Kallista P50047-G5 User manual

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
1 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
P50047-G5
©2015 KALLISTA

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
2 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
THANK YOU FOR CHOOSING KALLISTA
We appreciate your commitment to KALLISTA quality products. Please take a moment to review this manual
before you install your KALLISTA product. If you encounter any installation or performance problems, please do
not hesitate to contact us at the phone number listed at the bottom of the page.
IMPORTANT INFORMATION
WARNING: When using electrical products, basic precautions should always be followed,
including the following:
DANGER: Risk of electric shock. Connect only to circuits protected by a Ground-Fault Circuit-Interrupter
(GFCI) or Residual Current Device (RCD).
WARNING: Risk of electric shock.A qualified electrician should make all electrical connections.
WARNING: Risk of electric shock. Disconnect power before servicing.
WARNING: Risk of injury or property damage. Please read all instructions thoroughly before beginning
installation, including the following requirements.
NOTICE: Follow all local plumbing and electrical codes.
Grounding is required. The unit should be installed by a qualified service representative, and grounded.
Building materials and wiring should be routed away from the blower body and other heat-producing
components of the unit.
Install to permit access for servicing.
A pressure wire connector marked “Earth/Ground” is provided within the wiring compartment. To reduce the risk
of electric shock, connect this connector to the grounding terminal of your electric service or supply panel with
copper wire equivalent in size to the circuit conductor supplying this equipment.
Pressure wire connectors are provided on the exterior of the junction box or control within this unit to permit
connection of a bonding conductor between this unit and all other exposed metal in the vicinity, as needed to
comply with local requirements.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
3 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
PRODUCT INFORMATION
Electrical Requirements
The installation must have a Class A Ground-Fault Circuit-Interrupter (GFCI) or Residual Current Device (RCD).
The GFCI or RCD protect against line-to-ground shock hazard. Use a 220-240 V, 15A, 50/60 Hz dedicated
service for the bath with airjets.
For Canadian installations, install the bath with airjets in accordance with Canadian Electrical Code, Part I.
Product Notices
WARNING: Risk of personal or property damage. Unauthorized modification may cause unsafe
operation or effect performance of the bath with airjets. Do not relocate the bath blower motor, or make
other modifications to the bath system in the absence of kit or other published instructions, as this could
adversely affect the performance and safe operation of the product. KALLISTA shall not be liable under its
warranty or otherwise for personal injury or damage caused by any such unauthorized modification. Refer
to the “Before You Begin” section for blower motor relocation requirements, recommendations, and section
coverage information.
NOTICE: Keep the area around the blower motor clean and free of debris. Ensure that the area around the
blower motor is free of sawdust, insulation, dirt, or other small loose debris. Such material could clog the blower
motor air ducts and reduce the air flow through the blower.
FactoryAssembled Features
Factory assembled components include a blower motor, air harness, control, check valve, butterfly valves, lights
(if provided), electrical harnesses, and an illuminated user keypad. Other than power wiring and plumbing, no
assembly is required.
Connections and ServiceAccess
NOTICE: Provide unrestricted service access to the blower motor. You must provide access for servicing
the blower motor and controls. The access must be located immediately next to the blower motor. Study the
“Rough-In Information” section of this publication.
Before installation, ensure that there is proper access to the blower motor and final connections. If the blower
motor is installed in an enclosed area, an access panel is required at the blower motor. This panel should be at
least 34” (864 mm) wide and 15” (381 mm) high.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
4 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
TABLE OF CONTENTS
Thank You For Choosing Kallista ...................................................................................................................... 2
Important Information ........................................................................................................................................ 2
Product Information ........................................................................................................................................... 3
Electrical Requirements ..................................................................................................................................... 3
Product Notices ................................................................................................................................................. 3
Factory Assembled Features ............................................................................................................................. 3
Connections and Service Access ...................................................................................................................... 3
Table of Contents ............................................................................................................................................... 4
Before You Begin ............................................................................................................................................... 5
Tools and Materials ............................................................................................................................................ 6
Rough-In Information ......................................................................................................................................... 7
1. Prepare the Site ........................................................................................................................................... 8
2. Install the Tiling-In Bead (optional) ............................................................................................................... 9
3. Prepare the Bath with Airjets ........................................................................................................................ 9
4. Secure the Bath to the Subfloor - Standard ............................................................................................... 10
5. Install the Plumbing - Standard .................................................................................................................. 11
6. Make Power Connections - Standard ......................................................................................................... 12
7. Disconnect the Blower Motor and Check Valve - Remote .......................................................................... 13
8. Secure the Bath to the Subfloor - Remote ................................................................................................. 14
9. Mount the Blower Motor and Check Valve - Remote ................................................................................. 15
10. Connect the Cable at the Blower - Remote .............................................................................................. 16
11. Install the Power Cord at the Control - Remote ........................................................................................ 17
12. Install the Plumbing - Remote .................................................................................................................. 18
13. Make Power Connections - Remote ......................................................................................................... 19
14. Test Run the Bath with Airjets ................................................................................................................... 20
15. Complete the Finished Deck or Wall ........................................................................................................ 21
16. Clean-Up After Installation ........................................................................................................................ 21
17. Confirm Proper Operation ........................................................................................................................ 22
18. Operating Sequence ................................................................................................................................ 23
19. Troubleshooting Procedures .................................................................................................................... 25

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
5 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
BEFORE YOU BEGIN
CAUTION: Risk of product damage. Do not lift the bath by the piping or blower motor, or use the piping or
blower motor for structural support of the bath.
NOTE: This bath with airjets allows the blower motor and check valve to remain on the bath support board
(standard installation) as it is shipped or to be relocated to another location (remote installation). Refer to your
applicable installation throughout this installation guide.
For Standard and Remote Installations
We recommend this bath with airjets for drop-in or island installation, depending on the purchased model.
Inspect the bath for damage before you begin installation.
You must install this bath to an adequately supported, level subfloor.
Please read these instructions carefully to familiarize yourself with the required tools, material, and
installation sequences. Follow the sections that pertain to your particular installation. This will help you
avoid costly mistakes. In addition to installation instructions, read all operating and safety instructions.
The variety of installations possible with this bath may require framing procedures other than those
described in this manual.
Confirm adequate mounting and connection space for the faucet specified for your installation.
For Remote Installations
NOTICE: It is not necessary that the blower motor be relocated. The option is provided for the case that a
particular installation makes this effort practical.
For your convenience or accessibility, the blower motor and check valve can be mounted in a remote
location. Choose a space as close to the bath as possible to maximize bath performance. Plan and prepare
for the relocation. Pay attention to the following requirements and recommendations:
●The blower motor must be located within 15’ (4.6 m) of rigid piping from the bath air harness. This
limitation is for total pipe length and applies to any direction changes and elbows. There can be no more
than six changes of direction. There should be as few direction changes as possible.
●The blower motor must be mounted horizontally at least 2” (51 mm) above the floor. Do not mount the
blower motor with the blower motor discharge pointing up.
●The check valve must be relocated with the blower motor.At the new location, the check valve must
be no lower than 24” (610 mm) below the rim of the bath. The check valve must be within 12” (305 mm)
of the blower motor. The check valve must be oriented vertically with the flow arrow pointing up. DO
NOT relocate the control unit. The control unit must remain with the unit.
●Use 1-1/2” PVC or equivalent rigid piping. Use PVC unions or other means of making the installation
maintainable.
●The piping installation must meet the requirements of local plumbing or building codes. Ensure that the
installation does not reduce the fire rating of any walls. Piping must be supported at intervals along the
length in accordance with local codes.
●The blower motor must have adequate ventilation. Do not install the blower motor closer than 1” (25 mm)
from the wall or other objects. Provide a space of at least 15 cubic feet (.4 cubic meters) for cooling.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
6 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
BEFORE YOU BEGIN (CONT.)
●Ensure that the blower motor location is clean and free of dust or debris.
●If appropriate, install an additional access panel for blower motor maintenance.
●The 18 AWG (American Wire Gauge) minimum power cable to the blower motor must meet the
requirements of the applicable electrical or building codes. Ensure that the installation does not reduce
the fire rating of any walls.
●The power cord must be supported at intervals along the length in accordance with local codes. Power
cords must not rest on surfaces or floors that are subject to flooding.
●All material needed for the relocation must be supplied by the installer.
KALLISTA reserves the right to make revisions in the design of products without notice, as specified in the
Price Book.
TOOLSAND MATERIALS
Plus:
• Conventional woodworking tools and
materials or conventional masonry
tools and materials, as appropriate
• Drop cloth
• Construction Adhesive (optional)
• Cement or Mortar (optional)
• 2x4s or 2x6s (optional)
Level Pencil Tape Measure
Pipe WrenchSafety Glasses Silicone Sealant
Additional Tools and Materials for Blower Motor Relocation
●Electrician pliers
●Assorted screwdrivers
●Adjustable wrench
●Drill and bits to install the blower mounting fasteners
●18 AWG non-metallic sheathed cable, two conductors with ground, with support clips, as required
●One 4” (102 mm) x 2” (51 mm) electrical junction box with cover, gasket, and mounting screws
●Three strain reliefs: one must fit the blower motor cover with standard NPT (National Pipe Thread)
threads, the other two are to fit the holes in the new junction box
●Six wire connectors (wire nuts or equivalent)
●1-1/2” PVC or other rigid pipe with: fittings, unions, PVC cement (or equivalent fastening method), and
support clips, as required
●Four fasteners (such as flathead wood screws or concrete anchors) for mounting the blower motor
●Solid copper 8 gauge bonding wire, 36” (914 mm)

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
7 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
ROUGH-IN INFORMATION
32"
(813 mm)
60" (1524 mm)
7-9/16"
(192 mm)
16"
(406 mm)
1"
(25 mm)
22"
(559 mm)
1-11/16"
(43 mm)
5/8" (16 mm)
1-9/16"
(40 mm)
3-7/8"
(98 mm)
REQUIRED ELECTRICAL SERVICE
Dedicated circuit required, protected with Class A
Ground-Fault Circuit-Interrupter (GFCI) or Residual
Current Device (RCD):
Blower motor/control: 220-240 V, 15 A, 50/60 Hz
PRODUCT INFORMATION
Fixture*: Top Area Inside Area Weight
Bathing
Well
54-1/8” (1375 mm) x
25-15/16” (659 mm)
45-13/16” (1164 mm)
x 24-3/4” (629 mm)
75 lbs (34 kg) (00)
100 lbs (45.4 kg) (G5)
Water Depth Capacity
To
Overflow 16-1/4” (413 mm) 75 gal. (283.9 L)
*Approximate Measurements For Comparison Only
Heater Voltage Frequency Amperage
300 W 220-240 50/60 Hz 3A
ROUGHING-IN NOTES
No change in measurements if connected with required
drain illustrated.
Minimum Access Panel:
Blower/Control 34” (864 mm) W x
15” (381 mm) H Required
Faucet Area Recommended
Drop-in cutout 59-1/2″(1511 mm) x 31-1/2″(800 mm)
Floor support under bath must provide for a minimum of
55 lbs/square foot (268 kg/square meter) loading.
Hot water supply should be 70% of capacity or greater.
Installations will vary.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
8 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
1. PREPARE THE SITE
Provide clearance in this
area for the drain assembly.
Provide a 1/16" (2 mm)
gap between the bath
rim and the framing.
Flooring
NOTICE: Adequate floor support must be provided. Consult the “Rough-In Information” section for specific floor
loading requirements.
Install adequate floor support.
NOTICE: To ensure a successful installation, it is critical that bath be installed on a level subfloor.
Verify the subfloor is level. Adjust for level, if necessary.
Framing
CAUTION: Risk of property damage. Do not support the bath by the rim. The bath must be supported by
the support blocks only.
NOTICE: To ensure the bath does not rest on the rim, a 1/16” (2 mm) gap must exist between the framing and
the underside of the rim. When constructing the framing, take into account the gap and the thickness of the
finished wall/deck material.
NOTICE: The bath is for drop-in or raised deck installations only. If a deck-mount faucet will be installed, plan a
space on the deck to accommodate the deck-mount faucet.
Construct the framing according to the “Rough-In Information” section of this publication. Ensure a
1/16” (2 mm) gap will exist between the framing and the underside of the rim.
Provide access panels as required to service the blower motor and control.
Plumbing
NOTICE: For through-the-floor drain installations: A drain hole will need to be cut to accommodate the drain
connections. Position the plumbing according to the “Rough-In Information” section of this publication.
Cap the supplies and check for leaks.
Attach the drain to the bath according to the drain manufacturer’s instructions. Snug connections but do not
tighten. Do not connect the trap at this time.
Plan the drain connection to the trap.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
9 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
PREPARE THE SITE (CONT.)
Remove the drain assembly from the bath and install loosely to the trap.
Final drain connection to the bath will be made after the bath is set into the frame.
Place a clean drop cloth on the bottom of the basin area. This will prevent scratching the surface of the bath
during installation.
2. INSTALL THE TILING-IN BEAD (OPTIONAL)
NOTICE: Tiling-in bead should be installed if the finished wall material will come into contact with any top
surface of the bath. The tiling-in bead prevents water from seeping behind the wall and allows for an alcove
installation of many drop-in baths when a flanged version is not available.
NOTICE: The bottom edge of the tiling-in bead may have to be trimmed. This will ensure a proper fit in the
installation location.
Thoroughly clean the bath rim.
Install the tiling-in bead. Refer to the manufacturer’s instructions for proper installation.
3. PREPARE THE BATH WITHAIRJETS
Bath
Blower Motor
Control
Airjet User Keypad
Level Sensor
ForAll Installations
Position a clean drop cloth or similar material in the bottom of the bath to protect the finish. Ensure that the
airjets are covered. Be careful not to scratch the surface of the bath.
Blower Motor and Check Valve Options
NOTE: This bath with airjets allows the blower motor and check valve to remain on the bath support board
(standard installation) as it is shipped or to be relocated in another location (remote installation). Refer to your
applicable installation, standard or remote, throughout this installation guide.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
10 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
PREPARE THE BATH WITHAIRJETS (CONT.)
Standard Installation Sections
Secure the Bath to the Subfloor - Standard
Install the Plumbing - Standard
Make Power Connections - Standard
Then go to the “Test Run the Bath with Airjets” section.
Remote Location Sections
Disconnect the Blower Motor and Check Valve - Remote
Secure the Bath to the Subfloor - Remote
Mount the Blower Motor and Check Valve - Remote
Connect the Cable at the Blower - Remote
Install the Power Cord at the Control - Remote
Install the Plumbing - Remote
Make Power Connections - Remote
Then go to the “Test Run the Bath with Airjets” section.
4. SECURE THE BATH TO THE SUBFLOOR - STANDARD
Spread a 2" (51 mm) layer of
cement or mortar bed material.
Apply construction
adhesive to the
support blocks.
Clear spaces for
support blocks.
CAUTION: Risk of product damage. Do not support the bath with airjets by the rim.
NOTICE: Do not lift the bath by the air harness or blower motor, or use the piping or blower motor for structural
support of the bath.
NOTICE: The bath must be secured using one of the following two methods: cement or mortar bed, or
construction adhesive.
NOTICE: Ensure the subfloor is level before proceeding. If necessary, use shims to achieve level.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
11 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
SECURE THE BATH TO THE SUBFLOOR - STANDARD (CONT.)
Cement or Mortar Bed Method
NOTICE: Do not use gypsum cement or drywall compound, as these materials will not provide a durable bond.
Only use cement or mortar.
Spread a 2” (51 mm) thick layer of cement or mortar on the subfloor except where the support blocks will
be located.
Clear any cement or mortar away from the support block locations.
Place a plastic liner or similar material over the cement or mortar.
With help, carefully move the bath into the installation area. Make sure the blower motor control and
support blocks do not rest in the bed material.
Verify the support blocks are resting directly on the subfloor. Reposition or shim as needed.
Verify the bath is level across the top. If the bath is not level, shims must be used under the support blocks.
Remove the protective tape from the rim.
Apply a continuous bead of silicone sealant around the entire rim of the bath. Allow the sealant to cure
according to the manufacturer’s instructions.
ConstructionAdhesive Method
Apply a generous amount of high-quality construction adhesive to the bottom of the support blocks.
With help, carefully move the bath into the installation area.
Verify the support blocks are resting directly on the subfloor. Reposition or shim as needed.
Verify the bath is level across the top. If the bath is not level, shims must be used under the support blocks.
Remove the protective tape from the rim.
Apply a continuous bead of silicone sealant around the entire rim of the bath. Allow the sealant to cure
according to the manufacturer’s instructions.
5. INSTALL THE PLUMBING - STANDARD
CAUTION: Risk of property damage. A watertight seal must exist on all bath drain connections. The
watertight seal will prevent property damage.
NOTE: To simplify future maintenance, provide access to all plumbing connections.
Loosely make connections between the bath and overflow and the drain to the bath. Confirm locations and
adjust as needed.
Tighten connections between the bath and overflow, drain to bath, and drain assembly to trap according to
the drain manufacturer’s instructions.
Confirm drain assembly connections are snug according to the drain manufacturer’s instructions.
Install the faucet valving according to the faucet manufacturer’s instructions. Do not install the faucet trim at
this time.
Open the hot and cold water supplies. Check all connections for leaks.
Fill the bath to the overflow. Check the drain connections for leaks. Repair as needed.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
12 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
6. MAKE POWER CONNECTIONS - STANDARD
Neutral
Bus
NL1L2
120 V
120 V
240 V
S/N
*Equipment Ground
*Line Neutral (White)
Breaker Box
Typical Two-Pole
Circuit Breaker
with GFCI
120/240 VAC Source
No Connection
(Load Neutral)
*Connections to be Made
at the Circuit Breaker
*L1
*L2
240 V
Bond in accordance with national and local codes. Open
bonding lugs are located at the top of the junction box.
Field Wire (From Junction
Box To GFCI Breaker)
Typical Wiring Connection for North America
Wire
Connector
Brown (L2)
Blue (L1)
From Control
Ground
(Green with
Yellow Stripe)
Electrician to
provide suitable
strain relief cable.
Control
Power
Supply
Control Power
Junction Box
Blower
Motor Cord
External Power
NOTE: The product model number is printed on a label on the blower motor side of the bath with airjets.
This label also identifies the electrical rating of the product. All baths with airjets come equipped with a wiring
junction box and are designed to operate between 208 VAC and 240 VAC at either 50 Hz or 60 Hz.
WARNING: Risk of electric shock. Make sure the power has been disconnected before performing the
following procedures. Refer to the “Important Information” section.
WARNING: Risk of electric shock. Connect the control to a properly grounded Ground-Fault Circuit-
Interrupter (GFCI) or Residual Current Device (RCD). This will provide additional protection against
line-to-ground shock hazard. A 220-240 V, 15 A, 50/60 Hz dedicated circuit is required.
NOTICE: The load neutral is not used. There should be no connection to the load neutral terminal on the
Ground-Fault Circuit-Interrupter (GFCI). The green wire with the yellow stripe is the equipment ground and
needs to be connected to the neutral bus in the main circuit breaker box.
NOTICE: The bath with airjets control and system have been pre-wired at the factory. A qualified electrician
should make a routine service connection to the junction box.
Connect service to the junction box. The junction box contains blue, brown, and green with a yellow stripe
colored wires. Follow local electrical codes. Bond in accordance with national and local codes.
NOTE:A wiring harness has been pre-wired at the factory, allowing communication between the keypad, all
features, and the control. No additional wiring is required, but ensure that all wires are securely fastened.
NOTE: Your wiring harness includes an antenna for the optional remote control. Do not alter or damage this
antenna during installation.
Proceed to the “Test Run the Bath with Airjets” section.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
13 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
7. DISCONNECT THE BLOWER MOTORAND CHECK VALVE - REMOTE
Control
Baseboard
Mounting
Screws
Retaining
Screw
Blower Motor
Electrical Plug
Screw
Check
Valve
Elbow
NOTICE: This section applies only to installations in which the blower motor and check valve are being
relocated from the shipping position on the support board.
NOTICE: Do not cut the air harness (pipes) for this installation.
NOTICE: The check valve must be relocated with the blower motor.
Removing the Blower Motor
Disconnect the blower motor electrical plug from the control.
Remove any cable ties that support the blower motor cord.
Remove the retaining screw holding the air harness on the blower motor discharge. Do not discard the
screw at this time.
Remove the four blower motor mounting screws from the blower adapter baseboard. Keep these screws.
While restraining the tee with one hand, slide the blower motor away from the tee.
Remove the blower motor from the bath.
Remove the Check Valve
Remove the upper retaining screw at the check valve. Do not discard the screw at this time.
Remove the check valve and attached PVC elbow from the bath.
Prepare the Site for the Blower Motor and Check Valve
NOTE: Refer to the “Before You Begin” section for detailed requirements for the blower motor relocation.
Prepare the site where the blower motor will be installed. The site must be within 15’ (4.6 m) of the bath.
As appropriate, install an access panel to service the blower motor.
As appropriate to the installation, prepare the routing paths for the PVC piping and the new blower motor
power cable. Follow all applicable building, fire, plumbing, and electrical codes.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
14 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
8. SECURE THE BATH TO THE SUBFLOOR - REMOTE
Spread a 2" (51 mm) layer of
cement or mortar bed material.
Apply construction
adhesive to the
support blocks.
Clear spaces for
support blocks.
CAUTION: Risk of product damage. Do not support the bath with airjets by the rim.
NOTICE: Do not lift the bath by the air harness or blower motor, or use the piping or blower motor for structural
support of the bath.
NOTICE: The bath must be secured using one of the following two methods: cement or mortar bed, or
construction adhesive. Choose the installation option that best applies to your particular installation. Follow the
appropriate instructions.
NOTICE: Ensure the subfloor is level before proceeding. If necessary, use shims to achieve level.
Cement or Mortar Bed Method
NOTICE: Do not use gypsum cement or drywall compound, as these materials will not provide a durable bond.
Only use cement or mortar.
Spread a 2” (51 mm) thick layer of cement or mortar on the subfloor except where the support blocks will
be located.
Clear any cement or mortar away from the support block locations.
Place a plastic liner or similar material over the cement or mortar.
With help, carefully move the bath into the installation area. Make sure the blower motor control and
support blocks do not rest in the bed material.
Verify the support blocks are resting directly on the subfloor. Reposition or shim as needed.
Verify the bath is level across the top. If the bath is not level, shims must be used under the support blocks.
Remove the protective tape from the rim.
Apply a continuous bead of silicone sealant around the entire rim of the bath. Allow the sealant to cure
according to the manufacturer’s instructions.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
15 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
SECURE THE BATH TO THE SUBFLOOR - REMOTE (CONT.)
ConstructionAdhesive Method
Apply a generous amount of high-quality construction adhesive to the bottom of the support blocks.
With help, carefully move the bath into the installation area.
Verify the support blocks are resting directly on the subfloor. Reposition or shim as needed.
Verify the bath is level across the top. If the bath is not level, shims must be used under the support blocks.
Remove the protective tape from the rim.
Apply a continuous bead of silicone sealant around the entire rim of the bath. Allow the sealant to cure
according to the manufacturer’s instructions.
9. MOUNT THE BLOWER MOTORAND CHECK VALVE - REMOTE
1-1/2" Rigid Piping
(Not Supplied)
Check
Valve
Screw
Install elbow and check valve to
field pipe, use silicone or equivalent
sealant, and install retaining screw
or equivalent fastener.
Mount the blower motor
using four fasteners.
2" (51 mm) Min Connect blower motor to the check valve, use silicone
or equivalent sealant, and install retaining screw.
NOTE: The blower motor must be mounted horizontally 2” (51 mm) above the floor. Do not mount the blower
motor with the blower motor discharge pointing up.
NOTE: The check valve must be relocated with the blower motor. At the new location, the check valve
must be no lower than 24” (610 mm) below the rim of the bath. The check valve must be within 12” (305 mm) of
the blower motor. The check valve must be oriented vertically with the flow arrow pointing up.
NOTE: Refer to the “Before You Begin” section for other detailed requirements for the blower motor relocation.
At the new blower motor location, install a 2” (51 mm) block (not supplied) for the blower motor support.
Use the blower motor as a template to mark the location of the four mounting bolts or screws.
Drill four 1/8” (3 mm) pilot holes for the blower motor mounting screws.
Install and support PVC or other 1-1/2” rigid piping (not supplied) between the blower motor location and
the bath air harness.
Connect the new piping to the existing air harness without modifying the air harness. Align the new
pipe and secure the connection with PVC cement. Allow the PVC cement to cure according to the
manufacturer’s instructions.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
16 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
MOUNT THE BLOWER MOTORAND CHECK VALVE - REMOTE (CONT.)
Connect the check valve assembly to the new piping. Align the new pipe with the check valve assembly
and drill a hole for the existing mounting screw. Use silicone or equivalent sealant at the connection and
reuse the screw that was removed previously. Allow the sealant to cure according to the manufacturer’s
recommendations.
Apply silicone or equivalent sealant to the lower connection of the check valve assembly.
Align the blower motor with the lower connection of the check valve assembly. Position the motor on the
support block. Reinstall the retaining screw. Allow the sealant to cure according to the manufacturer’s
recommendations.
Fasten the blower motor to the new support block with the retained mounting screws.
10. CONNECT THE CABLEAT THE BLOWER - REMOTE
Cut existing cable
about 4" (102 mm)
from the blower motor.
Access Cover
Strain Relief
Blower Motor
Plug
Remove two screws
to remove the cover.
Route the Power Cable
Route two conductors with ground 18 AWG (American Wire Gauge) or equivalent power cable (not
supplied) between the bath and blower motor locations. Follow all applicable electrical and fire codes.
Ensure that the cable jacket meets applicable code requirements and the cable is properly supported and
protected.
Prepare the Blower for Remote Installation
Loosen the cable strain-relief nut on the blower motor. Push the nut back on the cable to provide clearance
for the cover removal.
Remove the two access cover screws from the back of the blower motor. As you are loosening the screws,
check periodically if the cover can be slid back on the electrical cable.
When the cover is loose, use electrician pliers or equivalent to cut the electrical cable at a point about
4” (102 mm) from where the cable disappears into the blower motor housing.
Pull the free end of the electrical cord through the cover, insert, and strain relief nut.
Discard the existing strain relief nut and insert.
Reconnect the blower motor plug to the control.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
17 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
CONNECT THE CABLEAT THE BLOWER - REMOTE (CONT.)
Install a standard NPT threaded strain relief to the blower motor cover.
Temporarily store the removed components in a safe location.
Connect the New Power Cable at the Blower Motor
At the blower motor 4” (102 mm) pigtail lead, strip back the cable jacket about 3” (76 mm).
Cut the unused brown conductor off at the cable jacket and cap off with a wire nut.
At the newly installed blower motor power cable, strip back the cable jacket about 2” (51 mm).
For installations in the United States, mark white conductors with red or black tape as required by the NEC.
Strip the wire insulation about 3/8” (10 mm) from the blower motor pigtail leads and the power cable leads.
Route the new power cable leads through the blower motor access cover and strain relief.
Using wire nuts or other approved termination devices, terminate the conductors as follows:
●Connect the black pigtail lead to the L1 conductor of the power cable.
●Connect the blue pigtail lead to the L2 conductor of the power cable.
●Connect the green with yellow stripe pigtail lead to the grounding/earthing conductor of the power cable.
With the two screws, reinstall the access cover on the blower motor.
Tighten the strain relief on the power cable at the blower motor.
Remove any dust or debris from the blower motor area.
11. INSTALL THE POWER CORDAT THE CONTROL - REMOTE
Blower
Adapter
Board
Second Junction Box
(Not Provided)
Blower
Motor Pigtail
New Field
Cable To
Blower Motor 50 Hz60 Hz
L1 L1
L2 N
NC NC Brown
GND GND
From Control
Black
Blue
Green w/Yellow Stripe
Wire Connectors
Field Cable to
Blower Motor
Brown
Black
Blue
From Control
Ground
(Green with Yellow Stripe)
Strip back the jackets
about 3" (76 mm) on
the field cable and on
the blower motor power
cord. Cut the brown
wire at the cable jacket.
Install the Junction Box on the Control
Install a second junction box with external bonding lug, two strain reliefs, and a cover (not supplied) on the
blower adapter board on the control.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
18 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
INSTALL THE POWER CORDAT THE CONTROL - REMOTE (CONT.)
Connect a solid copper 8 gauge bonding wire from the bonding lug on the new junction box to the spare
bonding lug on the control. Follow all local electrical codes.
Reconnect the Blower Motor Power Cord
If required, reconnect the blower motor power cord at the control.
Route the power cord through a strain relief on the new junction box. Tighten the strain relief.
At the end of the cut power cord, strip back the cable jacket about 3” (76 mm).
Cut the unused brown conductor off at the cable jacket and cap off with a wire nut.
Strip the wire insulation about 3/8” (10 mm) from the end of the wires.
Terminate the New Power Cable
Route the new power cable through the other strain relief on the new junction box. Tighten the strain relief.
Strip back the cable jacket about 3” (76 mm).
For installations in the United States, mark white conductors with red or black tape as required by the NEC.
Strip the end of the wires about 3/8” (10 mm).
Use approved termination devices to terminate the conductors as follows:
●Connect the black pigtail lead to the L1 conductor of the power cable.
●Connect the blue pigtail lead to the L2 conductor of the power cable.
●Connect the green with yellow stripe pigtail lead to the grounding/earthing conductor of the power cable.
Install the cover on the new junction box.
12. INSTALL THE PLUMBING - REMOTE
CAUTION: Risk of property damage. A watertight seal must exist on all bath drain connections. The
watertight seal will prevent property damage.
NOTE: To simplify future maintenance, provide access to all plumbing connections.
Loosely make connections between the bath and overflow and the drain to the bath. Confirm locations and
adjust as needed.
Tighten connections between the bath and overflow, drain to bath, and drain assembly to trap according to
the drain manufacturer’s instructions.
Confirm drain assembly connections are snug according to the drain manufacturer’s instructions.
Install the faucet valving according to the faucet manufacturer’s instructions. Do not install the faucet trim at
this time.
Open the hot and cold water supplies. Check all connections for leaks.
Fill the bath to the overflow. Check the drain connections for leaks. Repair as needed.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
19 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
13. MAKE POWER CONNECTIONS - REMOTE
Remote
Blower
Power Supply Cable
New Field
Cable To
Blower Motor
Second Junction Box
(Added for Remote Blower)
Blower Motor
Power Cord
Control Power
Junction Box
Control Power
Supply Cord
WARNING: Risk of electric shock. To reduce the risk of electric shock, connect the control to a properly
grounded Ground-Fault Circuit-Interrupter (GFCI) or Residual Current Device (RCD). This will provide
additional protection against line-to-ground shock hazard. A dedicated 220-240 V, 15 A, 50/60 Hz circuit is
required.
WARNING: Risk of electric shock. Make sure the power has been disconnected before performing the
following procedures.
NOTE: The bath with airjets model number is printed on a label near the bath blower motor. This label also
identifies the electrical rating of the bath.
Ensure that the control power supply cord is properly routed to the control power junction box. The control
power supply cord contains a brown wire (Line 1), a blue wire (Line 2), and a green wire with a yellow stripe
(ground or earth).
Install a strain relief (not provided) for the power supply cable to the control power junction box.
Route the power supply cable to the control power junction box.
As required, strip the jacket and wire insulation on both cables in order to make the connections.
For installations in the United States, mark any white conductor in the supply power wiring with red or black
tape as required by the NEC.
Connect service to the control power junction box.
Provide a separate equipment earthing or grounding conductor to the spare earth/ground lug located on
the junction box. This conductor must not be connected to any current-carrying conductor. Follow local
electrical codes.
Bond in accordance with national and local codes.
Clean the area of all dust and debris.
All wiring harnesses have been pre-wired at the factory. Make sure all wires are securely fastened.
NOTE: Your wiring harness includes an antenna for the optional remote control. Do not alter or damage this
antenna during installation.

INSTALLATION INSTRUCTIONS
60" x 32" Acrylic Air Bath
1107630-2-C
20 of 28
Questions? Problems? For additional assistance, please contact KALLISTA’s Customer
Service Department at 1-888-4-KALLISTA (1-888-452-5547) or kallista.com.
14. TEST RUN THE BATH WITH AIRJETS
Rotating Ring Key Pad
Purge Mode
Decrease Flow or Surge
Indicator Bar
Increase Flow or Surge
Surge Mode
Zone 3
Power On/Off
Zone 1
Air Flow Mode
Activates Mode Selected
Zone 2
Rotate outer ring to
access desired mode.
ForAll Installations
NOTE: For additional information on bath with airjets operation, see the “Confirm Proper Operation” section.
Check all electrical connections, and make sure the electrical power to the bath is turned on.
Make sure all PVC piping connections are properly made.
Temporarily remove the protective drop cloth from the bath.
Ensure that the area around the blower motor is clean and free of dust or debris.
Fill the bath to a level at least 4” (102 mm) above the top of the highest airjet.
Press the power button to start the bath.
Operate the bath with air flow in all three zones.
Check all bath PVC connections for leaks.
Stop the blower.
Check for any water leakage at the bath, the bath drain, and the air harness.
Test other features as desired by rotating the outer ring on the keypad and pressing “OK.”
Drain the bath and observe that the purge cycle starts.
Allow the automatic purge cycle to complete.
Replace the protective drop cloth in the bath.
Turn off power to the unit.
Table of contents
Other Kallista Bathtub manuals
Popular Bathtub manuals by other brands

Kohler
Kohler K-1013 Installation and care guide

Jacuzzi
Jacuzzi SHARP 170x70 Installation

Aston Global
Aston Global MT620-R Installation and owner's manual

Universal Tubs
Universal Tubs 2646 Assembly/Installation/Operating Instructions

Kohler
Kohler K-1394 Series installation guide

CAHABA
CAHABA VIOLET CA401004 installation manual

Kohler
Kohler K-513 Homeowner's guide

USSPA
USSPA VIBES Installation, use and maintenance instructions

DURAVIT
DURAVIT D-Code 26020758 Mounting instructions

Kaldewei
Kaldewei DUO POOL 150 Series installation instructions

Kohler
Kohler K-1360-H2 Homeowner's guide

Access
Access 3260 Series INSTALLATION & OPERATIONAL INSTRUCTIONS