K2K Technology KK2 Pro User manual

凯控科技(深圳)有限公司
K2K Technology (Shenzhen) Ltd.
Intelligent Dual Pump Controller
KK2 Pro Dual Pump Controller (220V, 380V)
Easy to use and simple to set, with basic functions
Patented products, protected by law
K2K Technology (Shenzhen) Ltd.
Tel:0755-86329782
Fax:0755-86329783

KK2 Pro Dual Pump Controller
Table of contents
1.0 Safety information for installing and using the controller..........................2
1.1 Area of Application.................................................................................................2
1.2 Qualification of personnel....................................................................................2
1.3 Safety information for the operator ..................................................................2
1.4 Hazards if safety information is neglected ......................................................2
1.5 Operating manual...................................................................................................3
1.7 Prohibited operations............................................................................................3
1.8 Transport and storage ...........................................................................................3
2.0 General product specifications, characteristics, and optional modes of
operation................................................................................................................................3
2.1 Product specifications............................................................................................3
2.2 Characteristics..........................................................................................................4
2.3 Optional functions and components (specially stated in the order if
required)...........................................................................................................................4
3.0 Settings, operational elements...............................................................................4
3.1 Settings......................................................................................................................4
3.2 Operating elements................................................................................................5
4.0 Controller setting.........................................................................................................6
4.1 Setting contents ......................................................................................................6
4.2 Setting method........................................................................................................9
5.0 Fault messages, possible malfunctions, and solutions..................................9
6.0 Installation, electric connection ...........................................................................12
6.1 Installation...............................................................................................................12
6.2 Electrical connection between power supply, water pump and floating
switch ..............................................................................................................................12
7.0 Air pipe connection...................................................................................................15
8.0 Technical data .............................................................................................................15
1/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
1.0 Safety information for installing and using the controller
1.1 Area of Application
KK2 dual controller is designed to control water pumps used in various
sewage, waste water and rainwater pump stations.
For activating pumps that run in an Ex-area, the following needs to be
considered: The control unit itself has to be mounted outside of the Ex-
area.
If the floating switch is mounted in the Ex-area, the relevant regulations
must be followed.
When connecting motor, the electronic and mechanical motor protection
switch must be set according to the standard range given below.
Three- phase AC 380V 4.5KW
Max.12A
Single-phase AC 220V 2.2 KW
Max. 12 A
1.2 Qualification of personnel
The personnel for installing, initiating, and maintaining the control unit
has to hold according qualifications for this work.
1.3 Safety information for the operator
The existing safety rules of local energy supply companies should be
followed. When opening the unit or when maintaining the pump the
power to the control unit needs to be completely shut off through an
external pre-fuse.
1.4 Hazards if safety information is neglected
Neglecting safety information will endanger people and product/ unit.
When neglecting safety information you are subject to lose any
entitlement to damages.
2/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
1.5 Operating manual
A circuit protection to the mains of max. 3 x 25 A needs to be installed
(When the max. current of the protection is3 x 25A, a single-core lead
with the cross section of 4 mm² is used)
1.6 Arbitrary modification and supply with replacement parts
Modifications of the product are only authorized if cleared with the
manufacturer in advance. Original parts and accessories authorized by the
manufacturer serve safety purposes. Using different parts may waive
manufacturer’s liability for possible consequences.
1.7 Prohibited operations
The safety of operation of the delivered product can only be granted when
the product is used appropriately according to paragraph 1.1 of the
operating manual. The limiting values given in technical values have to be
adhered to in any case.
1.8 Transport and storage
The control unit needs to be stored and transported avoiding damage by
blows, crush, and temperatures outside the realm of -20℃to +60℃.
2.0 General product specifications, characteristics, and optional modes of
operation
2.1 Product specifications
KK2 dual water pump controller is easy to use and simple to set. The
control information such as start time, run time and rated current can be
set into the controller through the Set button. All setting data, working
current and alarm information can be display on the screen.
3/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
2.2 Characteristics
- LCD plain text display - Current monitoring
- No-load protection - Float High Level
- Over load protection - Phase sequence and phase loss alarm
- Input voltage display - 72h Auto. Inspect.
- Service Mode - FS Start Delay & FS Stop Delay
- Acoustic alarm - Simple pump operation
- Manu/Auto functions - Dual pump alternation start
- 220V and 380V available
2.3 Optional functions and components (specially stated in the order if
required)
- Level FS
- High Level Flow Switch (FS)
- Schneider Contactor
- Chint Contactor
3.0 Settings, operational elements
3.1 Settings
Through the Set button and LCD display, all information and settings can
be checked. If a setting needs to be adjusted, the Set button has to be
turned until the display shows the desired setting. Now the Set button
needs to be pressed. The value saved last will start to flash. Settings may
be changed by turning the Set button. Once the desired value is attained,
it needs to be confirmed with the Set button. The value stops flashing and
is saved.
4/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
3.2 Operating elements
Set
button
By turning the Set but
ton, all settings as
well as fault messages, motor current,
power three-
phase voltage can be
checked. Additionally, the settings are
adjusted with the Set button.
Manual /
Auto
Red LED ON: Fault
Yellow LED ON: Run
Green LED ON: Auto
Green LED flashing: Manual
Green, yellow and red LEDs OFF: press
“0” to enter the pump forced stop
mode. Manual mode has turned off
automatically after 2 minutes to prevent
dry run.
Alarm
In case of fault, alarm will work to issue a
warning sound.
For “High Level FS Alarm” or “High
Level”, the alarm will disappear
automatically when the level returns to
the Stop Level.
Press the “Select /
Confirm” to conceal the
alarm.
5/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
4.0 Controller setting
4.1 Setting contents
The following chart shows different options for settings. The option will
appear in the upper line of the display while the lower line will show the
value to be changed. (If there is no setting operation, the screen will turn
off automatically in 2 minutes)
1st line 2nd line
Settings Explanation
Pump 1:
Current A FS S: ON/OFF
When the “Level Control” is “FS” mode, the
current pump current, lower FS S and upper FS X
ON/OFF will be displayed automatically.
Pump 2:
Current A FS x: ON/OFF
Pump 1:
Current A Actual level
When the “Level Control” is “Pressure”
mode, the pump current and level will be
displayed automatically.
Pump 2:
Current A
Voltage Monitor the pump voltage in real time
Current Monitor the pump current in real time
Rat. Current 1.0–12.0 A Set the pump rated current for normal operation
Max Try run 1-60 S
When the pump current during operation is 1/2
of the rated current and the non-load operating
time exceeds the set non-
load time, pump will
stop and issue an alarm.
6/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
1st line 2nd line
Settings Explanation
Level start 0-200cm
The value determines the start level of the first
pump (min. 5cm)
Level stop 0-200cm
The value determines the stop level of the first
pump (min. 3cm)
Peal level start 0-200cm The value determines the start
level of the
second pump
Peal level stop
0-200cm
The value determines the stop level of the
second pump
Pressure Stop
Delay
0-180 S
After the Stop level is reached, the pump will
keep running until the pre-
set time is over. The
value 0 deactivates this function.
High level 1-200cm
When the “Level Control” is “Pressure”
mode, and the level reaches the high level, the
controller will
work to issue a beep sound and
start the dual pump.
Comp height 0-99cm
When the “Level Control” is “Pressure”
mode, with the set Comp height, the height
displayed in the “Actual Level” is consistent
with the actual height.
FS Start Delay 0–180 S
In the FS control mode, the lower FS floats, the
pump can be delayed to start. With “0” set,
the start delay is not required.
FS Stop Delay 0–180 S In the FS control mode, the lower FS lowers, the
pump can be delayed to stop. With “0” set,
the start delay is not required
7/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
1st line 2nd line
Settings Explanation
Run Time 0-60 min
When one pump is running under the basic
load, if the total running time of the single
pump exceeds the set “Run Time”, the pump
will run alternately. After
three alternate runs,
the pump will issue an alarm and the LCD
display will display the “Run Time Alarm” (0-
60min; 0= Turn off this function). The alternate
condition is that two pumps are running in the
Auto mode.
Auto. Inspect. 0-10 S
After pump is out of service for 72h, the pump
will run for 1-10s automatically.
0=Turn off this function.
Power Supply Three-phase /
Single-phase
Three-phase / Single-phase; the “Three-
phase” or “Single-phase” option is available
for power supply.
Service mode OFF/ON ON: Set all data
OFF: Only display the set data but unable to set.
In the “ON” state, converted to the “OFF”
automatically if there is no any operation for 20
minutes.
Single P Mode
ON/OFF Check which pump can work normally
automatically; the single pump can run
automatically in the original set mode. Used for
maintenance of one pump.
Level Control Level Control models available include “FS” or
“Pressure”
Language Available language: Chinese, English, or German
language
8/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
1st line 2nd line
Settings
Explanation
Alarm info Include: a. High level alarm! b. Pump non-load
alarm!
c. Pump overload alarm! d. Alternate run alarm!
e. No
In the Auto mode, in case of an alarm, jump to
the home page.
4.2 Setting method
By turning the “Confirm/Select” set button clockwise, enter the next
screen, and by turning the “Set Button” counter clockwise to display the
previous screen. Press the Set button to enter the setting screen, with the
screen flashing in the inverse white color. By turning the Set button
clockwise, increase the value, and decrease the value if counter clockwise;
press this button to confirm the set value and return to the display screen.
Attention when setting: Auto Inspection time < Non-load protection time
5.0 Fault messages, possible malfunctions, and solutions
Message on Display
Possible cause Solution
High Level
1. The level floating switch
does not work
2. The set run time is too
short
3. The delay start time is too
long
1. Check the level floating
switch, and remove any
impurity if the switch is
blocked; if the FS contact
failed, replace the floating
switch.
2. Adjust the run time.
3. Adjust the delay start time.
9/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
Message on Display
Possible cause Solution
High water switch
1. The level floating switch
does not work
2. The set run time is too
short
3. The delay start time is too
long
1. Check the level floating
switch, and remove any
impurity if the switch is
blocked; if the FS contact
failed, replace the floating
switch.
2. Adjust the run time.
3. Adjust the delay start time.
A. No-load
The set delay stop time is
too long
The lower FS failed
Adjust the delay stop time
Check the FS
B . No-load
The set delay stop time is
too long
The lower FS failed
Adjust the delay stop time
A. Over load The current is too large Check the FS
1. Check the pump and
remove any impurities if
winding onto the pump.
2. Check the grid power
supply and pump cable for
electric leakage.
3. Replace any damaged
pump by a new one.
10/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
Message on Display
Possible cause Solution
B. Over load The current is too large
1. Check the pump and
remove any impurities if
winding onto the pump.
2. Check the grid power
supply and pump cable for
electric leakage.
3. Replace any damaged
pump by a new one.
Run Time Alarm
1. The lower FS is always in
the ON state or the level is
always at the low start level.
2.Pressure mode: Air pipe
inlet is clogged.
3. FS mode: The lower
floating switch works
abnormally
1.Check the floating switch or
air inlet, and remove any
impurity if blocked; if the
floating switch contact failed,
replace the floating switch.
2.Adjust the run time.
3.Adjust the floating switch
position.
Start/stop level
Start level and Stop level
are reversed each other
Check the set value
Start/flood level
Alarm level and Start level
are reversed each other
Check the set value
Start/ peak level
Low start level and high
start level are reversed each
other
Check the set value
Phase miss alarm Phase missing Check each phase of the input
Phase sequence
alarm
Phase sequence error
Check the output phase
sequence
In the pressure
mode, the water
level is displayed
incorrectly
1. Air leakage from air pipe
2. When connecting air
pipe, the end of the air vent
is not immersed in water.
1.Check each connection of
air pipe for air leakage.
2. Press the Manual button to
drain
the water level below
the air intake, and release the
Manual button.
11/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
6.0 Installation, electric connection
6.1 Installation
The controller can be connected to three-phase five-wire 380V power
supply or single-phase 220V power supply.
6.2 Electrical connection between power supply, water pump and floating
switch
The electric connection must be carried out by the qualified electrical
installation personnel according to the current national regulations.
Main circuit requires a fuse with the max. current of three-phase /
single-phase 16A.
12/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
380V power supply and motor wiring diagram
220V power supply and motor wiring diagram
J3 Temp
Pump1 Pump2
J3 Temp
Pump1 Pump2
13/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
FS and pressure pipe connection
In the pressure mode, the level FSes at 3·4·5·6 positions are not required
to be connected.
The high level alarm FS is floating over other level sensor. When the high
level alarm FS touches, the pump will be started and an alarm will be
issued. High level FS and other level sensor will form a dual protection.
If one pump needs to be removed for repair, press the “0” manually to
turn off the failed pump; the other pump can run normally and
automatically according to the previous setting contents.
Air pressure inlet
J2 Temp
High Level
Peak level start
Level start
14/ 16 Patented products, protected by law

KK2 Pro Dual Pump Controller
7.0 Air pipe connection
The standard configuration of the air pipe connection is 8/6mm hose joint.
When connecting air pipe, the controller shall be at the OFF state and the
air pipe shall be in the suspension non-pressure state in the entire process.
After connecting air pipe and the power supply is turned on, water can be
drained in a container! With the pressure mode available to control level,
drain the level below the air inlet each time to allow the air inlet in the
suspension state. It is recommended to enable the “Stop Delay”
function for this.
8.0 Technical data
No.
Item Technical index Unit Remarks
1 3 phase Rat. voltage 350~410 Vac
2 Max. 3 phase Rat. input
voltage 418 Vac
3 3 phase Rat. power 4.5 KW
4 3 phase Rat. current 8.9 A Pre-set
5 1 phase Rat. voltage 200~240 Vac
6 Max. 1 phase input
voltage 264 Vac
7 1 phase Rat. power 2.2 KW
8 1 phase Rat. current 12 A Pre-set
9 Working temperature -20 - +60 ℃
10 Housing / transparent
cover ABS/PC
11 Protection type IP 66
12 Controller size: 150Wx200Lx100mmH mm
Not including
the water joint
13 Cable hole diameter 2x Ø6~Ø10,2xØ4~Ø8
15/ 16 Patented products, protected by law
Table of contents
Other K2K Technology Controllers manuals
Popular Controllers manuals by other brands

Panasonic
Panasonic AKHRP900P - CAMERA CONTROLLER HC operating instructions

PG Drives Technology
PG Drives Technology SK79761-3 operating manual

Watts
Watts WFC-03 10Z HC RF 24 Quick installation guide

progressive automations
progressive automations LC-241 user manual

Husky
Husky Altanium Delta5 user guide

MultiTrode
MultiTrode MultiSmart Installation & operation manual