ12
Models EZ07, EZ09, EZ12, EZ16
Models EZ07, EZ09, EZ12, EZ16
115 Vac
230 Vac
208 Vac
Coil Valve
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
0.50 0.043 0.010 5061 4733 6680 6223 8453 7823 5100 4733 6735 6223 8526 7823 5006 4648 6603 6103 8348 7656
0.63 0.043 0.017 6051 5582 7798 7146 9374 8580 6107 5582 7877 7146 9471 8580 5971 5461 7686 6980 9238 8378
0.75 0.043 0.023 6713 6119 8364 7612 10045 9131 6785 6119 8455 7612 10157 9131 6611 5969 8234 7423 9888 8900
0.88 0.086 0.032 7127 6458 8869 8024 10642 9616 7209 6458 8973 8024 10769 9616 7011 6290 8723 7813 10464 9359
1.00 0.086 0.042 7448 6719 9262 8341 11104 9987 7539 6719 9375 8341 11243 9987 7322 6537 9101 8112 10909 9709
1.13 0.130 0.053 7747 6959 9624 8631 11530 10326 7845 6959 9748 8631 11680 10326 7610 6763 9451 8386 1
1320 10029
1.25 0.130 0.065 7986 7149 9914 8861 11869 10595 8090 7149 10045 8861 12029 10595 7840 6943 9729 8602 11646 10282
1.38 0.173 0.079 8213 7329 10188 9078 12190 10847 8324 7329 10327 9078 12359 10847 8058 7112 9993 8805 11954 10519
1.50 0.216 0.094 8398 7475 10412 9253 12451 11052 8514 7475 10558 9253 12628 11052 8236 7249 10208 8970 12205 10710
1.63 0.259 0.111 8578 7616 10627 9422 12703 11247 8699 7616 10779 9422 12886 11247 8408 7381 10415 9128 12446 10893
1.75 0.302 0.128 8726 7731 10806 9561 12910 11409 8851 7731 10963 9561 13100 11409 8550 7489 10586 9258 12645 11044
1.88 0.346 0.147 8871 7844 10980 9696 13113 11565 9001 7844 11143 9696 13309 11565 8690 7595 10753 9384 12839 11190
2.00 0.389 0.167 8993 7939 11126 9808 13282 11696 9126 7939 11293 9808 13484 11696 8806 7684 10893 9490 13001 11312
2.13 0.389 0.189 9113 8032 11270 9919 13450 11824 9251 8032 11442 9919 13657 11824 8922 7771 11030 9593 13161 11432
2.25 0.475 0.211 9215 8111 11392 10013 13
591 11932 9356 8111 11568 10013 13802 11932 9019 7844 11147 9681 13296 11533
2.38 0.518 0.236 9317 8189 11513 10106 13731 12040 9461 8189 11693 10106 13947 12040 9116 7917 11263 9768 13430 11633
2.50 0.562 0.260 9404 8255 11617 10185 13851 12131 9550 8255 11800 10185 14071 12131 9199 7979 11362 9841 13544 11718
2.63 0.648 0.288 9491 8322 11721 10264 13971 12222 9640 8322 11907 10264 14195 12222 9283 8041 11461 9915 13659 11803
2.75 0.691 0.315 9565 8379 11810 10332 14074 12300 9717 8379 11999 10332 14301 12300 9354 8094 11546 9978 13757 11876
160°F EWT 180°F EWT
Flow
Rate
(GPM)
Models EZ07, EZ09, EZ12 Models EZ07, EZ09, EZ12, EZ16 Models EZ07, EZ09, EZ12, EZ16
200°F EWT
Pressure Drop
(psig) 200°F EWT
208 Vac
200°F EWT
115 Vac 230 Vac
Standard Hydronic Coil (P/N's 6030245, 6030261) Heang Capacity (Btuh) - Hot Water
180°F EWT160°F EWT 160°F EWT 180°F EWT
Coil Valve
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(360 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(375 CFM)
Lo Fan
(260 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
Hi Fan
(340 CFM)
Lo Fan
(240 CFM)
0.50 0.043 0.010 8291 7676 10687 9869 13293 12244 8363 7676 10784 9869 13417 12244 8187 7517 10549 9657 13116 11972
0.63 0.043 0.017 9852 8980 12664 11487 15222 13746 9956 8980 12805 11487 15402 13746 9703 8758 12463 11189 14968 13375
0.75 0.043 0.023 11036 9926 13742 12311 16431 14704 11171 9926 13918 12311 16643 14704 10844 9648 13494 11955 16132 14275
0.88 0.086 0.032 11829 10526 14653 13022 17511 15544 11991 10526 14855 13022 17755 15544 11602 10205 14368 12620 17168 15061
1.00 0.130 0.042 12407 10971 15360 13565 18347 16184 12585 10971 15584 13565 18617 16184 12155 10621 15045 13127 17967 15657
1.13 0.130 0.053 12941 11379 16013 14060 19118 16767 13137 11379 16258 14060 19413 16767 12666 11000 15669 13587 18703 16197
1.25 0.173 0.065 13368 11700 16533 14450 19731 17224 13579 11700 16796 14450 20047 17224 13073 11297 16165 13947 19287 16620
1.38 0.216 0.079 13773 12001 17025 14814 20309 17651 13997 12001 17305 14814 20646 17651 13459 11576 16633 14284 19837 17014
1.50 0.259 0.094 14102 12244 17425 15108 20779 17994 14338 12244 17719 15108 21133 17994 13772 11800 17012 14555 20283 17331
1.63 0.302 0.111 14419 12477 17809 15388 21229 18322 14667 12477 18118 15388 21600 18322 14072 12015 17376 14813 20709 17632
1.75 0.346 0.128 14680 12668 18125 15618 21599 18590 14938 12668 18446 15618 21986 18590 14320 12191 17676 15025 21060 17879
1.88 0.389 0.147 14935 12853 18433 15841 21959 18850 15203 12853 18766 15841 22360 18850 14562 12361 17967 15230 21401 18118
2.00 0.432 0.167 15149 13007 18690 16026 22260 19066 15424 13007 19034 16026 22672 19066 14764 12503 18211 15400 21685 18316
2.13 0.475 0.189 15359 13159 18943 16208 22556 19277 15643 13159 19297 16208 22980 19277 14963 12642 18450 15567 21964 18509
2.25 0.518 0.211 15536 13286 19157 16361 22805 19455 15828 13286 19520 16361 23239 19455 15130 12758 18652 15706 22200 18672
2.38 0.605 0.236 15713 13412 19370 16512 23052 19631 16011 13412 19741 16512 23497 19631 15297 12874 18853 15845 22433 18832
2.50 0.648 0.260 15863 13519 19550 16640 23263 19779 16168 13519 19929 16640 23716 19779 15439 12972 19023 15962 22632 18968
2.63 0.734 0.288 16014 13626 19731 16768 23473 19928 16325 13626 20117 16768 23935 19928 15581 13070 19194 16079 22830 19104
2.75 0.778 0.315 16143 13717 19885 16877 23653 20054 16459 13717 20278 16877 24123 20054 15703 13153 19340 16178 22999 19219
160°F EWT 180°F EWT 160°F EWT 180°F EWT
Flow
Rate
(GPM)
Pressure Drop
(psig)
High-Capacity Hydronic Coil (P/N 6030390) Heang Capacity (Btuh) - Hot Water
Models EZ07, EZ09, EZ12
Models EZ07, EZ09, EZ12, EZ16
Models EZ07, EZ09, EZ12, EZ16
115 Vac 230 Vac 208 Vac
200°F EWT 200°F EWT 200°F EWT160°F EWT 180°F EWT

14
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Dimensional drawings
Units must be installed in accordance with all applicable codes. Ensure there is adequate clearance for ser-
vicing and proper operation. A minimum of 18 inches in front of the chassis is required. Provide additional
space for service technician to work on the unit. Ensure that drapes, bed, bedspread, furniture, etc., DO
NOT block either return or discharge air openings.
1 1/4” RECESSED
LOUVER
WALL SLEEVE
ENCLOSURE 9”
5”
42”
52”
1/2” 3 1/2”
FLOOR SPACE FOR PIPING
ROUGH-IN (TYP R.H. & L.H.)
4”
REMOVABLE FRONT PANEL
Figure 1 Top View
21”
3”
52”
1/2”
1 3/4”
WALL SPACE FOR
PIPING ROUGH-IN
(TYP R.H. & L.H.)
3 1/2”
REMOVABLE KICKPLATE
Figure 2 Front View

15
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Panel/Curtain/Window Wall Application
Units must be installed in accordance with all applicable
codes. Ensure there is adequate clearance for servicing
and proper operation. A minimum of 18 inches in front of
the chassis is required. Provide additional space for ser-
vice technician to work on the unit. Ensure drapes, bed,
bedspread, furniture, etc., DO NOT block either return or
discharge air openings.
WALL THICKNESS (IN
INCHES)
WALL SLEEVE
PART NUMBER
SLEEVE
DEPTH
ENCLOSURE
PART NUMBER
ENCLOSURE
DEPTH
5 to 5-3/4 2401135-00 13-3/4 4082338 17
6 to 6-3/4 2401135-00 13-3/4 4082337 16
7 to 7-3/4 2401135-00 13-3/4 4082336 15
8 to 8-3/4 2401135-00 13-3/4 4082335 14
9 to 9-3/4 2401135-00 13-3/4 4082334 13
10 to 10-3/4 2401135-00 13-3/4 4082333 12
11 to 11-3/4 2401135-00 13-3/4 4082332 11
12 to 12-3/4 2401135-00 13-3/4 4082331 10
13 to 13-3/4 2401135-00 13-3/4 4082330 9
ENCLOSURE DEPTH
CHASSIS
WINDOW SILL
SHEET ROCK
ENCLOSURE
WALL THICKNESS
WALL
STUD
WALL SLEEVE
*EXAMPLE TYPICAL APPLICATION
A/C PANEL
EXTERNAL
LOUVER
MULLION
Figure 3 Typical Panel/Curtain/Window Wall Application
ENCLOSURE DEPTH
(SEE CHART FOR DEPTH OPTIONS)
52”
21”
3” - 6”
Figure 4 Room Enclosure Dimensions
SLEEVE DEPTH
(SEE CHART FOR
DEPTH OPTIONS)
42”
16”
13.75”
Figure 5 Wall Sleeve Dimensions

16
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Block Wall Application
Wall Sleeve and Room Enclosure Selection (Panel
Wall)
To select the correct enclosure rst determine wall thickness. Wall thickness is measured from the indoor
sheet rock panel to the outside wall.
ENCLOSURE DEPTH
(SEE CHART FOR DEPTH OPTIONS)
52”
21”
3” - 6”
Figure 6 Room Enclosure Dimensions
SLEEVE DEPTH
(SEE CHART FOR
DEPTH OPTIONS)
42”
16”
15”
Figure 7 Wall Sleeve Dimensions
WALL THICKNESS (IN
INCHES)
WALL SLEEVE
PART NUMBER
SLEEVE
DEPTH
ENCLOSURE
PART NUMBER
ENCLOSURE
DEPTH
5 to 5-3/4 2400405-00 15 4083373 19
6 to 6-3/4 2400405-00 15 4082339 18
7 to 7-3/4 2400405-00 15 4082338 17
8 to 8-3/4 2400405-00 15 4082337 16
9 to 9-3/4 2400405-00 15 4082336 15
10 to 10-3/4 2400405-00 15 4082335 14
11 to 11-3/4 2400405-00 15 4082334 13
12 to 12-3/4 2400405-00 15 4082333 12
13 to 13-3/4 2400405-00 15 4082332 11
14 to 14-3/4 2400405-00 15 4082331 10
Figure 5 Typical Block Wall Application

17
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Installation Data
For Replacement Units
1. Inspect the existing wall sleeve to insure
it is not damaged and that it is securely
mounted in the wall. Use a level gauge to
insure the sleeve is pitched properly. Be
sure that any gaskets originally mounted on
the wall sleeve that are missing or worn be
replaced.
2. Certain installations with extended sleeves
will require the use of baes. Sheet metal
baes are attached to the condenser coil
ange and have seals on their outer surface.
ese seals will seat against the outdoor
grill when the unit is slid into an extended
wall sleeve. It is important that units
installed in extended wall sleeves have these
baes installed. Without baes, compres-
sor life may be shortened.
3. Inspect the unit specication label in order
to identify the model number. At this time
voltage, capacity, and other special features
should be noted.
4. Be sure the amperage of the dedicated elec-
trical service to the unit is correct. Use of
an extension cord will void warranty.
Receiving Units
Do not store or transport the unit on end. For
proper storing, each carton is marked with
“up” arrows. In the event that elevator transfer
makes up-ended positioning unavoidable, abso-
lutely insure the unit is in the normal upright
position for at least 24 hours before operat-
ing. e units must be handled with care at all
times. Rough handling can damage internal
electrical and refrigeration components.
Wall Sleeve and Room
Enclosure Selection (Block
Wall)
To select the correct enclosure rst determine wall
thickness, then choose the correct Wall Sleeve and
Enclosure from the chart.
Installation Notes
CAUTION! To prevent damage, this unit
should NOT be operated to provide supplementary
heating and cooling during the construction period.
e unit is designed for operation in a normal indoor
environment. Operating this unit in an unenclosed
space or exposure to construction environment may
result in permanent equipment damage.
1. Units must be installed in accordance with all appli-
cable codes.
2. Ensure that there is adequate clearance for servicing
and proper operation. A minimum of 18 inches in
front of the chassis is required. Provide additional
space for service technician to work on the unit.
3. Any gaps between the air discharge outlet and the
discharge grille will cause the unit to short cycle.
is condition will shorten compressor life. Small
gaps should be sealed with foam rubber gaskets.
Larger gaps may require a sheet metal collar (consult
installing contractor).
4. Be sure that the amperage of the dedicated electrical
service to the unit is correct.
5. Aer the unit is installed in the sleeve, the shipping
carton can be cut down and secured to the unit to
protect it during the construction phase.

18
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
Installation Data (cont.)
Installation Checklist
Installation and maintenance should be performed
by qualied personnel who are familiar with local
codes and regulations, and are experienced with this
type of equipment.
• All electrical connections and circuits must be
installed in compliance with and conform to
the National Electrical Code (USA), Canadian
Electrical Code (Canada), and local codes that
have jurisdiction.
• Ensure the supply air outlet is properly sealed
to discharge of enclosure.
• Electrical power is disconnected during instal-
lation or service.
• Condenser air inlet and outlet MUST be clear
and free of obstructions.
• Condenser seals and baes, where applicable,
must be installed.
• Ensure that drapes, bed, bedspread, furniture,
etc., DO NOT block either return or discharge
air openings.
• When existing wall sleeves are utilized, inspect
existing wall sleeve.
Framing
Proper building practices must be used when con-
structing a wall opening to support a PTAC wall
sleeve and chassis. Units must be installed in accor-
dance with all applicable codes.
MAIN
6” FROM
FINISHED
FLOOR
CRIPPLE
JACK STUDS
16 1/2”
HEADER - (1) 4”X4” OR
(2) 2” X 4” ON EDGE
42 1/2”
FLOOR
JACK STUD
SUB-FLOOR
STUD
Figure 8 Framing and Minimum Wall Opening
Electrical Outlet Location
e outlet must be located within the shaded area on
the illustration below.
16 1/2”
6” FROM
FINISHED FLOOR
42 1/2”
REQUIRED OUTLET
LOCATION
4 1/4” MAX
6”
Figure 9 Outlet Location
Other manuals for EZ Series
3
This manual suits for next models
1