Kamstrup ULTRAFLOW 54 DN150-250 Parts list manual

Technical description
ULTRAFLOW
®
54 DN150-250
Kamstrup A/S
Industrivej 28, Stilling
DK-866 Skanderborg
TEL: +45 89 93 1
FAX: +45 89 93 1 1
www.kamstrup.com

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
2

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 3
Contents
1
Gener l description ........................................................................................................ 5
2
D t ............................................................................................................................... 6
2.1
Electrical data ........................................................................................................................................ 6
2.2
Mechanical data .................................................................................................................................... 6
2.3
Flow data ............................................................................................................................................... 7
2.4
Material ................................................................................................................................................. 7
3
Type overview ................................................................................................................. 8
4
Ordering det ils.............................................................................................................. 9
4.1
Type numbers of ULTRAFLOW
®
54 for MULTICAL
®
.................................................................................... 9
4.2
Type numbers of separate ULTRAFLOW
®
54 ............................................................................................ 9
4.2.1
Ordering details of separate ULTRAFLOW
®
54 .................................................................................. 1
4.2.2
Type numbers of output and supply modules .................................................................................. 1
4.2.3
Programming variants of pulse figures and pulse durations ............................................................. 11
4.3
Accessories ......................................................................................................................................... 12
4.3.1
Cables............................................................................................................................................ 13
5
Dimensioned sketches .................................................................................................. 14
6
Pressure loss ................................................................................................................ 16
7
Inst ll tion ................................................................................................................... 17
7.1
Installation angle of ULTRAFLOW
®
54 ................................................................................................... 18
7.1.1
Mounting ULTRAFLOW
®
54 in lifting ring .......................................................................................... 18
7.2
Mounting of ULTRAFLOW
®
54 electronics box ....................................................................................... 19
7.2.1
Orientation of flow sensor electronics box ...................................................................................... 2
7.3
Straight inlet ........................................................................................................................................ 21
7.4
Operating pressure .............................................................................................................................. 21
7.5
Connection to calculator ...................................................................................................................... 22
7.5.1
ULTRAFLOW
®
54 and MULTICAL
®
, galvanically coupled ................................................................... 22
7.5.2
ULTRAFLOW
®
54 and MULTICAL
®
, galvanically separated ................................................................ 22
7.6
Connection of power supply ................................................................................................................. 24
7.6.1
Battery supply ................................................................................................................................ 24
7.6.2
Mains supply modules ................................................................................................................... 24
7.6.3
Mains supply cable ........................................................................................................................ 25
7.6.4
Danish regulations for the connection of mains operated meters ..................................................... 25
7.6.5
Cable connections .......................................................................................................................... 26
7.6.6
Change of supply unit ..................................................................................................................... 26
7.7
Example of connection of ULTRAFLOW
®
54 for MULTICAL
®
.................................................................... 27
7.8
Calculator with two flow sensors .......................................................................................................... 28
7.9
Testing the function ............................................................................................................................. 28
8
Function l description .................................................................................................. 29
8.1
Ultrasound combined with piezo ceramics ........................................................................................... 29
8.2
Principles ............................................................................................................................................ 29
8.3
Transient time method ......................................................................................................................... 29
8.4
Signal paths ........................................................................................................................................ 31
8.5
Measuring sequences .......................................................................................................................... 31
8.6
Function .............................................................................................................................................. 32
8.7
Guidelines for dimensioning ULTRAFLOW
®
........................................................................................... 33
8.8
Pulse output ........................................................................................................................................ 34

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
4
8.8.1
Galvanically coupled ...................................................................................................................... 34
8.8.2
Galvanically separated................................................................................................................... 35
8.9
Pulse emission ................................................................................................................................... 37
8.1
Accuracy ........................................................................................................................................ 37
8.11
Power consumption ....................................................................................................................... 38
8.12
Interface plug/serial data............................................................................................................... 38
8.13
Test mode ..................................................................................................................................... 39
8.14
Externally controlled start/stop ...................................................................................................... 39
8.15
Calibration procedure using serial data and externally controlled start/stop .................................. 4
9
C libr ting ULTRAFLOW
®
.............................................................................................. 41
9.1
Test instructions for ULTRAFLOW
54, DN15 -25 ............................................................................... 41
9.1.1
Installation angle for ULTRAFLOW
®
................................................................................................. 41
9.1.2
Technical data ............................................................................................................................... 41
9.1.3
Connection .................................................................................................................................... 42
9.2
Sealing ............................................................................................................................................... 43
9.3
Optimization in connection with calibration......................................................................................... 44
9.4
PULSE TESTER ..................................................................................................................................... 45
9.4.1
Technical data of PULSE TESTER ..................................................................................................... 45
9.4.2
Hold-function ................................................................................................................................ 47
9.4.3
Push-button functions ................................................................................................................... 47
9.4.4
Use of PULSE TESTER ..................................................................................................................... 47
9.4.5
Spare parts .................................................................................................................................... 48
9.4.6
Battery replacement ...................................................................................................................... 48
10
METERTOOL ................................................................................................................. 49
1 .1
Introduction .................................................................................................................................. 49
1 .2
System Requirements for PC .......................................................................................................... 49
1 .2.1
Interface .................................................................................................................................... 49
1 .2.2
Installation ................................................................................................................................ 51
1 .3
METERTOOL for ULTRAFLOW
®
X4 .................................................................................................... 52
1 .3.1
Files .......................................................................................................................................... 52
1 .3.2
Utilities ..................................................................................................................................... 52
1 .3.3
Windows ................................................................................................................................... 52
1 .3.4
Help .......................................................................................................................................... 53
1 .4
Application .................................................................................................................................... 53
1 .4.1
COM-port selection .................................................................................................................... 53
1 .4.2
Flow meter adjustment .............................................................................................................. 54
1 .4.3
Programming of standard flow curve .......................................................................................... 54
1 .4.4
Pulse Divider ............................................................................................................................. 55
1 .4.5
Meter type ................................................................................................................................. 57
1 .4.6
Help .......................................................................................................................................... 57
1 .5
Update .......................................................................................................................................... 58
11
Troubleshooting ........................................................................................................... 59
12
Approv ls..................................................................................................................... 60
12.1
Measuring Instruments Directive .................................................................................................... 6
12.2
CE-Marking .................................................................................................................................... 6
12.3
Declaration of conformity ............................................................................................................... 61
13
Dispos l ....................................................................................................................... 62
14
Documents ................................................................................................................... 63

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 5
1Gener l description
ULTRAFLOW
®
54 DN15 -25 is a static flow sensor based on the ultrasonic measuring principle. It is primarily
used as a volume flow sensor for energy meters such as MULTICAL
®
. ULTRAFLOW
®
54 DN15 -25 has been
designed for use in heating and cooling installations where water is the heat-bearing medium.
ULTRAFLOW
®
54 DN15 -25 employs ultrasonic measuring techniques and microprocessor technology. All
calculating and flow measuring circuits are collected on one single board, thus providing a compact and rational
design and, in addition, exceptionally high measuring accuracy and reliability is obtained.
The volume is measured using bidirectional ultrasonic technique based on the transit time method, with proven
long-term stability and accuracy. Four ultrasonic transducers are used to send sound signals both against and
with the flow. The ultrasonic signal travelling with the flow reaches the opposite transducer first. The time
difference between the two signals can be converted into flow velocity and thereby also volume.
A three-wire signal cable is used to connect ULTRAFLOW
®
54 DN15 -25 to the Kamstrup MULTICAL
®
calculator.
The cable supplies the flow sensor and also transfers the signal from sensor to calculator. A signal corresponding
to the flow – or more correctly, a number of pulses proportional to the water volume flowing through – is
transmitted.
ULTRAFLOW
®
54 DN15 -25 is available with internal supply, e.g. if the distance between MULTICAL
®
and
ULTRAFLOW
®
is 1 meters or more. If ULTRAFLOW
®
54 DN15 -25 is used for other equipment (e.g. other brands
of calculators), the sensor must be fitted with a galvanically separated output module and a supply of its own.

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
6
2D t
ULTRAFLOW
®
54 DN15 -25
2.1 Electric l d t
Supply voltage 3.6 V ± .1 V
Supply, galvanically coupled output
module (Y=1)
Powered by MULTICAL
®
Supply, galvanically separated output
module (Y=2)
1)
Mains supply 23 VAC +15/-3 %, 5 Hz
24 VAC ±5 %, 5 Hz
Power consumption < 1 W
Backup Integral SuperCap eliminates interruptions due to short-term power failures
Supply, galvanically separated output
module (Y=3)
Battery 3.65 VDC, D-cell lithium
Replacement interval 6-years @ t
BAT
< 3 °C
Mains supply 23 VAC +15/-3 %, 5 Hz
24 VAC ±5 %, 5 Hz
Power consumption < 1 W
Backup Integral SuperCap eliminates interruptions due to short-term power failures
Signal cable length, from flow sensor
electronics box with galvanically
coupled output module (Y=1)
Max. 1 m (powered by calculator)
Signal cable length, from flow sensor
electronics box with galvanically
separated output module (Y=2 and 3)
Depending on calculator (use of own supply in ULTRAFLOW
®
).
See paragraph 7.5.2 for applications with MULTICAL
®
EMC data Fulfil DS/EN 1434:2 7 class C, MID E1 and E2
2.2 Mech nic l d t
Metrological class 2 or 3
Environmental class Fulfils DS/EN 1434 class C
Ambient temperature 5…55°C (indoors)
Protection class IP67 When installed properly. See paragraph 7.2
Humidity 93% RH non-condensing
Mechanical environment MID M1 and M2
Temperature of medium 2…15 °C (Heat-, heat/cooling meters)
2…5 °C (Cooling meters)
At medium temperatures above 9 °C (T
med
> 9 °C)
or medium temperature more than 5°C below
ambient temperature (T
med
< T
amb
- 5°C), the
electronics box must be wall mounted or
mounted via the enclosed distance piece.
Storage temp. empty
sensor
-25…7 °C, 6 °C if battery mounted/enclosed
Pressure stage PN25
1)
It is possible to use battery supply in combination with output module (Y=2), e.g. for temporary supply of flow sensors installed at
construction sites.

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 7
2.3 Flow d t
Nom. flow q
p
Nom. diameter Pulse figures
1)
Dynamic range Flow @ 125 Hz
2)
∆
∆∆
∆p @ q
p
Min. Cutoff
[m³/h] [mm] [imp/l]
q
i
:q
p
q
s
:q
p[m³/h] [bar] [l/h]
150 DN150 1 1:100 2:1 450 0.02 300
250 DN150 0.6 1:100 2:1 750 0.055 500
400 DN150 0.4 1:100 2:1 1125 0.04 800
400 DN200 0.4 1:100 2:1 1125 0.01 800
400 DN250 0.4 1:100 2:1 1125 0.01 800
600 DN200 0.25 1:100 2:1 1800 0.022 1200
600 DN250 0.25 1:100 2:1 1800 0.022 1200
1000 DN250 0.15 1:100 2:1 3000 0.015 2000
1)
Standard pulse figure. Appears from ULTRAFLOW
®
label. For other pulse figures see paragraph 4.
2)
Saturation flow. Max. pulse frequency, 128 Hz, is maintained at higher flow rates.
Table 1
2.4 M teri l
Wetted p rts
Housing Stainless steel, W.no. 1.43 7
Transducer holder Stainless steel, W.no. 1.43 8
Transducer Titanium
Gaskets Fibre
Electronics box
Base, cover Thermoplastic, PC 1 % GF
Fitting hardware, Thermoplastic, PPS 4 % GF
distance piece for
electronics box
Sign l c ble (optional for separate ULTRAFLOW
®
54)
Silicone cable (3x .5 mm
2
)
Power supply c ble 24/230 VAC (optional)
Cable with PVC-mantle (2x .75 mm²)

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
8
3Type overview
Nom. flow q
p
[m³/h]
150 DN150x500 mm
250 DN150x500 mm
400 DN150x500 mm DN200x500 mm DN250x600 mm
600 DN200x500 mm DN250x600 mm
1000
DN250x600 mm
Overall lengths
Flange EN 1 92, PN25
Table 2

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 9
4Ordering det ils
4.1 Type numbers of ULTRAFLOW
®
54 for MULTICAL
®
The table below shows a list of type numbers for ULTRAFLOW
®
54 ordered with MULTICAL
®
q
p
q
i
q
s
Connection PN Length Pulse figure Material
[m³/h]
[m³/h]
[m³/h]
[mm] [bar]
[mm]
[imp/l]
flow sensor case
65-5- FCCN -XXX 150 1.5 300 DN150 25 500 1 447 (489) Stainless steel
65-5- FDCN -XXX 250 2.5 500 DN150 25 500 0.6 481 Stainless steel
65-5- FECN -XXX 400 4 800 DN150 25 500 0.4 491 Stainless steel
65-5- FECP -XXX 400 4 800 DN200 25 500 0.4 491 Stainless steel
65-5- FECR -XXX 400 4 800 DN250 25 600 0.4 491 Stainless steel
65-5- FFCP -XXX *) 600 6 1200 DN200 25 500 0.25 492 Stainless steel
65-5- FFCR -XXX *) 600 6 1200 DN250 25 600 0.25 492 Stainless steel
65-5-
FGCR
-XXX *)
1000
10
2000
DN250
25
600
0.15
493
Stainless steel
XXX, code re marking and final assembly.
*) Cannot be delivered with MID approval
Type number CCC
Table 3
4.2 Type numbers of sep r te ULTRAFLOW
®
54
q
p
q
i
q
s
Connection PN Length Material
[m³/h]
[m³/h]
[m³/h]
[mm] [bar]
[mm]
flow sensor case
65-5- FCCN -YZ -XXX 150 1.5 300 DN150 25 500 Stainless steel
65-5- FDCN -YZ -XXX 250 2.5 500 DN150 25 500 Stainless steel
65-5- FECN -YZ -XXX 400 4 800 DN150 25 500 Stainless steel
65-5- FECP -YZ -XXX 400 4 800 DN200 25 500 Stainless steel
65-5- FECR -YZ -XXX 400 4 800 DN250 25 600 Stainless steel
65-5- FFCP -YZ -XXX *) 600 6 1200 DN200 25 500 Stainless steel
65-5- FFCR -YZ -XXX *) 600 6 1200 DN250 25 600 Stainless steel
65-5-
FGCR
-YZ
-XXX *)
1000
10
2000
DN250
25
600
Stainless steel
XXX, code re marking and final assembly.
*) Cannot be delivered with MID approval
Type number
Table 4

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
1
4.2.1 Ordering det ils of sep r te ULTRAFLOW
®
54
Type number composition of separate ULTRAFLOW
®
54
ULTRAFLOW
®
54. Type no: 65-5 - XX XX - Y Z - XXX
Dynamic range and flow
Connection and overall length
Output module
Supply module
Final assembly and marking
In addition to the basic variants listed above in
Table 3
, you must select output module (Y), supply module (Z) as
well as pulse figure programming (CC) and pulse duration (E).
The variant with galvanically coupled output module (Y=1) is solely for use together with MULTICAL
®
.
The variant with galvanically separated output module (Y=2 or 3) is used in the following situations:
1)
More than 1 m cable length between MULTICAL
®
and ULTRAFLOW
®
is required.
2)
As flow sensor no. 2 in connection with MULTICAL
®
. If two flow sensors are used together with
MULTICAL
®
, one must include a galvanically separated output module (Y=2 or 3). For further details see
paragraph
7.8 Calculator with two flow sensors
.
3)
Together with other equipment/foreign calculators.
Ple se note:
Flow info cannot be read if output module with galvanic separation is used.
4.2.2 Type numbers of output nd supply modules
Type number overview of output modules (Y) and supply modules (Z) for separate ULTRAFLOW
®
54.
Y Output module Corresponding supply module
1 Galvanically coupled module
0 (powered by MULTICAL
®
)
2 Galvanically separated module 0, 7, 8
3 Galvanically separated module 0, 2, 7, 8
Z Supply module Corresponding output module
0 No supply 1, 2, 3
2 Battery, D-cell 3
7 230 VAC supply module 2, 3
8 24 VAC supply module 2, 3
Table 5. Output modules Y) and supply modules Z).

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 11
4.2.3 Progr mming v ri nts of pulse figures nd pulse dur tions
Overview of programming variants as to pulse figures (CC) and pulse durations
(
E) for separate ULTRAFLOW
®
Table 6. Pulse figures CC) and pulse durations E).
q
p
[m³/h] [imp/l] [l/pulse] CC [ms] (E=1) [ms] (E=4) [ms] (E=5) [ms] (E=6)
150 1 33 3.9 - - - Default
150 10 34 - 20 - -
150 25 64 - 20 - -
150 100 35 - 20 50 100
150 250 65 - 20 50 100
150 1000 36 - 20 50 100
150 2500 66 - 20 50 100
250 0.6 43 3.9 - - - Default
250 10 34 - 20 - -
250 25 64 - 20 - -
250 100 35 - 20 50 100
250 250 65 - 20 50 100
250 1000 36 - 20 50 100
250 2500 66 - 20 50 100
400 0.4 63 3.9 - - - Default
400 100 35 - 20 50 -
400 250 65 - 20 50 100
400 1000 36 - 20 50 100
400 2500 66 - 20 50 100
600 0.25 14 3.9 - - - Default
600 100 35 - 20 50 -
600 250 65 - 20 50 -
600 1000 36 - 20 50 100
600 2500 66 - 20 50 100
1000 0.15 54 3.9 - - - Default
1000 (0.25) 4 14 3.9 - - - *)
1000 100 35 - 20 50 -
1000 250 65 - 20 50 -
1000 1000 36 - 20 50 100
1000 2500 66 - 20 50 100
*) Spare part for ULTRAFLOW
®
type 65-S/R/T. Configured 65-5-FGCR. No flow info.
Pulse figure Pulse duration

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
12
4.3 Accessories
Please note that not all article numbers mentioned in the table can be directly ordered, some must be ordered via
our service department.
1)
Obligatory when changing from mains supply module to battery supply.
2)
Including 5 -29 .
Article number Description Note
(when ordering ULTRAFLOW
®
)
65- - -2 D-cell lithium battery with two-pole connector
3 26-477
1)
Fitting for D-cell battery
Enclosed if battery
supply or “No supply” is
selected
165 -157
1)
Plug for cable connection
Enclosed if battery
supply or “No supply” is
selected
Article number
Description
Note
(when ordering ULTRAFLOW
®
)
65- - -7
2
)
23 VAC supply module
65- - -8
2
)
24 VAC supply module
5 -29 Cable between supply module and output module Enclosed if supply
module is selected
5 -286 24/23 V AC power cable Optional
Article number
Description
Note
(when ordering ULTRAFLOW
®
)
555 -1 61 Output module (Y=1), galvanically coupled
555 -1 62 Output module (Y=2), galvanically separated
555 -1219 Output module (Y=3), galvanically separated,
“Low power”

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 13
4.3.1 C bles
ULTRAFLOW
®
54 DN15 -25 , when ordered with MULTICAL
®
, is delivered with 2.5 m signal cable, optionally 5 or
1 m. The cable is mounted in the ULTRAFLOW
®
54 electronics box and in MULTICAL
®
6xx. When ULTRAFLOW
®
54
is ordered with MULTICAL
®
8xx, the calculator is delivered separately. Hence the cable is only mounted in the
ULTRAFLOW
®
54 electronics box.
ULTRAFLOW
®
54 DN15 -25 , when ordered as a separate flow sensor, is optionally available with signal cable in
lengths of 2.5, 5 or 1 m. The cable is mounted in the ULTRAFLOW
®
54 electronics box.
If 24/23 VAC supply module is selected, the sensor is optionally available with power supply cable. The cable is
mounted in the sensor's electronics box from the factory.
Article number
Description
Note
(when ordering ULTRAFLOW
®
)
5 -333 2.5 m silicone cable (3-wire)
Default for ULTRAFLOW
®
ordered with MULTICAL
®
Optional for separate
ULTRAFLOW
®
5 -259 5 m silicone cable (3-wire) Optional
5 -27 1 m silicone cable (3-wire) Optional
3 26-2 7 Mounting fitting for electronics box Enclosed (mounted)
6561-332 Short distance piece (article)
3 26-5 7 Long distance piece Enclosed
1 51- 6 Collar band for short and long distance piece Enclosed
115 -14 Gasket, DN15 PN25 (1 pc) Enclosed (2 pcs.)
115 -139 Gasket, DN2 PN25 (1 pc) Enclosed (2 pcs.)
115 -141 Gasket, DN25 PN25 (1 pc) Enclosed (2 pcs.)

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
14
5Dimensioned sketches
All measurements are in mm, unless otherwise stated.
Figure 1
Flange EN 1 92-1, PN25
Nom.
di meter Nom. flow q
p
L D k B1 Bolts Steel tube
length
Approx.
weight
[m³/h] Qu ntity
Thre d
d
2
C [
[[
[kg]
]]
]
DN15 15 & 25 5
3
25
119 8 M24 26 65 37
DN15 4 5
3
25
14 8 M24 26 625 36
DN2 4 & 6 5
36
31
166 12 M24 26 57 49
DN25 4 & 6 6
425
37
166 12 M27 3 57 79
DN25 1 6
425
37
194 12 M27 3 5 75
Table 7

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 15
Figure 2
Nom. di meter Nom. flow q
p
E
[m³/h]
DN15 15 & 25 282
DN15 4 3 3
DN2 4 & 6 329
DN25 4 & 6 329
DN25 1 357
Table 8

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
16
6Pressure loss
Pressure loss in a flow sensor is stated as max. pressure loss at q
p
.
According to EN 1434 max. pressure loss must not exceed .25 bar unless the energy meter includes a flow
controller or functions as pressure reducing equipment.
The pressure loss in a meter increases with the square of the flow and can be stated as:
pkvQ ∆×=
where:
Q = volume flow rate [m³/h]
kv = volume flow rate at 1 bar pressure loss
∆
p = pressure loss [bar]
Nom. flow q
p
Nom. diameter Q at 0.25 bar
[m³/h] [mm] [m³/h]
A 150 & 250 DN150 1060 530
B 400 DN150 2000 1000
C 400 & 600 DN200 & DN250 4040 2020
D
1000
DN250
8160
4080
Graph kv
Table 9. Pressure loss table.
∆
∆∆
∆p ULTRAFLOW
®
54 DN150-250
0,01
0,1
1
100 1000 10000
Flow [m³/h]
∆
∆
∆
∆p [bar]
ABCD
Diagram 1. Pressure loss graphs.

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 17
7Inst ll tion
Prior to installation of the flow sensor, the system should be flushed.
Correct flow sensor position (flow or return) appears from the front label of MULTICAL
®
. The flow direction is
indicated by an arrow on the side of the flow sensor.
Ple se note:
ULTRAFLOW
®
54 may be lifted in the lifting rings only.
Pressure st ge of ULTRAFLOW
®
54:
PN25
Temper ture of medium, ULTRAFLOW
®
54:
2…15 °C/2…5 °C. See marking on label.
Mech nic l environment:
M1 and M2 (fixed installation with minimum vibration and fixed installation with
considerable or high vibration level respectively). See marking on label.
Electrom gnetic environment:
E1 and E2 (housing/light industry and industry respectively). See marking on label.
The meter’s signal cables must be drawn at min. 25 cm distance to other installations.
Clim tic environment:
Must be installed in environments with non-condensing humidity as well as in closed
locations (indoors).
The ambient temperature must be within 5…55°C.
M inten nce nd rep ir:
The flow sensor is verified separately and can, therefore, be separated from the
calculator. It is permitted to replace the supply and change the supply type. For battery supply a lithium battery
with connector from Kamstrup A/S must be used. Lithium batteries must be correctly handled and disposed of
(see Kamstrup document 551 -4 8, ”Lithium batteries - Handling and disposal”). Other repairs require
subsequent re-verification in an accredited laboratory.
If ULTRAFLOW
®
54 is connected via a galvanically coupled output module, the flow sensor may be connected to a
Kamstrup MULTICAL
®
calculator only.
If other calculator types are connected, ULTRAFLOW
®
54 must be fitted with a galvanically separated output
module and a power supply of its own.
Note:
Please make sure that pulse figures of flow sensor and calculator are identical.
The steel tube between flow sensor housing and electronics box may not be disassembled.
At medium temperatures above 9 °C (T
med
> 9 °C) or medium temperature more than 5°C below ambient
temperature (T
med
< T
amb
- 5°C) the flow sensor's electronics box must be mounted via the enclosed distance piece.
Alternatively, the electronics box can be wall mounted at a distance of minimum 17 mm from the sensor.
In order to prevent cavitation the back pressure at ULTRAFLOW
®
must be min. 1.5 bar at q
p
and min. 2.5 bar at q
s
.
This applies to temperatures up to approx. 8
o
C.
When the installation has been completed, water flow can be turned on. The valve on the inlet side must be
opened first.

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
18
7.1 Inst ll tion ngle of ULTRAFLOW
®
54
ULTRAFLOW
®
can be installed horizontally,
vertically, or at an angle.
ULTRAFLOW
®
54 is normally installed
horizontally, with the lifting rings oriented
vertically. The ultrasound paths in the flow
sensor tube will thus be vertical, which is
optimal in connection with possible
stratification of the medium.
7.1.1 Mounting ULTRAFLOW
®
54 in lifting ring
ULTRAFLOW
®
54 can be mounted hanging from one of the two lifting rings depending on required flow direction.
The enclosed distance piece can be used to secure optimal position of the electronics box. (See
paragraph 7.2
)
Figure 4
Figure 5
Figure 3

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1 19
7.2 Mounting of ULTRAFLOW
®
54 electronics box
At
medium temper ture below 90°C (T
med
< 90°C) nd t medium temper ture less th n
5°C below mbient temper ture (T
med
> T
mb
- 5°C)
the electronics box can be mounted
directly on the flow sensor housing via the factory mounted fitting.
If the flow sensor is vertically mounted, the cable connections of the electronics box will
be horizontally oriented. This is permitted. If the cable connections should preferably
point downwards, the electronics box can be mounted via the enclosed distance piece,
which moves the box approx. 17 mm away from the flow sensor housing. Alternatively,
a shorter distance piece, which only moves the box approx. 45 mm away from the flow
sensor housing, can be used. The short distance piece must be ordered separately
(6561-332).
At
medium temper ture bove 90°C (T
med
> 90°C)
the temperature is too high for the
electronics box to be mounted directly on the flow sensor housing.
Therefore, the electronics box must be mounted via the enclosed distance piece. The
cable connections must always point downwards. (See
paragraph 7.2.1
)
Alternatively, the electronics box can be wall mounted as long as the distance to flow
sensor housing and pipe installation is minimum 17 mm.
It can also be an advantage to use the enclosed distance piece if the flow sensor
housing is insulated and the electronics box must be removed from the insulation.
If the required position of the electronics box differs from standard position, the
distance piece can be mounted with the enclosed collar band around the flow sensor
housing. However, please note that the cable connections must always point
downwards. (See
paragraph 7.2.1
)
At
medium temper ture more th n 5°C below mbient temper ture (T
med
< T
mb
- 5°C)
(typically in cooling installations) it is important to take action to avoid condensation
in the electronics box.
Therefore, the electronics box must be mounted via the enclosed distance piece.
The cable connections must always point downwards. (See
paragraph 7.2.1
).
Alternatively, the electronics box can be wall mounted as long as the distance to flow sensor housing and pipe
installation is minimum 17 mm.
Furthermore, when mounting the electronics box please make sure that the cable connections on the box are at a
higher level than the cable connection on the flow sensor housing.
By vertical mounting of ULTRAFLOW
®
54 in a riser this can be secured by mounting the distance piece by means of
the collar band as shown in
Figure 8
.
Figure 7
Figure 8
Figure 6

TECHNICAL DESCRIPTION ULTRAFLOW
®
54 DN150-250
5512-876 GB/ 4-2 12/Rev. F1
2
If ULTRAFLOW
®
54 is mounted horizontally, the electronics box can be mounted on the distance piece by means of
the collar band. The distance piece can then be turned upwards until the cable connections on the electronics box
are in a higher position than the cable connection on the flow sensor housing. See
Figure 9
.
Alternatively, the electronics box can be wall mounted at a suitable distance to the installation (minimum 17
mm).
7.2.1 Orient tion of flow sensor electronics box
Mounting the electronics box, the cable connections must always be horizontally or downwards oriented in order
to avoid the risk of water and condensation being led into the electronics box via the cables.
This is especially important in humid environments, when ULTRAFLOW
®
54 is used as cooling sensor or if the
medium temperature can become more than 5°C lower than the ambient temperature (T
med
< T
amb
- 5°C).
Furthermore, steel tube and wires must in general hang freely downwards after the cable connections to form a
drip nose for drainage of water and condensation.
Figure 9
Figure 10
Max. 90° Max. 90°
Table of contents
Other Kamstrup Accessories manuals
Popular Accessories manuals by other brands

Altimaster
Altimaster N3 quick start guide

Century
Century SENSORE PIR SENS3-36044 quick start guide

Apogee Instruments
Apogee Instruments SQ-422 owner's manual

Shenzhen Yongchangda Electronics Co,Ltd
Shenzhen Yongchangda Electronics Co,Ltd OJB-LS712-Z Operation instructions

Vestamatic
Vestamatic VRS Luxsensor S Installation and operating instructions

Bose
Bose Wave WaveRadio/ owner's guide