Kampmann Katherm NX User manual

459/04/14/1 GB I Sap-Nummer 1146161
Katherm X 3.45
Trench eating with natural convection
Installation instructions
Keep these instructions in a safe place for future use!
Kampmann.de/installation_manuals

2
Table of Contents
1. Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3. Models/Scope of Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Levelling/Water Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5. Thermoelectric Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6. Screed Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7. Dimensions/Height Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8. Water Connection/Pipe Conduits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
9. umber of Height-adjustment Feet
and Raised Floor Mounting Feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
10. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
11. Possible Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
12. Model Overview - Valve Bodies/Return Shut-off Valves . . . . . . . 12
3.45 Katherm X - atural Convection
Table of Contents
Key to symbols:
Caution! Danger!
Non-compliance with this
information may lead to
serious personal injuries
or damage to property.
Danger of
electric shock!
Non-compliance with this
information may lead to
serious personal injuries
or damage to property
from an electric current.
Carefully read these
instructions in full prior
to any assembly and
installation work!
Anyone involved in the
installation, commissioning
and use of this product is
obliged to pass these
instructions to trades
people who are involved
at the same time or at a
later date, as well as to
end users or operators.
Retain these instructions
until the final
decommissioning!
Content or design-
related changes may be
made without any prior
notice!

3
1. Intended Use
Kampmann Katherm NX are built in line with the state of the art and
recognised safety regulations. Nevertheless their use may result in danger
to people or damage to the unit or other material property if they are not
properly installed or properly used.
Katherm NX should only be used indoors (e.g. living space, offices, showrooms
etc.) They are not suitable for use in humid environments, such as swimming
pools or outdoors. The products should be protected from any moisture
during installation. Check the application with the manufacturer in case of any
doubt. Any use other than the use specified above is deemed not to be
correct and proper. The operator of the unit is solely responsible for any
damage resulting from such use. Correct and proper use is deemed to include
observing the installation information described in these instructions.
The installation of this product requires specialist knowledge of heating,
cooling, ventilation and electrical engineering. This knowledge, generally
learned in vocational training in the fields mentioned in section 2, is not
described separately. Errors with the connection or modifications may lead
to the unit being damaged! The manufacturer shall not be liable for any
damage caused by an incorrect connection and/or improper handling.
Katherm X
1
Linear grille (alternative: roll-up grille)
2
PowerKon heat exchanger
3
Floor duct
4
Flow, 1/2"
5
Return, 1/2"
6
eight-adjustment feet with sound insulation
7
Raised floor mounting feet with sound insulation
8
Struts
9
Pipe conduit for water connection
bl
Cable conduit
bm
Connection cover
Example shown: Katherm NX 225
2
3
1
4
7
5
6
8
9
bm
bl
Katherm X - atural Convection 3.45
Intended Use
Caution: Do not remove struts

4
2. Safety Information
Installation, assembly and maintenance work on electrical units should
only be performed by a qualified electrician in compliance with the VDE
guidelines. Wiring should comply with the applicable VDE regulations and
provisions laid down by the regional electricity providers. Non-compliance
with the regulations and operating instructions may result in the units
malfunctioning with consequential damage and danger to people. The
units may be incorrectly wired by the wires being swapped – danger
of fatal injury! Disconnect all parts of the system from the mains power
supply and prevent them from being reconnected before starting any
connection and maintenance work! The unit should only be connected to
fixed cabling.
Please read these instructions in full to guarantee a correct installation.
Please note the following safety-relevant information:
• Disconnect all parts of the system that are being worked on.
• Ensure that the system cannot be accidentally re-connected!
• Caution! Pipes, casings and fittings may become very hot depending on
the operating mode!
• Qualified personnel must have undergone training to provide them with
adequate knowledge of the following:
• Safety and accident prevention regulations
• Guidelines and recognised technical regulations, i.e. VDE (Association of
German Electricians) regulations
• DIN and EN standards
• Accident prevention regulations VBG, VBG4, VBG9a
• DIN VDE 0100, DIN VDE 0105
• EN 60730 (Part 1)
• Technical wiring regulations issued by the regional electricity providers
Modifications to the unit
Do not undertake any modifications, refurbishments or upgrades on the
Katherm NX unit without discussing these with the manufacturer as these
may impair the safety and operation of the unit. Do not carry out any
action on the unit that is not described in these instructions. On-site
systems and cabling must be suitable for connection to the intended
system!
The floor duct has openings provided for the installation of
a potential compensation line.
3. Models/Scope of Delivery
Floor ducts are delivered as standard with the following (see Fig. 2):
leight-adjustment feet, room-side, 1Rubber underlays for sound
absorption 2; screws and rawlplugs, provided on-site;
lraised floor mounting feet with sound absorption 3
3.45 Katherm X - atural Convection
Safety Information

5
4. Levelling/Water Connection
lRemove the outer stretch wrapping and cardboard box.
Caution: Do not remove the struts during installation and operation.
lPlace the Katherm NX with the PowerKon heat exchanger near the
window.
Caution: The height-adjustment feet are already fitted to the floor duct.
owever, these were attached to the foot underneath the duct
for transportation purposes. Loosen the outer fastening nut on
the height-adjustment feet and turn the raised floor mounting
feet 180° so that is pointing outwards (see Fig. 1) in order to
install and adjust the height of the duct.
lThen set up the floor duct and adjust the height of the height-
adjustment feet 1and adjusting screws on the raised floor mounting
feet with sound absorption 3.
lFix the height-adjustment feet, room-side 1with rubber underlays for
sound absorption 2, with screws and rawlplugs provided on-site.
lUse the pipe opening cut out on the room-side for the water-side
connection. Remove the pipe conduit that has been cut out. Seal
the thermostatic valve and return shut-off valve with appropriate
sealing compound and screw the valves to the fan connections on the
convector.
lThen fit the flow and return pipes.
lRun a pressure test.
lAttach these installation instructions to the floor duct so that they are
clearly visible to any trades people at a later date.
lCover the grille and floor duct with a transparent protective cover to
protect them from dirt or cement.
5. Thermoelectric Actuator
Lay an empty conduit Ø 23 mm for the connection cable from the
thermoelectric actuator to the floor duct and flush-mounted box
(provided on-site) to connect the thermoelectric actuator.
Window-side
Example shown: Katherm NX 225
Room-side
1
2
3
Fig. 1: Turning the height-
adjustment feet
Fig. 2: eight adjustment on the
raised floor mounting feet
Katherm X - atural Convection 3.45
Levelling/Water Connection
1
2
3

6
6. Screed Work
Check the following before starting the screed work:
lThe water is connected properly,
lThe electricity is connected properly,
lThe floor duct is the correct height and distance from the window,
lThe grille is covered (Caution! Cement destroys the surface of the grille!),
lThe sound insulation (not with raised floors) is installed beneath the floor
duct,
lThere are no sound bridges to the bare concrete, particularly around the
height-adjustment feet.
lAll openings and cut-outs in the floor duct heating are sealed from the
screed using appropriate material.
lThe duct openings and cut-outs should be additionally sealed when using
floating screed or other viscous floor coverings.
Caution: The floor duct must not be pressed together by the screed or floor.
Provide expansion joints if needed.
7. Dimensions/Height Adjustment
Separately packaged roll-up grilles, e.g.
when using installation covers to protect
from dirt, are pre-rolled in the factory.
If the steel spiral springs are stretched,
this may result in the grille appearing
over-long. Unroll and lay out the grille for
a few hours to return it to its original
length. The frame is easier to fit if the
roll-up grille is inserted with an up and
down movement as per the figure
above.
3.45 Katherm X - atural Convection
Screed Work
All dimensions in mm
Front view
Duct height
eight-adjustment foot
Mounting foot
Rubber underlay for
sound absorption
Section Duct width
Window-side
Max. A
Room-side
Larghezza/altezza canale
Raised floor mounting feet
Adjusting screws L = 60 mm, Ø = 8mm
Sound absorption
Duct width /height max. A
B C D
130 / 92 126 50 50 155
130 / 120 154 50 50 155
175 / 92 126 70 50 200
175 / 120 154 70 50 200
175 / 150 184 70 100 200
175 / 200 234 70 100 200
225 / 92 126 100 50 250
225 / 120 154 100 50 250
225 / 150 184 100 100 250
225 / 200 234 100 100 250

7
8. Water Connection • Pipe Conduits
Katherm X 130 (only opposite-end connection)
Duct height 92/120 mm
1
Flow
2
Return
3
Valve body, axial 1/2”,
type 194000246909 or
type 194000346911 (presettable)
4
Thermoelectric actuator,
type 194000146905
5
Return shut-off valve,
straight, type 194000145952
6
Unit shown with roll-up grille
7
Pipe conduits, cut-out
8
Cable conduits
Katherm X - atural Convection 3.45
Water Connection • Pipe Conduits
43
1
6
8
7
5
2
6
8
7
Connection side, left
Connection side, right
All dimensions in mm
Katherm X 130
A B C D
Duct height 92 mm
63 43 92 42
Duct height 120 mm
91 71 120 70

8
3.45 Katherm X - atural Convection
Water Connection • Pipe Conduits
Katherm X 175, single-end connection
Duct height 92/120 mm
1
Flow
2
Return
3
Valve body, axial, 1/2”,
type 194000246909 or
type 194000346911 (presettable)
4
Thermoelectric actuator,
type 194000146905
5
Return shut-off valve,
straight, type 194000145952
6
Unit shown with roll-up grille
7
Pipe conduits, cut-out
8
Cable conduits
Duct height 150/200 mm
1
Flow
2
Return
3
Valve body, straight 1/2”,
type 194000146909 or
type 194000346909 (presettable)
4
Thermoelectric actuator,
type 194000146905
5
Return shut-off valve,
straight, type 194000145952
6
Unit shown with roll-up grille
7
Pipe conduits, cut-out
8
Cable conduits
43
1
8
7
4
5
3
12
6
8
7
2
5
6
All dimensions in mm
All dimensions in mm
Katherm X 175 A B C D
Duct height 92 mm
63 43 92 42
Duct height 120 mm
91 71 120 70
Katherm X 175 A B C D
Duct height 150 mm
57 16 150 50
Duct height 200 mm
107 66 200 100

9
Katherm X - atural Convection 3.45
Water Connection • Pipe Conduits
Katherm X 225, single-end connection
Duct height 92/120 mm
1
Flow
2
Return
3
Valve body, straight 1/2”,
type 194000146909 or
type 194000346909 (presettable)
4
Thermoelectric actuator,
type 194000146905
5
Return shut-off valve,
straight, type 194000145952
6
Unit shown with roll-up grille
7
Pipe conduits, cut-out
8
Cable conduits
Duct height 150/200 mm
1
Flow
2
Return
3
Valve body, straight 1/2”,
type 194000146909 or
type 194000346909 (presettable)
4
Thermoelectric actuator,
type 194000146905
5
Return shut-off valve,
straight, type 194000145952
6
Unit shown with roll-up grille
7
Pipe conduits, cut-out
8
Cable conduits
4
3
1
6
8
7
4
5
3
12
6
8
7
2
5
All dimensions in mm
All dimensions in mm
Katherm X 225 A B C D
Duct height 92 mm
63 43 92 42
Duct height 120 mm
91 71 120 70
Katherm X 225 A B C D
Duct height 150 mm
57 16 150 50
Duct height 200 mm
107 66 200 100

10
3.45 Katherm X - atural Convection
umber of height-adjustment feet and raised floor mounting feet
9. umber of height-adjustment feet and
raised floor mounting feet
10. Maintenance
Information
Maintenance on Katherm NX floor ducts should only be carried out
by qualified personnel trained in compliance with the installation and
operating instructions as well as any regulations currently in force. Regular
maintenance and inspections are required in order to permanently
guarantee the function and performance of the Katherm NX.
Heat exchanger
lInspect the integral heat exchanger every six months for dirt and
possible damage. A visual inspection is sufficient here.
lCarefully vacuum the heat exchanger if dirty.
Valves
lInspect the valves as well every 12 months and check the leak-tightness
(visual inspection)!
Duct length [mm] umber of height-adjustment feet umber of raised floor mounting feet
900 2 2
1100 2 3
1300 2 3
1500 2 3
1700 2 3
1900 2 4
2100 2 4
2300 2 4
2500 2 4
2700 2 4
2900 2 5
3100 2 5

11
Katherm X - atural Convection 3.45
Possible Control Options
Room thermostat, surface-
mounted, type 194000146904
Thermoelectric
actuator
Type 194000146905
Valve body 1/2 ",
type 194000246909 or
type 194000346911
Valve body 1/2"
Type 194000146909 or
type 194000346909
Valve body 1/2"
Type 194000146909 or
type 194000346909
Room thermostat, flush-
mounted, type 194000146927
Connection cable
Thermoelectric actuator
Approx. 1,900 mm (should be laid loosely
in the empty duct)
Clock thermostat, surface-
mounted, type 194000146910
Connection cable
Thermoelectric actuator
Approx. 1,900 mm (should be laid loosely
in the empty duct)
Example shown:
Katherm NX 225
with linear grille
Example shown:
Katherm NX 225
with linear grille
Mains
power supply
3 x 1,5
Mains
power supply
3 x 1,5
Mains
power supply
3 x 1,5
Mains
power supply
3 x 1,5
3 x 1,5 3 x 1,5 3 x 1,5 3 x 1,5
Clock thermostat, flush-
mounted, type 194000146933
3 x 1,5
to further thermoelectric
actuators type 194000146905
(total max. 10)
The number of connecting wires required with cable diameters (e.g 3 x 1.5) incl. fuses is given on the individual control units.
Flush-mounted
box (provided
on-site)
Valve body 1/2 ",
type 194000246909 or
type 194000346911
11. Possible Control Options
Note: Always place 194000 in front of the respective type number. e.g. 146904 →194000146904
Sample controls
An option for electric controls is the combination of a room thermostat and the
corresponding number of actuators and valves. The required room temperature is set
on the room thermostat. If the room temperature falls below this set value, the
thermoelectric actuator opens the water-side valve.
Thermoelectric
actuator
Type 194000146905

12
3.45 Katherm X - atural Convection
Model Overview - Valve Bodies/Return Shut-off Valves
12. Model Overview - Valve Bodies/Return Shut-off Valves
Duct height [mm]
92
120
150
200
//
Axial,
type 194000246909
or
type 194000346911
(presettable)
Return shut-off
valve, straight,
type 194000145952
Axial,
type 194000246909
or
type 194000346911
(presettable)
Valve, straight,
type 194000146909
or
type 194000346909
(presettable)
Return shut-off
valve, straight,
type 194000145952
Return shut-off
valve, straight,
type 194000145952
Valve, straight,
type 194000146909
or
type 194000346909
(presettable)
Valve, straight,
type 194000146909
or
type 194000346909
(presettable)
Return shut-off
valve, straight,
type 194000145952
Return shut-off
valve, straight,
type 194000145952
Flow, 1/2”
connection
Return, 1/2”
connection
Flow, 1/2”
connection
Return, 1/2”
connection
Flow, 1/2”
connection
Return, 1/2”
connection
NX 130
Katherm NX
NX 175 NX 225

13
Katherm X - atural Convection 3.45
otes

14
3.45 Katherm X - atural Convection
otes

15
Katherm X - atural Convection 3.45
otes

Kampmann.de
Kampmann GmbH
Friedrich-Ebert-Str. 128 - 130
49811 Lingen (Ems)
Germany
T+49 591 7108-0
F+49 591 7108-300
Einfo@kampmann.de
Kampmann UK Ltd.
Dial ouse, Govett Avenue
Shepperton, Middlesex, TW17 8AG
Great Britain
T+44 (0)1932 228592
F+44 (0)1932 228949
Einfo@kampmann-uk.co.uk
Table of contents
Other Kampmann Heating System manuals
Popular Heating System manuals by other brands

Zehnder Rittling
Zehnder Rittling ComfoConnect KNX C manual

Viessmann
Viessmann Vitodens 100-W operating instructions

Payne
Payne PY1P User's information manual

Helios
Helios KWL EC 270 W L Installation and operating instructions

Viessmann
Viessmann VITOVENT 300 operating instructions

Clean Energy
Clean Energy CE-140 owner's manual