JP Fluid Control BW Series User manual

JP FLUID CONTROL
MANUAL-BW-EN v1.3 www.jpfluidcontrol.com 1
BW-SERIES
ELECTRICAL BALL VALVES
Manual –BW-series
ELECTRICAL BALL VALVES
Energy efficient and robust electrical ball valve with wide field of
application. Common applications include ventilation, heating
systems, solar water heaters, irrigation systems and industrial
equipment.
Features
Value
Media
Neutral liquids and gases.
Medium Temperature
-10..110°C
Ambient Temperature
-10..50°C
Operating pressure
0..10 bar
IP-rating
IP54
All ball valves of the BW series are compatible with the actuators from
the AW1 series. The tables below are showing the different versions.
The product code of a complete electric ball valve is composed of the
code for the actuator and the ball valve.
Example Product Code:
BW2 –012 –AW1 –R230AC
Valve
Pipe Thread
Actuator
Internal Relay
Voltage
2-way 230V AC
G1/2" On/Off
Overview Actuators
Product Code
Power
Supply
Operation
P (W)
Open
T (Nm)
AW1-230AC
230V~50Hz
3 way
5W
16s
4
AW1-R230AC
230V~50Hz
On/Off
5W
16s
4
AW1-024AC
24V~50Hz
3 way
5W
16s
4
AW1-R024AC
24V~50Hz
On/Off
5W
16s
4
AW1-024DC
24V DC
3 way
3W
6s
2.5
AW1-R024DC
24V DC
On/Off
3W
6s
2.5
AW1-012DC
12V DC
3 way
3W
6s
2.5
AW1-R012DC
12V DC
On/Off
3W
6s
2.5
Overview Ball Valves
Code
Pipe
(P)
Function
Orifice (D)
Kv (m3/h)
AxBxC (mm)
LxH (mm)
BW2-012
G1/2"
2/2 way
12 mm
8.6
28x28
50x113
BW2-034
G3/4"
2/2 way
15 mm
21
30x35
58x115
BW2-100
G1"
2/2 way
20 mm
26
35x45
73x120
BW3-012
G1/2"
3/2 way
10 mm
6.4
28x28x28
54x113
BW3-034
G3/4"
3/2 way
13 mm
10
30x35x40
70x115
BW3-100
G1"
3/2 way
18 mm
16
35x45x45
83x120

JP FLUID CONTROL
MANUAL-BW-EN v1.3 www.jpfluidcontrol.com 2
BW-SERIES
ELECTRICAL BALL VALVES
1. TECHNICAL OVERVIEW
1.1.Principle of operation
Ball valves control the flow of a fluid or gas by means of a rotating ball
with a hole. By rotating the ball 90° around its axis, the valve will for
example open or close. The valve can have two or three connection ports
(2-way or 3-way). The three-way balls have a T-shaped hole. Therefore,
different switching schemes are possible. Electric ball valves are actuated
with an electric motor. The AW1 actuator features a transmission to
arrange a smooth and slow opening and closing with a high torque. The
AW1 actuator is equipped with two limit switches. Once the actuator
reaches one of the two end positions (90° rotation), the power supply to
the electric motor shuts down and no electrical power is needed to stay
in the end positions.
The AW1 actuator is available with 3-point control or On/Off control with
internal relay (see Chapter 0).
1.2. Materials
Component
Material
Valve body
Brass (EN: CW617N, CuZn40Pb2)
Ball seal
PTFE
O-ring
EPDM
Actuator housing
PC GF10 (polycarbonate)
Actuator coupling
POM (Polyoxymethylene)
1.3.Circuit Diagram
The table below shows the circuit functions of the ball valves. The 2-way
ball valves are open or closed. The 3-way ball valves can be arranged in
two different ways (by rotating the ball 180°).
2-way
3-way (T-bore)
1.4.Flow chart
The following graph shows the flow rate (l/min) of the ball valves as a
function of the differential pressure across the inlet and outlet of the
valve. The scale of the vertical axis is logarithmic.
1.5. Duty Cycle
The BW-series are suitable for continuous use. High switching
frequencies and high pressures can reduce the lifespan.
1.6. Compliance
The actuators are CE marked and comply with the LVD Directive
(2006/95/EC) and EMC Directive (2004/108/EC), provided that the cables
and connectors are properly connected.
1.7. Description Type Plate
The following figure shows an example of the type plate of the actuator.
Observe the specifications and the connection diagram before using the
product.
10 100 1000
0 1 2 3 4 5 6 7 8 9
Flow rate water (l/min)
dp (bar)
BW2-012 BW3-012
BW2-034 BW3-034
BW2-100 BW3-100

JP FLUID CONTROL
MANUAL-BW-EN v1.3 www.jpfluidcontrol.com 3
BW-SERIES
ELECTRICAL BALL VALVES
2. GENERAL SAFETY INSTRUCTIONS
Please read the safety instructions before installing, using or maintaining
the device.
►This device will contain gas and/or liquid under pressure. The
actuator only complies protection class IP54 (according to IEC
60529), if the device is properly connected. Improper use may
be hazardous.
►This product is not a safety device and may not be used as
such.
►Never put your hands/body parts or other objects into ports
of the valve. The rotating ball can cause serious injuries or
damages.
►Correct transport, proper storage and installation, and proper
use and maintenance, are essential for reliable and error-free
operation. The product may not function properly as a result
of dirt, wear, damage (for example, by dropping) or improper
use. Therefore, the product should not be used in
applications where a malfunction can cause danger or
damage.
►Check the compatibility of the medium used, temperature
and other operating conditions with the materials and
specifications of the product. It is the responsibility of the
user to select the right product for the application.
►This product is not intended or approved for medical
applications, food and/or application in gas appliances.
►Never exceed the limits for pressure, temperature or voltage
as indicated on the product and/or in the technical
documentation.
►It is not allowed to change the construction of this device.
►Beware of electric shock when working with electrical
equipment.
3. INSTALLATION AND MAINTENANCE
3.1. Safety Instructions
►It is recommended to install the electric ball valve in a dry
environment. In moist environments, make sure that no
moisture can penetrate the actuator. Install the ball valve in
a safe way to avoid electric shock, burning or other injuries.
Make sure the electric ball valve is not in contact with or in
the vicinity of flammable materials. Ensure that the product
is protected from frost. Frost may damage the product and/or
block the moving parts, causing the electric ball valve to
malfunction.
►Maintenance may only be performed when the system is not
pressurized, electrically disconnected and cooled down.
►Turn off the power supply before performing any work on the
electric ball valve to prevent the risk of electrical shock and to
prevent activation of the actuator.
►The product is only safe when properly installed and operated
by qualified persons. Please read the safety instructions and
technical documentation carefully before installation, use or
maintenance.
►Ensure a controlled commissioning after installation or
maintenance.
3.2. Installation
Clean fluids and gases
It is recommended to use electrical ball valves in combination with clean
liquids or gases. Dirt can cause excessive wear. Make sure that the pipes
don’t contain dirt before installing the device. Optionally, install a filter
(500 µm) upstream of the electric ball valve.
Mounting the valve
The pipes on both sides of the valve must be securely fastened. During
installation, make sure that force may only be exercised at designated
areas on the valve, such as the hexagon; never on the actuator. Avoid
vibration in the pipes. Use a suitable sealant for threaded connections of
the ball valve. Avoid the entry of thread sealing material in the valve, this
can lead to malfunctioning of the valve.
Position
It is recommended to install the electric ball valve in vertical position with
the actuator facing upwards. This reduces the probability of the collection
of moisture in the actuator. When the electric ball valve is mounted at an
angle, it is recommended to deviate maximally 90° from the vertical
position. Ensure that drops cannot slip along the cable and enter the
actuator.
Installation of the actuator on the coil
►The device can be damaged by the use of unsuitable tools.
►The 3-way valves can be installed in two different ways by
rotating the ball 180°.

JP FLUID CONTROL
MANUAL-BW-EN v1.3 www.jpfluidcontrol.com 4
BW-SERIES
ELECTRICAL BALL VALVES
Off / closed
On / open
2-way
3-way
►The actuator needs to be attached with the aid of the nut
present.
►Make sure that the ball is in the correct position. If necessary,
adjust the position (2) using a wrench.
►The actuator is into the valve body (two ways) with 2-pin (1).
Tighten the nut securely (3), so there is no clearance between
the actuator and the valve.

JP FLUID CONTROL
MANUAL-BW-EN v1.3 www.jpfluidcontrol.com 5
BW-SERIES
ELECTRICAL BALL VALVES
3.3. Electrical Wiring Diagram
Verify that the actuator code matches the connection diagram. Improper
installation can permanently damage the actuator or lead to dangerous
situations. The actuators have internal position switches, which results
that only energy consumed during opening or closing.
AW1-230AC, AW1-024AC (3-point)
BLACK
BLUE
BROWN
Neutral
Phase (close)
Phase (open)
~
o
Connecting the blue control wire closes the valve in 16s. Connecting the
brown control wire opens the valve in 16s. If both control wires are
disconnected, the valve will remain In the current position. In this way,
the position of the valve can be regulated. Never connect the blue and
brown control wires at the same time! This will damage the actuator.
The actuator consumes energy only during opening and closing.
AW1-R230AC, AW1-R024AC (ON/OFF, INTERNAL RELAY)
~BLUE
BRO WN
BLACK
Neutral
Phase
Phase (open)
o
Connecting the control wire (black) opens the valve in 16s. Once the
control wire shuts down, the valve closes in 16s. The actuator consumes
energy only during opening and closing.
AW1-R024DC, AW1-R012DC (ON/OFF, INTERNAL RELAY)
+BLACK
BRO WN
BLUE
Minus
Plus (close)
Plus (open)
-
Connecting the control wire (blue) opens the valve in 6s. Once the
control wire shuts down, the valve closes in 6s. The actuator consumes
energy only during opening and closing.
AW1-024DC, AW1-012DC (3-point)
BLUE
BLACK
BROWN
Minus
Plus (close)
Plus (open)
+
-
Connecting the brown control wire, the valve closes in 6s. Connecting
the black control wire, the valve opens in 6s. If both control wires are
connected, the valve will remain in the current position. In this way,
the position of the valve can be regulated. Never connect the black
and brown control wires at the same time! This will damage the
actuator. The actuator consumes energy only during opening and
closing.
4. SPARE PARTS
The valve bodies and actuators of the BW and AW1 series are
exchangeable. If only one component is defective, this part can be
replaced.
5. DISPOSAL
The removal of the product should be performed in accordance with the
applicable laws. Keep in mind the media that are still present in the valve.
This manual can be downloaded from www.jpfluidcontrol.com Modifications reserved © JP Fluid Control
This document has been prepared with great care. JP Fluid control assumes no responsibility for any errors that may appear in this document. No rights can be derived from this document
This manual suits for next models
4
Table of contents
Other JP Fluid Control Control Unit manuals
Popular Control Unit manuals by other brands

Siemens
Siemens Synco RMZ792 Basic documentation

Turbo
Turbo Eco-Net 128 Use and maintenance instructions

Emerson
Emerson White Rodgers 36H Series installation instructions

Behringer
Behringer 2500 Series quick start guide

Allen-Bradley
Allen-Bradley ControlNet 1786-RPFRL/B installation instructions

Pickering
Pickering 43-182B user manual

Leader Light
Leader Light LL IN8-RSxxx user manual

Monster
Monster MTS YOKE instruction manual

Aritech
Aritech IU2050C Installation sheet

National Instruments
National Instruments NI 9234 Getting started

Miller Electric
Miller Electric V-92 owner's manual

Mankenberg
Mankenberg EB 1.12 Original operating manual