IV Produkt EcoHeater Series Installation guide

Translation of the original instructions
Operation and Maintenance
NEW EcoHeater 060-300
Order number:
Project:

Unit specifications
Unit parts and accessories
Damper (code EMT-01)
Sound attenuator (code EMT-02)
Combustion gas bypass (code EHP-B)
Size
060 100 150
190 240 300
Filter
Coarse-65% (G4)
ePM10-60% (M5)
ePM2.5-50% (M6)
ePM1-50% (F7)
ePM1-70% (F8)
ePM1-85% (F9)
ePM1-70% (C7)
Aluminium

Table of Contents
1 Safety precautions
1.1 Lockable safety switch .............................................................................4
1.2 Inspection doors ...........................................................................................4
1.3 Electrical connection ..................................................................................4
1.4 Compressor section ...................................................................................4
2 General
2.1 Intended use ....................................................................................................5
2.2 Manufacturer ....................................................................................................5
2.3 Designations ....................................................................................................5
2.4 CE marking and EU Declaration of Conformity ......................6
2.5 Maintenance .....................................................................................................6
2.6 Handling of refrigerant ..............................................................................6
2.7 Extended warranty .......................................................................................7
2.8 Spare parts ........................................................................................................7
2.9 Dismantling and decommissioning .................................................7
3 Technical description
3.1 Design ...................................................................................................................8
3.2 Function ...............................................................................................................9
4 Wiring instructions and fuse protection
4.1 Wiring diagrams ..........................................................................................12
4.2 Recommended fuse protection and power supply ..........12
4.3 Wiring instructions ....................................................................................13
5 Operation
5.1 Commissioning ...........................................................................................14
5.2 Commissioning combustion gas bypass .................................15
6 Maintenance instructions
6.1 Service schedule ........................................................................................16
6.2 Filters (code ELEF) ....................................................................................17
6.3 Fan unit (code ENF) ..................................................................................20
6.4 Damper (code EMT-01) .........................................................................23
6.5 Combustion gas bypass (code EHP-B) .....................................24
6.6 Sound attenuator (code EMT-02) ...................................................25
6.7 Compressor section (code EHP-C) ..............................................26
7 Troubleshooting
7.1 Troubleshooting in the event of an alarm .................................28
7.2 Troubleshooting via symptoms and status message ......29
7.3 Alarm reset .....................................................................................................30

Page 4
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
1 Safety precautions
Observe warning labels on the unit as well as the following safety precautions:
1.1 Lockable safety switch
WARNING!
High voltage and rotating fan impeller, risk of personal injury.
Working on/servicing the unit –Shut down the unit via the service
switch in the control equipment, then turn the safety switch to the 0
position and lock it.
NB:
The safety switch is not designed for starting/stopping the unit. Always use
the service switch in the control equipment to start and shut down the unit.
1.2 Inspection doors
WARNING!
Positive pressure inside the unit, risk of personal injury.
Allow the pressure to drop before you open the inspection doors.
WARNING!
Rotating fan impeller, risk of personal injury. Shut down the unit via
the service switch in the control equipment, then turn the safety
switch to the 0 position and lock it. Wait at least 3 minutes before
opening inspection doors.
NB:
The doors in front of moving parts should normally be locked; there are no
safety guards. Before carrying out work, unlock the doors with the key pro-
vided.
1.3 Electrical connection
WARNING!
Rotating fan impeller, risk of personal injury. The unit must not be
energised until all ducts have been connected.
NB:
Wiring of connections and other electrical work may only be carried out by
a qualified electrician or by service personnel recommended by IV Produkt.
1.4 Compressor section
WARNING!
Hot surfaces, risk of personal injury. Shut down the unit via the ser-
vice switch in the control equipment, then turn the safety switch to
the 0 position and lock it. Wait at least 30 minutes before opening
the compressor inspection doors.

Page 5
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
2 General
2.1 Intended use
The EcoHeater extract air heat pump is intended for energy recovery from the
extract air in apartment blocks.
When installed indoors, the air handling unit must be installed in an area that
maintains a temperature between +7 and +30°C, and with a moisture content of
<3.5 g/kg in the fan room in winter. The unit can also be equipped for installation
in cold attics or outdoors.
Any other use and installation in other environments are prohibited unless spe-
cifically permitted by IV Produkt AB.
2.2 Manufacturer
The EcoHeater extract air heat pump is manufactured by:
IV Produkt AB
Sjöuddevägen 7
SE-350 43 VÄXJÖ
2.3 Designations
The EcoHeater extract air heat pump comprises two sections, a fan section and
compressor section, as well as a possible combustion gas bypass.
Each section has a model identification label placed on the front.
The model type plate shows the series number and the requisite designations to
identify the section.
Kodnyckel
Code key
Beteckning
Project name
Ordernummer
Order number
Max. varv
Max. rev.
Tillv. ort
Made in Tillv. månad
Manuf. month
YYMM
Modell
Model
– –
Max. temp. °Cr/m
Art. Nr. 19121-1001
Typical model identification label

Page 6
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
2.4 CE marking and EU Declaration of Conformity
EcoHeater extract air heat pumps are CE marked, which means that upon
delivery, they conform to applicable provisions in EU Machinery Directive
2006/42/EC as well as to the EU Directives applicable to other types of air
handling units, e.g. the Pressure Equipment Directive.
As certification confirming that the requirements have been met, we provide
an EU Declaration of Conformity, which is available under Documentation at
ivprodukt.docfactory.com, or under Order unique documentation at
docs.ivprodukt.com.
0
1
Art. Nr. 19194-0001_01
12 3
180
s
Typical CE label for air handling units
2.5 Maintenance
The ongoing maintenance of this unit can be carried out either by the person
normally in charge of maintaining the building or through a contract with a well-
reputed service company. Service and repair of the refrigerant circuit are carried
out by a certified refrigeration technician.
2.6 Handling of refrigerant
The following information summarises the requirements and guidelines for han-
dling the refrigerant used in cooling units. For further information, see the F-gas
Regulations.
The unit is marked with the amount of refrigerant and carbon dioxide equivalent,
alternatively see docs.ivprodukt.com (Technical data).
Operator responsibilities
By operator, we refer to the European Parliament’s definition: “...the natural or
legal person exercising actual power over the technical functioning of the equip-
ment and systems...”.
Generally speaking, the unit operator must:
• Minimise and prevent leakage
• Take corrective action to remedy any leakage that arises
• Ensure that the service and repair of the refrigerant circuit are carried out by
a certified refrigeration technician
• Ensure that refrigerant is handled in an environmentally secure manner and
in accordance with national regulations.

Page 7
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
Leakage inspection and registration
For size 060-190 no further actions are needed beyond operator responsibility,
see "Operator responsibilities" page 6.
For size 240-300:
• Leakage inspection must be conducted by a certified refrigeration techni-
cian:
during installation/commissioning
periodically at least once per 12 months between inspections
within one month after any work is performed (for example tightening a leak
or replacing components).
• The operator must record events, such as the volume and type of refrigerant
topped up, refrigerant taken into possession, results of inspections and work
done, person and company who carried out service and maintenance.
2.7 Extended warranty
In cases in which the equipment delivered falls under a 5-year warranty, in ac-
cordance with ABM 07 with supplement ABM-V 07 or in accordance with NL 09
with supplement VU13, the IV Produkt Service and Warranty Manual is supplied
with the product.
In order to lay claim to an extended warranty, a complete, documented and
signed IV Produkt Service and Warranty Manual must be presented.
2.8 Spare parts
Spare parts and accessories for this unit are ordered from your nearest IV
Produkt sales representative. When ordering, state the order number and
designation. These are stated on a model type plate, affixed to each component.
There is a separate spare parts list for the unit, refer to Order Unique
Documentation at docs.ivprodukt.com.
2.9 Dismantling and decommissioning
When an air handling unit is to be dismantled, separate instructions must be fol-
lowed, see Dismantling and decommissioning the AHU under Documentation at
ivprodukt.docfactory.com.

Page 8
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
3 Technical description
3.1 Design
The EcoHeater extract air heat pump comprises two sections, a fan section and
compressor section.
Fan section Compressor section
Fan section
The fan section has a direct driven chamber fan with an EC motor and deep-
ridged filter. EcoHeater sizes 240 and 300 have double fans. The fan unit is with-
drawable. Replace the filter from the front of the unit.
Compressor section
The compressor section comprises a DX heat recovery coil, electronic expan-
sion valve, a variable speed controlled compressor, fully soldered plate heat
exchanger (between refrigerant and the liquid side), frost-protected evaporation
water outlet for outdoor operation, and integrated control equipment with electri-
cal connection.
The cooling circuit is integrated in the compressor section. The compressor and
control components are shielded from the extract air stream. The cooling circuit
is factory tested and built in accordance with PED 2014/68/EU, Module A2.
Designed in accordance with EN378.
The cooling circuit is supplied with a high-pressure switch, as well as protection
and alarm functions for high/low pressure. The cooling circuit is controlled so
freezing does not occur in the extract air coil. Refrigerant is R410a.
All piping and electrical connections are made via the front. Frost protection
(heating wire) for the condensation outlet is a maximum of 1 metre from the Eco-
Heater’s casing for outdoor operation.

Page 9
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
3.2 Function
General
The incoming water to the EcoHeater must be at least 20 °C to ensure the
operational safety of the EcoHeater.
Recovered energy is returned to the property's heating system.
max temp out = 60 ˚C
min temp in = 20 ˚C
max temp in = 53 ˚C
normal ∆t = 7 ˚CCP1
GT3
EcoHeater
Min 10 °C
Max 30 °C
Drain
CP2
GT5
GT6
GT7
GF1
F0
HP1
LT12
OP1
EV1
GT4 GT2 GP4
GP2
ET1
OT1
EP1
FF
C1 CT1
+2 °C
C1 Compressor, variable speed controlled GT2 Temperature sensor extract air
Drain Condensate drain, frost protected (for
outdoor configuration)
GT3 Temperature sensor outdoor air (north-
east location)
EP1 Low-pressure sensor cooling circuit GT4 Temperature sensor exhaust air
ET1 Pressure sensor cooling circuit suction
gas
GT5 Temperature sensor water out
CT1 Temperature sensor compressor sump GT6 Temperature sensor water in
LT12 Temperature sensor liquid line OT1 Temperature sensor hot gas
EV1 Expansion valve, electronic HP1 High-pressure switch
F0 Frequency inverter for compressor OP1 High-pressure sensor cooling circuit
EA Extract air fan, variable speed controlled CP2 Circulation pump radiator circuit
GF1 Water flow sensor CP1 Circulation pump heat pump
GP4 Pressure extract air duct GT7 Temperature sensor radiator circuit (for
internal control only, not used for exter-
nal control 0 – 10 VDC).

Page 10
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
Control
The EcoHeater has a factory-set time programme for continuous operation at
one speed. The time programme can be changed on the Climatix display for
control at up to three fan speeds.
• In case of malfunction of FF (extract air fan), an alarm sounds and the unit
stops.
• The EcoHeater must be interlocked via circulation pump CP1.
• If GT6 (temperature sensor water in) registers a temperature that is too high,
the compressor stops. It restarts automatically when the temperature falls to
the permitted value.
• If EP1 (pressure sensor cooling circuit) and/or GT4 (temperature sensor
exhaust air) register a temperature that is too low, the compressor’s speed is
reduced until the temperature reaches the permitted value.
• If OP1 (high-pressure sensor cooling circuit) registers a condensation tem-
perature that is too high, the speed of the compressor is reduced.
• If GT4 (temperature sensor exhaust air) is lower than 12 °C, the compressor
cannot be started.
• If GT4 (temperature sensor exhaust air) is more than 3 °C lower than GT2
(temperature sensor extract air), the compressor cannot be started.
• If GF1 (water flow sensor) registers too low flow, the compressor cannot be
started. Restart occurs automatically when the permitted flow is reached.
Compressor protection
In case of an alarm from FI (frequency inverter) or HP1 (high-pressure switch),
the compressor stops. The high-pressure switch is reset manually.
Temperature control
Temperature control to EcoHeater can be controlled via external control signal
(0-10 VDC from sub-central unit, for example, district heating central), internal
radiator curve or based on accumulation tank temperature, so that full capac-
ity from the unit is utilised before the property’s alternative energy sources are
used.
Pressure control
Pressure control can be used by GP4 maintaining a constant pressure in the
extract air duct. The current air flow can be read on the Climatix display.
If the duct pressure deviates from the setpoint after a set time, an alarm sounds.

Page 11
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
Smoke/fire
If GT2 (temperature sensor extract air) registers a temperature higher than the
set alarm limit, a smoke/fire alarm sounds.
Communication
Communication via Modbus TCP/IP and text-web included as standard.
Current limiting
The EcoHeater is equipped with a function that measures the compressor’s
power consumption. The power consumption can be limited to an adjustable
value. If the unit is connected to a fuse that is less than the one recommended,
this function should be used. For recommended fuse protection, refer to
docs.ivprodukt.com (Technical Data).
To activate the function, do the following on the Carel control unit:
IV Produkt
%
087
Demand:
083%
Status: UnitOn
Inv
ON
1. Press the circle button.
2. Press the down arrow to highlight status – I/O.
3. Press the enter button.
4. Press the up arrow to access the “Current limit” menu.
5. Press the enter button so that the cursor starts flashing.
6. Press the up arrow to change “NO” to “YES”.
7. Press the enter button so that the cursor starts flashing on the row below.
8. Use arrow up/down to set the compressor's maximum power consumption.
Reduce the size of the fuse with the fans’ power consumption, refer to order
unique documentation at docs.ivprodukt.com (Technical Data), or the prod-
uct selection program IV Produkt Designer.
9. Press the enter button.
10.Press the back arrow button twice to return to the start menu.

Page 12
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
4 Wiring instructions and fuse protection
4.1 Wiring diagrams
For wiring diagrams, see order-unique electrical diagrams enclosed with the
delivery of a unit or on docs.ivprodukt.com (Control diagram).
4.2 Recommended fuse protection and power supply
Power supply is connected to the switch in the compressor section.
For recommended fuse protection and power supply, refer to
docs.ivprodukt.com (Technical Data).

Page 13
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
4.3 Wiring instructions
Option 1 - Temperature control
external 0-10 VDC (code STA-08)
208
207
221
222
226
225
209
210
224
223
N
L 1
PE
L 3
L 2
1
N
5
3
2
HB1
N
6
4POWER SUPPLY
3×400V~50Hz
SETPOINT HEATING 0-10V
SIGNAL GND (ACTUAL ZERO)
INTERLOCK FROM
CIRCULATION PUMP
CENTRAL FIRE ALARM, WHERE
FITTED (OPEN CONTACT IN
THE EVENT OF ALARM)
GROUP ALARM
OUTDOOR AIR SENSOR (GT3)
Option 2 - Temperature control
internal radiator curve (code STA-09)
208
207
221
222
226
225
209
210
224
223
N
L 1
PE
L 3
L 2
1
N
5
3
2
HB1
N
6
4
FLOW TEMP SENSOR (GT7)
POWER SUPPLY
3×400V~50Hz
OUTDOOR AIR SENSOR (GT3)
INTERLOCK FROM
CIRCULATION PUMP
GROUP ALARM
CENTRAL FIRE ALARM, WHERE
FITTED (OPEN CONTACT IN
THE EVENT OF ALARM)
Option 3 - Temperature control
of accumulation tanks (code STA-10)
208
207
221
222
226
225
209
210
224
223
N
L 1
PE
L 3
L 2
1
N
5
3
2
HB1
N
6
4POWER SUPPLY
3×400V~50Hz
OUTDOOR AIR SENSOR (GT3)
INTERLOCK FROM
CIRCULATION PUMP
GROUP ALARM
CENTRAL FIRE ALARM, WHERE
FITTED (OPEN CONTACT IN
THE EVENT OF ALARM)
TEMPERATUR SENSOR
ACCUMULATOR TANK (GT7)

Page 14
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
5 Operation
5.1 Commissioning
Commissioning of the unit must be carried out by competent personnel in ac-
cordance with the separate checklist:
THE NEW EcoHeater, Start-up checklist
and according to the separate commissioning protocol:
EcoHeater, Commissioning report
The documents can be downloaded from ivprodukt.docfactory.com.
The validity of the product warranty is conditional on the system having been
commissioned correctly. Working on the unit during the warranty period without
the approval of IV Produkt shall render the warranty void.
The unit was designed and manufactured based on given operation cases
that must comply with the unit’s use for optimal function and a good operating
economy.
External circumstances should not be changed without checking that such
changes are within the unit’s intended area of operation.
When commissioning EcoHeater for an occupied property, the fan section must
be started immediately after installation to avoid disruption to the property’s
ventilation. The compressor section is then commissioned separately.
NB!
It is important that the oil inside the speed-controlled compressor
crankcase is warm before starting the heat pump. The crankcase heat-
ing must be switched on long enough before the unit begins operat-
ing so that the oil maintains a temperature of at least 30 ºC. The maxi-
mum warm-up time is approximately 2–3 hours. The temperature can be
measured externally at the bottom of the compressor.
Prior to commissioning, the contractor must:
NB:
Wiring of connections and other electrical work may only be carried out
by a qualified electrician or by service personnel recommended by IV
Produkt.
1. Connect the unit to the power supply via a lockable safety switch.
2. Connect all ducts.
WARNING!
Rotating fan impeller. The unit must not be energised until all
ducts have been connected.
Follow the troubleshooting instructions in the troubleshooting chart before
contacting a service representative for servicing a unit under warranty. This will
prevent any unnecessary service calls.

Page 15
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
5.2 Commissioning combustion gas bypass
If the EcoHeater is equipped with a combustion gas bypass, check that the
combustion gas bypass:
1. Is connected to the unit’s fan section and connected according to the wiring
instructions, see order-unique wiring diagrams enclosed with the delivery of the
unit or on docs.ivprodukt.com (Control diagram).
2. Shows Control Send and Return.open mode Yes on the Climatix display
(Main menu > Unit > Damper control > Fire damper). If error messages are
displayed, address any errors.
3. Has a working end position function. Go to Start manual test on the Climatix
display (Main menu > Unit > Damper control > Fire damper - Start manual
test). Select Active. If error messages are displayed, address any errors and
restart the test.

Page 16
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
6 Maintenance instructions
6.1 Service schedule
The service schedule comprises actions and service intervals for functional sections that may be part
of the EcoHeater extract air heat pump. The unit consists of one or more of these functional sections.
For the parts that come into question, refer to order unique documentation at
docs.ivprodukt.com (Technical Data).
Make copies of the service schedule for future use before you fill in servicing data for the first time.
Service year 20.......-....... or unit no. ............................... Service performed * (date and signature)
Functional section Code Recommended
action (insp.)
Page
ref. 12 mths 24 mths 36 mths 48 mths
date date date date
Filter ELEF
Check pressure drop
Change filter if
necessary
17 signature signature signature signature
Fan unit ENF
Visual inspection
Clean if necessary
Check the air flow
20 signature signature signature signature
Damper EMT-01
Visual inspection
Clean if necessary
Check tightness
23 signature signature signature signature
Combustion
gas bypass EHP-B
Visual inspection
Clean if necessary
Check tightness
24 signature signature signature signature
Check function 15 signature signature signature signature
Sound
attenuator EMT-02 Visual inspection
Clean if necessary 25 signature signature signature signature
DX heat
recovery coil
EHP-C
Visual inspection
Check drainage.
Clean if necessary
Check function
26 signature signature signature signature
Cooling circuit Periodic inspection 6
*More frequent servicing may be required in certain environments. Replace the filter if the pressure drop
across the filter exceeds the specified final pressure drop.

Page 17
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
6.2 Filters (code ELEF)
The air filter protects sensitive components inside the unit, such as the heat re-
covery coil, from exposure to impurities.
The dust separation efficiency varies considerably between various filter types.
The dust collecting efficiency also varies substantially. Use filters of the same
quality and capacity when you change them.
The filters are designed for one-time use. If they become clogged, the unit will
lose capacity.
Filter data
For filter data, refer to Filter Overview under Documentation at
ivprodukt.docfactory.com. For current filters, see order-unique documentation on
docs.ivprodukt.com (Technical Data and Parts List).

Page 18
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
Inspection
Check the pressure drop across the filter. The pressure drop is measured with a
pressure gauge connected to the measurement outlets. The measurement out-
lets are connected to each side of the filter.
–
+
xx Pa
The filter should be changed if the pressure drop across them exceeds the spec-
ified final pressure drop. It is important to stop the unit before changing filters to
prevent dust from coming loose and being drawn into the unit. Also carry out a
visual inspection of the filter for damage and deposits.
The final pressure drop is specified on the filter section decal (filled in when the
air handling unit is put into operation).
Art. Nr: 19121-1101_02SV
F I LT E R DATA
Nominellt luftflöde
Nominal air flow................................................
Antal filter Mått
Number of filters............ Dimensions........................
............ ........................
............ ........................
Filterklass/Filter Class.............................................
Begynnelsetryckfall
Initial Pressure Drop..................................................Pa
Sluttryckfall
Final Pressure Drop...................................................Pa
m³/s
m³/h

Page 19
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
Filter replacement
1. Shut down the unit via the service switch in the control equipment, then turn
the safety switch to the 0 position and lock it.
NB!
The safety switch is not designed for starting/stopping the unit. Always
use the service switch in the control equipment to start and shut down
the unit.
2. If a filter monitor has been installed, disconnect the requisite measurement
cables to the hatch/post in order to open the inspection hatch.
3. Wait until the fans have stopped, then open the inspection hatch.
WARNING!
Positive pressure inside the unit, risk of personal injury. Allow
the pressure to drop before you open the inspection doors.
4. Release the eccentric rails.
Eccentric rails
5. Remove the old filter by pulling it towards you. Discarded filters should be
disposed of correctly. The filter is completely combustible.
6. Clean the filter cabinet.
7. Install the new filter, press in the eccentric rails to engage them and close
the inspection hatch.
8. If a fixed filter monitor has been installed, reconnect the measurement ca-
bles to the metering sockets on the hatch/post.
9. Start the unit.

Page 20
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
6.3 Fan unit (code ENF)
3
1
2
The fan transports air through the system. The fan shall overcome the flow re-
sistance found in air diffusers, ducts and units.
The fan speed is regulated to provide correct air flow. If the fan generates a low-
er air flow, this will impair the function of the ventilation system.
•If the extract air flow is too low, the ventilation capacity will be unsatisfactory.
•If a centrifugal fan is rotating in the wrong direction, the air flow will still go
the right way, but with a considerable reduction in capacity. Therefore check
the direction of rotation.
1. EC motor with control unit
2. Fan impeller
3. Anti-vibration mounting
This manual suits for next models
6
Table of contents
Popular Heater manuals by other brands

HeatStar
HeatStar HS80CVX Operating instructions and owner's manual

Orbegozo
Orbegozo BP 3200 instruction manual

DeLonghi
DeLonghi HWB Series manual

Elnur Gabarron
Elnur Gabarron IFT Series Installation instructions and user guide

Glen Dimplex
Glen Dimplex Quantum G6 Series manual

Utilitech
Utilitech CZ464EBKLSCN quick start guide