
2-7 Operation Instruction for Installation
1) Prior to installation, please check whether the battery is normal.
Press the reset key RST on the front panel for 3S for startup. During startup, 4 capacity indicator lights on the
front panel, ALM alarm indicator light (red) and RUN running indicator light lights up. Check whether all indicator
lights light up normally; then the ALM alarm indicator light goes out, the RUN running indicator light lights up and
the capacity indicator light lights up according to the capacity.
If the ALM alarm indicator light flashes after startup, it means that the battery has an alarm. The newly installed
battery seldom has alarm. The common alarm is the battery undervoltage alarm (which is resulted from non-use of
the battery for a long time). Such case may be removed after the battery is charged for 30min; if the alarm may not be
removed, please press the reset key RST for 10S, until all LEDs light up for reset, execute the battery reset operation
and confirm whether the alarm is removed. If the alarm is removed, the battery may be used normally. Otherwise the
battery shall be reworked.
2) For the battery which is normal after detection, please press the reset key RST for 3S to execute the battery
ON/OFF operation.
Instructions of
manual
operation of
the reset key
RST
Startup In the OFF state of BMS, press the key for 3S for
startup;
Shutdow
n
In the non-standby state of BMS, press the key for
3S for shutdown;
Reset In the non-standby state of BMS, press the key for
10S, until all LEDs light up for reset.
Instructions: “Shutdown” and “standby” and “startup” and “activation” in Chinese have the same meaning;
3) Installation of the lithium battery, wiring and startup.
Make the battery pack in a standby state, install it in the battery cabinet one by one, the anode and cathode of the
battery pack are connected respectively, which are connected to the switching mode power supply or UPS (Please
note that the switching mode power supply and UPS shall be disconnected from the AC). Press the reset key RST of
one of battery packs for 3S for startup. Such startup battery may activate other batteries which are connected in
parallel (or press the reset key RST of each battery pack for 3S successively) and the whole battery pack with high
capacity enters the working state. Later, apply AC to the power supply equipment such as switching mode power
supply and UPS to make the whole standby system run.
The specification of the connecting line is selected according to the load current, with the common
specifications of the connecting line as follows: