Keller Acculevel User manual

Keller America Inc User’s Guide Rev. 07/19

Keller America Inc User’s Guide Rev. 07/19
Table of Contents
I. CompanyInformaon..................................................................................2
II. ContactInformaon……......……………………………………………………………………..2
III. ProductApplicability.………....………………………………………………………………….2
IV. ProductOverview…………………………………………………………………………………….3
V. Lightning/SurgeProtecon.………………………………………………………………………4
VI. Opons/Accessories.………………………………………………………………………………5
VII. Installaon……....………………………………………………………………………………………6
VIII. Useandcare...…………….…………………………………………………………………………..8
IX. TermsandCondions…....…………………………………………………………………………9
X. Appendix
a. Generic2-wireCurrentLoopConguraon………………………………A-1
b. Generic3-wireVoltageOutputConguraon…………………………..A-1
i. Econoline
1. 4-20mA,Cable..................………………………………….......A-2
2. 4-20mA,mPmConnector..................………………………A-2
3. 0.5-4.5VDC,Cable................…………………………………..A-2
4. 0.5-4.5VDC,mPmConnector................……………………A-2
ii. Valueline
1. 4-20mA,Cable................…………………………………………A-3
2. 4-20mA,DIN43650Connector................…………………A-3
3. 4-20mA,MIL-C-26482Connector.................……………A-4
4. 0-5/10VDC,Cable.................……………………………………A-3
5. 0-5/10VDC,DIN43650Connector..................……………A-3
6. 0-5/10VDC,MIL-C-26482Connector.................………..A-4
iii. Preciseline
1. 4-20mA+RS485,Cable................…………………………….A-5
2. 0-5/10VDC+RS485,Cable.................………………………..A-5
3.SDI-12+RS485,Cable.........................................…………A-5
4. 4-20mA+RS485,MIL-C-26482Connector...................A-6
5. 0-5/10VDC+RS485,MIL-C-26482Connector.....………..A-6
6. SDI-12+RS485,DIN43650Connector........................…A-5
iv. Levelgage
1. 4-20mA,Cable................…………………………………………A-7
2. 0-5/10VDC,Cable.................………………………………….…A-7
v. LevelRat
1. 4-20mA+RS485,Cable..............………………………………A-7
2. 0-5/10VDC+RS485,Cable..............…………………………A-7
vi. Acculevel
1. 4-20mA+RS485,Cable.………………..............………………A-7
2. 0-5/10VDC+RS485,Cable..............…………………………A-7
3. SDI-12+RS485,Cable..................................................A-8
vii. Microlevel/Nanolevel
1. 4-20mA+RS485,Cable...………………………………...........A-8
c. SubmersibleLevelTransmiers
i. InstallaonTips.………………………………………..……………A9-11

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
IV. Product Overview - Level Transmiers
Acculevel-TheAcculevelfromKellerisahighaccuracysubmersibleleveltransmier.
IncorporangallofthefeaturesoftheLevelgageincludingtheNSF61andNSF372
cercaons,theAcculevelhasaddionalfeaturesthatprovideenhancedfunconality,
includingdualoutputs;i.e.,oneanalog(4…20mA,0…5VDC,0…10VDC)andonedigital
(RS485).TheRS485interfaceprovideslevelandtemperatureinformaonandallowsthe
usertorescaletheanalogoutputfrom10…110%ofthebasicrange.Addionally,the
AcculeveliscapableofgreateraccuracythantheLevelgage,withastandardaccuracyof
0.25%BRTEBandanoponal0.1%BRTEB.TheAcculevelcanbemanufacturedin316L
stainlesssteelortaniumforincreasedresistancetocorrosion,notablyfromseawater.
Acculevel SDI -TheAcculevelSDIisaversionoftheAcculevelhighaccuracysubmersible
leveltransmierthatisavailablewithSDI-12orRS485digitalcommunicaonprotocols.
Itisavailablewithstandardaccuracyof±0.1%FSTEBinrangesupto900WCand
oponalUSGSOSWaccuracyforrangesupto70WC.TheAcculevelSDIcanbemanu-
facturedinstandard316Lstainlesssteeloroponaltaniumforincreasedresistanceto
corrosion,notablyfromseawater,carriestheNSF61andNSF372approvals.
Levelgage-TheKellerLevelgageisageneralpurposesubmersibleleveltransmier
availablein1%and0.5%BRTEBaccuracy.Constructedfrom316Lstainlesssteel,itis
ideallysuitedformostfreshwatermonitoringapplicaons.Withstandardconstrucon
(i.e.EPDMandXLPE)materials,theLevelgagehasbeenceredtoNSF61andNSF372
standardsforuseindrinkingwater.Itisavailableincustomrangesfrom0…3WCto
0…900WC.Cablelengthsarecuttouserspecicaons.TheLevelgageisalsoavailable
invariousoutputconguraons,including4…20mA,0…5VDC,and0…10VDC.
LevelRat -TheKellerLevelRatisspecicallydesignedtoprovide0.5%BRTEBaccuracy
forlevelindicaoningrease-ladenenvironmentscommonlyfoundinlistaonsserving
commercialconcerns.TheLevelRatdesigntakesastepawayfromthelargeandbulky
proteconcagedesignsbyulizingauniquediaphragmmaterialthatoersthenon-
sckproperesofTeonandprovidesaddedresistancetodamagefromdebris.The
LevelRatprovidesdualoutputs;yourchoiceofanalogoutputs(4…20mA,0…5VDC,or
0…10VDC)plusonedigital(RS485)forlevelrangesfrom0…5WCto0…100WC.
Microlevel-TheMicrolevelcombinesthecapabilityoftheAcculevelwithaclassleading
0.63”(16mm)outsidediameter.TheMicrolevelisavailableinfullscalerangesfrom0…3
WCthrough0…900WCandprovides0.25%BRTEBaccuracy.LiketheAcculevel,italso
providesboth4…20mAanalogandRS485Digitaloutput.TheRS485interfaceprovides
levelandtemperatureinformaon.Italsoallowstheusertorescaletheanalogoutput
from10…110%ofthebasicrange.
Nanolevel-TheNanolevelisuniquelydesignedforhighaccuracymeasurementof
verylowpressureranges.TheNanolevelisavailableinfullscalerangesfrom0…4inWC
through0…10WCandisavailablewithstandardaccuracy0.25%BRTEBand0.1%BR
TEBoponal.LiketheAcculevel,italsoprovidesboth4…20mAanalogandRS485Digital
output.TheRS485interfaceprovideslevelandtemperatureinformaon.Italsoallows
theusertorescaletheanalogoutputfrom10…110%ofthebasicrange.
Page3
I. Company Informaon
KellerAmericaIncistheNorthAmericansubsidiaryofKellerAGfürDruckmesstechnik,
whichconnuesastheleaderinlevelandpressuresensing.Fromhumblebeginnings,
Kellernowprovidesitsproductsandexpersethroughaworldwidenetworkoffacto-
ry-trainedprofessionals.
Withtheadventofinexpensive,miniaturizedmicroprocessors,Kellerconnuestoad-
vancethestate-of-the-artinfullypackagedpressuretransmiers,withTotalErrorBand
performancenotpossiblejustafewshortyearsago.Annualsensorproduconnow
exceeds1millionpieces.
DoingbusinesswithKelleriseasyandmostinquiriesareansweredwithin24hours.
StandarddeliveryonU.S.-assembledproductsis3daysARO.Weoerconvenientterms
withapprovedcreditandacceptmostmajorcreditcards.
AtKeller,providingcustomerswithsuperiorvalueisawayoflife.
II. Contact Informaon
KellerAmerica,Inc.
351BellKingRd
NewportNews,Virginia,23606
P:877-253-5537
F:757-596-6659
Web: www.kelleramerica.com
Email: sales@kelleramerica.com
III. Product Applicability:
Unlessotherwisenoted,thismanualcontainsuserinformaonforthefollowinglevel
andpressureinstrumentaonprovidedbyKellerAmerica:Acculevel™,Levelgage™,
LevelRat™,Microlevel™,Econolevel™,andNanolevel™submersibleleveltransmiers;
Econoline™,Valueline™,andPreciseline™abovegroundpressuretransmiers.
Electronic copies of this user’s guide can be found at: hp://www.kelleramerica.com/
manuals-and-soware/manuals/Keller_America_Users_Guide.pdf
Page2

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
VI. Opons /Accessories:
Titanium Construcon -OponalfortheAcculevelandPreciseline.Highlyrecommend-
edforbrackishandseawaterapplicaons.
External Surge Protector-Recommendedforlightning/surgeproteconofuser’spower
supply/readout/PLC,etc.TobeusedinconjunconwithLevelgage,Acculevel,LevelRat,
Econolevel,Microlevel,Nanolevel,Valueline,orPreciselinetransmiers.
½” NPT Pipe conduit ng -½”NPTmaleng,allowsrigidmounngto½”conduitfor
Levelgage,Acculevel,orLevelRatsubmersibletransmiers.Itcanalsobeaddedtoour
PreciselineandValuelinepressuretransmiers.
Drying Tube Assembly-Cleartubelledwithindicangdesiccant,aachesdirectlyto
cableventtube,interceptswatervapor.Highlyrecommendedwhenoperangisinhigh
humiditycondions.Mustbeperiodicallyrenewedasdesiccantbecomessaturated,
turningcolorfromblue(dry)topink(saturated).
Bellows Assembly-Alternavetothedryingtube,thisaneroidbellowsaachesto
cableventtubeandrequiresnoperiodicmaintenance.Notethattheuseofthebellows
resultsinaclosedreferencepressuresystemsubjecttozeroshierrorsinducedby
changingtemperaturesofupto0.0004psi/ºC.Notrecommendedforusewithaccuracy
requirementsof±0.25%FSorbeer,orranges<2psi.
Electrical Connectors -mPm393isoponalfortheEconoline,DIN43650andMIL-C
26482areoponalforValuelineandPreciseline.ThemPm393andMIL-C26482mang
connectorsfeaturesoldercupswhiletheDIN43650incorporatesscrewterminals.
RS485 Converter/Cable -FortheuserwhowishestocommunicatewiththeirAcculevel,
LevelRat,Nanolevel,Microlevel,orPreciselinetransmierviatheRS485digitalinterface.
AvailableinRS232andUSBversions,alongwithcableadapters,asneeded,andCCS30
Soware(alsoavailablefordownload,freeofchargefromwww.kelleramerica.com).
Consultfactoryfordetails.
Terminaon Enclosure-Convenientoponcomplemennggauge-typepressure/level
transmiers,whereitisdesiredtoterminatethetransmiercableclosetothemea-
surementpoint.ItincludesaNEMA4Xclearfrontenclosure(7.9X4.7X3.5inches)with
two,liquid-ghtcablengs(onein,oneout),aterminalstrip,andampleroomfor
mounngadryingtubeorbellowsassembly.
Stabilizing Weight-ZincpropshaanodeadaptedtotØ21mmO.D.ofLevelgage,
Acculevel,andLevelRatsubmersibleleveltransmiers.Aidsincorrosionresistanceas
wellashelpsensurethatthecableremainstautinturbulentcondions.
Cable Hanger-Singleeyefor0.230”diametercable.Designedtogripthecablejacket
andprovideasuspensionpointforinstallaonofcabledtransmiers.
Pressure Test Adapters -Designedtofacilitatecalibraonandmaintenancetesng,
thesespecialtyadaptersallowforconneconofthevariousKellerleveltransmierstoa
pressurecalibrator.
Page5
Econolevel-TheEconolevelbyKellerisalowcostgeneralpurposesubmersiblelevel
transmierdesignedforhighvolumeapplicaons.Itisavailableinnominalpressure
rangesfortankandwelllevelmonitoringapplicaons.TheEconolevelprovidesa
4…20mAanalogoutputthatiscompablewithmostSCADAsystemsandPLCs.Mini-
mumorderquanesapply.
IV. Product Overview cont’d - Pressure Transmiers
Econoline-TheEconolinebyKellerisalowcostgeneralpurposepressuretransmier.It
isavailableinnominalpressurerangesbetween5psiand10,000psiandwithathreaded
¼”NPTpressureconnecon.Idealfortankandpipepressuremonitoringapplicaon,it
provideseither4…20mAor0.5…4.5VDC(raometricornon-raometric)analogoutputs
thatarecompablewithmostSCADAsystemsandPLCs.
Valueline-TheValuelinebyKellerisahighlyversaleandaccuratepressuretransmier.
Itisavailableincustompressurerangesfrom0…2through0…15,000PSIandyourchoice
ofelectricalconneconsincludingaachedcable,DIN43650,andMIL-C-26482connec-
tors.Theaachedcableversionisfullysubmersible,makingittheidealchoicewhen
installedinavalvepitorotherenvironmentpronetoperiodicooding.TheValueline
alsocarriestheNSF61andNSF372approvalsfordrinkingwaterapplicaons.
Preciseline -ThePreciselineisourmostaccurateabove-groundpressuretransmier.
Withstandardaccuracyof0.25%BRTEBandoponal0.1%BRTEB,a¼”NPTpressure
connecon,anddualoutputs(analoganddigital)thePreciselineoersversalityin
designandapplicaon.LiketheAcculevel,theanalogoutputcanberescaledviathe
RS485interface.TheRS485interfacealsoallowstemperaturedatatoberetrievedifthe
applicaondemands.LiketheValueline,thePreciselineisincludedintheNSF61and
372approvals.
Preciseline SDI-ThePreciselineSDIishighlyprecisepressuretransmierthatisavail-
ablewithSDI-12orRS485digitalcommunicaonprotocols.Itisavailablewithstandard
accuracyof±0.1%FSTEBinrangesupto900WCandoponalUSGSOSWaccuracy
forrangesupto70WC.ItcomeswithyourchoiceofaachedcableorMIL-C-26482
connectorelectricalconnecons.Thecableversionisfullysubmersible,makingitthe
idealchoiceinenvironmentspronetoperiodicooding,whiletheNSF61andNSF372
approvalsmakethePreciselineSDIsuitableforuseindrinkingwaterapplicaons.
V. Lightning / Surge Protecon:
Asofthiswring,Kelleristheonlypressure/leveltransmiermanufacturerintheworld
toprovide,atnoaddionalcharge,alifemewarrantyagainstdamagecausedbylight-
ningand/orelectricalsurge.Thisguaranteeappliestothe4…20mAoutput
versionofthefollowingproducts:Levelgage,Acculevel,LevelRat,Microlevel,Valueline,
andPreciseline.Thiswarrantyapplieseveninthecaseofadirectlightningstrike.The
user’sliabilityislimitedtoshippingcoststoKellerAmerica.
Page4

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
Thecalculaonsbelowareusefulinidenfyingtheminimumsupplyvoltageneededfor
acurrentloopwithaddionallineimpedancesorconversely,themaximumcurrentloop
impedanceallowedforagivensupplyvoltage.
Minimumsupplyvoltagewithlightningproteconoponinstalled:
11VDC+(Totalloopimpedancex0.022)
Minimumsupplyvoltagewithoutlightningproteconoponinstalled:
8VDC+(TotalloopImpedancex0.022)
Maximumallowableloopimpedancewithlightningproteconopon
installed:
(SupplyVDC–11VDC)/0.022
Maximumallowableloopimpedancewithoutlightningproteconopon
installed:
(SupplyVDC–8VDC)/0.022
Transmier Anchoring-ItisrecommendedthatKellersubmersibletransmiersbe
installedinasllingwelloraachedtorigidconduitviaaconduitngintegraltothe
transmier,inordertopreventdamagetothetransmierfromimpactwithimmovable
objects.Itisnotadvisabletoethetransmiertoapumportopiping,asanyproblem
withthetransmiercouldrequirethatthepumpbepulledfromtheinstallaon.
Someapplicaonsrequirethetransmiertobesuspendedwithoutaprotecveslling
wellorconduitaachment.Inallinstallaons,careshouldbetakentopreventdamage
tothesubmersiblecable.
Transmier Submersion -Damagetosubmersiblecablecanleadtofailureofthetrans-
mier.Kelleremploysaruggedcablejacketmaterialstominimizetheriskofcutsand
abrasion.Sll,takecarewhenloweringyourtransmierintothewell,makingsurethe
cabledoesnotdragoversharpedges.Avoiddroppingthetransmierfromthesurface.
Donotsubmergeelectricalconneconendofcable.
Condensaon protecon -Kellerhasopmizedthesizeofthecableventtominimize
theoccurrenceofwatervaporincursion.Inareasofhighhumidity,itmaybedesirable
touseaDryingTubeAssembly(desiccant)orBellowsAssemblytopreventwatervapor
fromenteringtheventtube.ContactKellerAmericafororderinginformaon.
Bending of Cable-Ourjacketedcableisquiteexible.However,caremustbetakento
ensuretheventtubeintegraltothecableisnotcrimpedwhenbendingthecabletosuit
yourinstallaon.Itisrecommendedthatthecablenotbebenttoaradiussmallerthan
1inch.
Cable Compression -Manyusersemployacompressionngtosecureourcableasit
entersajunconbox.Caremustbetakenthatthengisnotoverghtened,causing
damage to the cable and/or crimping the vent tube.
Page7
Digital Display / Meter -TheTRIDENTdisplaybyPrecisionDigitalisaversaleandcost
eecveprocessmeterprovidinganeasytouseandreaddisplay/controllerforyour
levelandpressuremeasurementapplicaon.Formoreinformaonandtechnicalsup-
port,pleasecontactPrecisionDigitalat(800)343-1001oronlineatwww.predig.com.
VII. Installaon:
Thefollowingisimportantinstallaonandgeneralmaintenanceinformaonforsub-
mersibletransmiers.PleasecontactKellerAmericaforaddionalinstrucon.
Supply Voltage-Adequatesupplyvoltageiscricaltoensureproperoperaonof4-20
mApressureandleveltransmiers.Withouttheminimumrequiredvoltageavailableat
thetransmier,thetransmierwillnotoutputthecorrectanalogvalue.
Manyanalogtransmierswillappeartooperateproperlyevenwhenthesupplyvoltage
isnotadequatetopowertheloopwhenthetransmiershouldbeoutpung20mA.
Forexample,a10voltsupplymayappeartobeenoughtopowerananalogtransmier
whenitisoutpung4mAwithzeropressureapplied,butasthetransmier’soutput
increaseswithincreasingpressure,voltagedropsacrossotherdevicesintheloop(ana-
loginputdevices,cableand/orexternalbarrierdevices)mayreducethesupplyvoltage
tothetransmierandpreventitfromprovidingthecorrectoutputaboveacertaininput
pressure/levelthreshold.
KellerAmerica’s4-20mApressureandleveltransmiersfeaturemicroprocessorbased
signalcondioning.Duringpowerup,thecircuitperformsachecksequencewhichde-
termineswhetherthereissucientsupplyvoltagetopoweralldevicesontheloop,by
sengtheoutputto~110%ofthemaximumvalue,i.e.,~22.5mA.Ifthesupplyvoltage
isnotsucienttosupply22.5mAtothecircuit,thenthemaximumpossiblecurrentwill
beseenontheanalogoutput,e.g.,17mA,andthetransmierwillnotiniatenormal
operaon.
Thebenetofthistechnologyisthattotalloopimpedanceisaccountedforpriorto
placingtheequipmentintoservice,prevenngfalseindicaonswhenthevoltagesupply
isinsucienttosupporttheloopwithmaximumpressureapplied.
Mostcurrentloopscontainanaloginputdevices,indicatorsorothercomponentshaving
inputimpedanceswhichmustbeconsideredwhencalculangthesupplyvoltagesneed-
ed.Forexampleananaloginputdevicewitha250OhmInputImpedancewillrequire
anaddionalvoltageof5.5VDC(250x0.022=5.5)inaddiontotheminimumsupply
voltagenecessaryforthetransmiertooperateproperlyovertheenrerange.
Page6
Total Loop
Impedance
Indicator
Analog Input
Device
Cable
Resistance IS Barrier
4 - 20mA output
Level / Pressure
Transmitter

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
theinput/nosecaptothedeviceisclear.Finishbysrringinfreshwater.Wipedrywitha
soragortowel.
Asoapscumandhard-waterstainremovermayalsobeused,ifnecessary,butonly
aercompabilitywithanyo-ringsealsintheKELLERproductisdetermined.Followthe
solventmanufacturer’srecommendaonsforsafehandling.
IX. Terms and Condions:
Oers -Unlessotherwiseindicated,thepricessetforthinthisquotaonarevalidfor60
daysfromthedateofthequotaonandapplytoproductsthatarescheduledforship-
mentwithintwelvemonthsfromthedateoftheBuyer’spurchaseoratKellerAmerica,
Inc.shippingcapabiliesatthemetheorderisentered,whicheverislater.
Acceptance of order-Anypurchaseordertobeacceptedhastorefertoaquotaon,
whetherdeliveredbysurfacemail,e-mailorfacsimile.Alloralordersmustbeconrmed
inwring.Byreferringtothisquotaon,BuyeracceptsandadoptstheGeneralTerms
andCondionsofSale(“TermsandCondions“)totheexclusionofanyaddionalor
dierenttermsappearinginBuyer’spurchaseorderandwaivesanyrightBuyermay
havetoenforceanysuchaddionalordierentterms.OurConrmaonofOrderor
Invoicevalidatesorders.Ordersforcustom-conguredproductsarebuilttoyourspeci-
caonandthereforemaynotbecanceledoncetheorderhasbeenconrmed.
Date of shipment-Theesmatedshippingcapabilitystatedonthequotaonisgiven
solelyfortheBuyer’sinformaonanddoesnotconstuteacommitmenttodeliver
productsinaccordanceherewith.Buyermayrequestaspecicshippingdateorshipping
schedule.KellerAmerica,Inc.willscheduleshipmentsbaseduponBuyer’srequestand
KellerAmerica,Inc.’sshippingcapabiliesatthemeBuyer’spurchaseorderispro-
cessed,atwhichmeKellerAmerica,Inc.willissuetoBuyeraformalAcknowledgment
ofOrderthatwillindicatetheesmatedshippingdate(s).Aertheshipmentshavebeen
scheduled,BuyermaynotcancelorpostponeascheduledshipmentunlessBuyersub-
mitsitsrequestinwringandKellerAmerica,Inc.consentsbyissuinganewacknowl-
edgment.
Anyrequesttocancelortorescheduletheshipmentthatisreceivedlessthan21days
fromthedatescheduledfortheshipmentoftheproductscoveredbytherequestmay
berejectedasunmely,ormaybeaccepteduponpaymentofthecancellaonchargeof
20%orareschedulingchargeof10%ofthesalespriceshownonthisquotaonatKeller
America,Inc.’sopon.KellerAmerica,Inc.willuseitsbesteortstoshiponorevenbe-
foretheesmatedshippingdatesindicated,butwillnotbeliableforanydelayorfailure
todeliver.KellerAmerica,Inc.shallnotbeliableforanyspecial,incidentalorconsequen-
aldamagesresulngfordeliverydelaysorinabilitytodeliver.
AllgoodsormaterialssuppliedbyKellerAmerica,Inc.remainitspropertyunltotalpay-
mentisreceived.AllsuchgoodsandmaterialsareatthesoleriskoftheBuyerandinthe
eventofbeingdamaged,destroyedorlostaerdelivery.KellerAmerica,Inc.isentled
toreceivethetotalpaymentofthosegoods.
Page9
Posion Sensivity-Thetransmiershouldbeinstalledinavercalposion,other-
wiseitmayexhibitanoset.Ifthetransmiermustbeinstalledinanyposionother
thanvercal,measuretheoutputwithnopressureappliedpriortoconnecontoyour
display,PLC,orcontroller.Usethemeasuredvalueforyourzeropoint.
VIII. Use and Care:
Safe Handling-SafehandlingofKELLERpressuremeasurementdevicesisaccomplished
ifanominalamountofcareistaken.Thingstoavoidare:
•Sharpimpactagainsthardsurfaces
•Contactwithchemicalsknowntobecorrosivetothematerialsofconstrucon
•ProbingofpressuresensingmembranewithANYTHING
Limits of Pressure -KELLERpressuresensors,transducersandtransmiersaredesigned
towithstandacertainamountofoverpressurewithoutdamageorcalibraonshi.It
canrangefrom15Xforthelowerpressurerangesto1.1Xforthehighestranges.This
valueisdierentforeachproductandisreferredtointheproductliteratureas“Over
pressure”.Itistheuser’sresponsibilitytoensurethattheproperKELLERproductischo-
senfortheparcularpressurecondionsexpected.
Environmental condions-EachKELLERproductisdesignedtobecompablewitha
parcularenvironment.Itistheuser’sresponsibilitytoensurethattheKELLERproduct
isnotexposedtoanenvironmentalcondionforwhichitisnotdesigned.Thesecondi-
onscanincludeoperangtemperaturerangeandexposuretohigh-pressurewaterjets,
medianotcompablewiththematerialsofconstrucon,submergenceoftransmiers
notdesignedforthatpurpose,orpotenallyexplosiveatmospheres.AKELLERengi-
neercanhelptheuserdeterminethecorrectchoiceofenclosuretosuittheparcular
applicaon.
Electrical condions -EachKELLERproductisdesignedtooperateproperlywithina
specicrangeofelectricalcondions.Thespecicproductlabeldenestherang(s),
ifany,thatappliestotheproducttowhichitisaxed.Alltransmiersaredesigned
towithstandreversepolarityaswellasovervoltagetoacertainextent.Itistheuser’s
responsibilitytoensurethatallelectricalconneconsaremadetotheKELLERproducts
inaccordancewithKELLERrecommendaonsaswellaslocalelectricalcode.Wirecolors
orconnectorpin-outsareeitherprintedonthelabelaxedtotheproductorprovided
separately.
Cleaning-WARNING!Undernocircumstancesshouldthemembrane,pressureinput
port,ornosecaptotheKELLERdevicebeprobedwithanyobject.Damagetothesens-
ingmembraneispermanentand,inmostcases,requiresrepairorreplacement.
Regardingmedia-isolatedproducts,shouldthepressureinputornosecaptothesensor,
transducer,ortransmierbecomefouled,itmaybecleanedinthefollowingmanner:
Thedeviceshouldbeslowlyloweredmembrane-endintoasoluonofwarm,soapy
water.Careshouldbetakennottosubmergetheenredevice,unlessitisspecically
designedforconnuoussubmergence.Agitateinthesoluonfor20-30secondsorunl
Page8

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
uponpaymentofalltravelexpensesbyBuyer.
WarrantyperiodfortheLevelgage,LevelRat,Acculevel,Microlevel,Preciseline,andVal-
uelineproductsis24(twenty-four)monthsfromdateofshipment.Warrantyperiodfor
allotherproductshereinis12(twelve)monthsfromdateofshipment.Warrantyrepair
coversallapplicablepartsandlabor.Thiswarrantyisgiveninlieuofanyotherwarranty,
expressorimplied.KellerAmerica,Inc.explicitlydisclaimsanyimpliedwarranesof
merchantabilityandtnessforaparcularpurpose.Therearenowarranes,expressor
implied,thatextendbeyondthedescriponherein.Thesoleandexclusiveremedyfor
anyclaimsagainstKellerAmerica,Inc.shallbethewarrantydescribedinthisdocument.
Alldamages,directorconsequenal,limitedtothedescribedwarrantyareexcluded.
Repairs-UnlessotherwiserequestedinwringbytheBuyer,allproductsreturnedto
KellerAmerica,Inc.underthetermsofthewarrantywillbecheckedandanalyzedinor-
dertodeterminethecauseofthedefault(s)claimedbytheBuyer.Areportwillthenbe
submiedtotheBuyerpoinngoutthenatureofthedefault(s),thepartyresponsible
forthedefault(s)andthequotaonoftherepair,ifneeded.Forfurtherrepairinstruc-
onsgotowww.kelleramerica.com.
Complaints-AllclaimsordisputesmustbemadeinwringtoKellerAmerica,Inc.a
maximumof60daysfromreceiptofthegoods,includingdiscoveryoffaultsnotpre-
viouslyapparent.Ifthewarrantyclaimsarejused,KellerAmerica,Inc.isfreeatits
discreontorepair,replaceorissuecredit.Nofurthercompensaonfordamageswillbe
made.
AnydisputesorclaimsofBuyermustbeiniatedinapropercourtorotheradjudicave
body,asapplicable,withinone(1)yearfromthedateofshipmentbyKellerAmerica,
Inc.,oritsrepresentave(s),orsuchclaimshallbedeemedinvalidorexpiredandcannot
berenewed.Totheextentallowed,thislimitaonperiodshalltrumpanyapplicable
statutorylimitaonsperiodthatmaystatealongerperiod.
Limitaon of responsibility -Ourresponsibilityconcernsthecorrectfunconofour
productsonly.Itcannotbeextendedtothewholesysteminwhichtheyareused.Our
responsibilityislimitedtothereplacement,repairorreimbursementofthegoodswe
agreearedefecveornon-conforming.Theclaimmustbeinwringwithin60daysfrom
receiptofthegoods.
Place of jurisdicon / applicable law -Thecontractmadebyacceptanceofthisoer
shallbedeemedmadeintheStateofVirginiaandshallbegovernedbyandconstrued
inaccordancewiththelawsofthatstatewithoutreferencetoorapplicaonofany
conictsoflawsprinciplesandwithoutconsideraonoftheplaceofexecuon.Buyer
expresslyagreestothesubjectmaerandpersonaljurisdiconoftheCircuitCourtsfor
theCityofNewportNews,Virginia,orthefederalDistrictCourtfortheEasternDistrict
ofVirginia,NewportNewsDivision.
Assignment-Neitherthisoernoranycontractresulngtherefrommaybeassigned
ortransferredinwholeorpartwithoutthepriorwrienconsentofKellerAmerica,Inc.
Page11
Price -Unlessotherwisespeciedinthequotaon,ourpricesareinUSdollars(USD).
Theyareexclusiveoffreightcostsandofallstateandlocalsales,use,excise,privilege
andsimilartaxes.SuchtaxesimposedonKellerAmerica,Inc.orwhichKellerAmerica,
Inc.hasadutytocollectinconneconwiththesaleordeliveryoftheproductsde-
scribedonthequotaonshallbepaidbyBuyerandwillappearasseparateitemsonthe
invoice.
Shipment / freight -DeliveriesareF.O.B.NewportNews,VA.Titleandriskoflossshall
passtoBuyerupontenderoftheproductsbyKellerAmerica,Inc.toacommoncarrier.
InabsenceofspecicwrieninstruconfromBuyer,KellerAmerica,Inc.willselectthe
commoncarrier,butKellerAmerica,Inc.shallnottherebyincuranyliabilityinconnec-
onwithshipment.Buyershallberesponsibleforanyfreightcharge.Declaredvaluefor
eachshipmentwillbeamaximumof$100regardlessoftheactualvalueofthegoods,
notwithstandingwrieninstruconsfromtheBuyerspecifyingahigherdeclaredvalue.
Iftheproductsareshippedfreightprepaid,BuyershallpayKellerAmerica,Inc.theap-
propriatefreightcharges,whichwillbeshownasseparateitemsontheinvoice.
Payment -TermsareindicatedonourConrmaonofOrderandonourInvoices.Keller
America,Inc.willsubmitaninvoicetoBuyerforeachshipmentatthemeofshipment.
Exceptasotherwiseprovidedonthequotaon,Buyershallpaytheamountinvoicedby
KellerAmerica,Inc.within30daysfromthedateoftheinvoice.Ifinthejudgmentof
KellerAmerica,Inc.thenancialcondionorpaymentrecordofBuyeratanymedoes
notjusfyshipmentunderthepaymenttermsspeciedabove,KellerAmerica,Inc.may
refusetoshipunlessitreceivespaymentinadvance,oratitsopon,paymentupon
delivery.2%interestpermonthischargedonoverdueaccounts.
Documentaon -Theinformaongiveninourdocumentaon,printedmaer,data
sheetsandpricelistsiswithoutcommitment.Thisinformaonspeciestheproductbut
isnowarranty,unlessagreedinwring.
Warranes -KellerAmerica,Inc.warrantsthattheproductsthatitsellsaredelivered
freefromdefectsinmaterialandworkmanship.KellerAmerica,Inc.’sliabilityunderthis
warrantyislimitedtoreplacingorrepairingorissuingacreditnote,atitsopon,for
anyproductwhichisreturnedtothefactory,transportaonchargesprepaid,and
whichisdeterminedbyKellerAmerica,Inc.tobedefecve.Thiswarrantydoesnotapply
tobaeriesandaccumulatorsandtoanyproductwhichhasbeensubjectedtoordam-
agedduetomisuse,misapplicaon,negligenceoraccident,orwhichhasbeenrepaired
oralteredwithoutexpresspriorandwrienconsentfromKellerAmerica,Inc.Inorder
toobtainserviceunderthetermsofthewarranty,BuyermustnofyKellerAmerica,
Inc.ofanydefectsbeforetheexpiraonofthewarrantyperiodandmakesuitable
arrangementsfortheperformanceofservices.Inallcases,Buyershallberesponsible
forpackagingandshippingtheproductstotheKellerAmerica,Inc.plantwithshipping
chargesprepaid.KellerAmerica,Inc.shallpayforthereturnofanyproductstoBuyerif
theshipmentistoalocaonwithintheconnentalUSA.Buyershallberesponsiblefor
payingallshippingdues,taxes,andotherchargesforproductsreturnedtoanyother
locaon.KellerAmerica,Inc.willprovideon-siteserviceonlyuponprioragreementand
Page10

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
X: Appendix
+ SUPPLY
OUTPUT/GROUND
2-WIRE
TRANSMITTER
POWER
SUPPLY
DISPLAY/
CONTROL
+
-
-
+
2-WIRE CURRENT LOOP
3-WIRE VOLTAGE OUTPUT
+ SUPPLY
+ OUTPUT
3-WIRE
TRANSMITTER
POWER
SUPPLY
DISPLAY/
CONTROL
+
-
-
+
GROUND
A-1
PleaserefertoSeconVII:Installaonforminimumsupplyvoltageinformaon.
NoassignmentortransferinviolaonofthisprovisionshallbevalidorbindingonKeller
America,Inc.
Aorney’s fees-UponanybreachofthisAgreement,thereasonableaorney’sfeesand
costsofthesubstanallyprevailingparty,whetherbyligaonorselement,shallbe
paid by the breaching party.
Page12

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
NOTES:
1: FOR TRANSMITTERS WITH LIGHTNING/SURGE PROTECTION, CONNECT DRAIN WIRE
TO A LOW-IMPEDANCE EARTH GROUND. FOR TRANSMITTERS WITHOUT LIGHTNING/
SURGE PROTECTION, THIS PIN IS CONNECTED TO THE TRANSMITTER CASE.
2: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.
VALUELINE w/ATTACHED CABLE...4-20mA
VALUELINE w/ATTACHED CABLE...0-5...10VDC
VALUELINE w/DIN43650...4-20mA
VIEW OF REAR OF TRANSMITTER
VALUELINE w/DIN43650...0-5...10VDCVALUELINE
+ OUTPUT
VIEW OF REAR OF TRANSMITTER
3
1
2
3
1
2
DRAIN
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
DRAIN
BLACK: + SUPPLY
WHITE: GROUND
RED: + OUTPUT
+ SUPPLY
OUTPUT/GROUND
SEE NOTE 1.
+ SUPPLY
GROUND
A-3
1
2
3
4
1
2
3
4
DRAIN/CASE GROUND
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
DRAIN
BLACK: + SUPPLY
WHITE: GROUND
RED: + OUTPUT
ECONOLINE w/CABLE...4-20mA
ECONOLINE w/mPm393...4-20mA
ECONOLINE w/CABLE...0,5-4,5VDC
ECONOLINE w/mPm393...0,5-4,5VDC
CASE
+ SUPPLY
OUTPUT/GND
VIEW OF REAR OF TRANSMITTER
CASE
+ SUPPLY
GROUND
VIEW OF REAR OF TRANSMITTER
+ OUTPUT
A-2
NOTES:
1: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
BLUE: RS485A
YELLOW: RS485B
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: GROUND
RED: + OUTPUT
BLUE: RS485A
YELLOW: RS485B
PRECISELINE w/ATTACHED CABLE...4-20mA + RS485
PRECISELINE w/ATTACHED CABLE...0-5...10VDC + RS485
DRAIN (NOTE 1)
BLACK: GROUND
WHITE: SDI-12
RED: + VCC
BLUE: RS485A
YELLOW: RS485B
PRECISELINE SDI w/ATTACHED CABLE...SDI-12+ RS485
A-5
NOTES:
1: FOR TRANSMITTERS WITH LIGHTNING/SURGE PROTECTION, CONNECT DRAIN WIRE
TO A LOW-IMPEDANCE EARTH GROUND. FOR TRANSMITTERS WITHOUT LIGHTNING/
SURGE PROTECTION, THIS PIN IS CONNECTED TO THE TRANSMITTER CASE.
2: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.
A
B
C
D
E
F
A
B
C
D
E
F
+ SUPPLY
OUTPUT/GROUND
VALUELINE W/MIL-C-26482...4-20mA
REAR VIEW OF TRANSMITTER
VALUELINE W/MIL-C-26482...0-5...10VDC
+ SUPPLY
GROUND
+ OUTPUT
REAR VIEW OF TRANSMITTER
E: DRAIN
A-4
NOTES:
1: FOR TRANSMITTERS WITH LIGHTNING/SURGE PROTECTION, CONNECT DRAIN WIRE
TO A LOW-IMPEDANCE EARTH GROUND. FOR TRANSMITTERS WITHOUT LIGHTNING/
SURGE PROTECTION, THIS PIN IS CONNECTED TO THE TRANSMITTER CASE.
2: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
NOTES:
1: FOR LIGHTNING/SURGE PROTECTION TO BE EFFECTIVE, CONNECT DRAIN WIRE TO
A LOW-IMPEDANCE EARTH GROUND.
2: LIGHTNING PROTECTION NOT AVAILABLE ON ECONOLEVEL. DRAIN WIRE
CONECTION NOT REQUIRED.
3: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.
LEVELGAGE & ECONOLEVEL w/ATTACHED CABLE...4-20mA
LEVELGAGE w/ATTACHED CABLE...0-5...10VDC
ACCULEVEL & LEVELRAT w/ATTACHED CABLE...4-20mA + RS485
ACCULEVEL & LEVELRAT w/ATTACHED CABLE...0-5...10VDC + RS485
DRAIN (NOTE 1,2)
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: GROUND
RED: + OUTPUT
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
BLUE: RS485A
YELLOW: RS485B
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: GROUND
RED: + OUTPUT
BLUE: RS485A
YELLOW: RS485B
A-7
PRECISELINE w/MIL-C-26482...4-20mA + RS485
REAR VIEW OF TRANSMITTER
PRECISELINE w/MIL-C-26482...0-5...10VDC + RS485
REAR VIEW OF TRANSMITTER
A: + SUPPLY
C: OUTPUT/GROUND
A: + SUPPLY
C: GROUND
B: + OUTPUT
D: RS485A
F: RS485B
D: RS485A
F: RS485B
E: DRAIN
A
B
C
D
E
F
A
B
C
D
E
F
PRECISELINE SDI w/MIL-C-26482...SDI-12 + RS485
REAR VIEW OF TRANSMITTER
A: + SUPPLY
C: GROUND
B: SDI-12
F: RS485B
D: RS485A
A
B
C
D
E
F
A-6
NOTES:
1: FOR TRANSMITTERS WITH LIGHTNING/SURGE PROTECTION, CONNECT DRAIN WIRE
TO A LOW-IMPEDANCE EARTH GROUND. FOR TRANSMITTERS WITHOUT LIGHTNING/
SURGE PROTECTION, THIS PIN IS CONNECTED TO THE TRANSMITTER CASE.
2: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
A-9
MINIMUM PIPE BEND RADIUS
Acculevel/ Levelgage
Ø0.83”
Microlevel
Ø0.63”
Schedule40
1”IPS
(Ø1.315x0.133”w) 22” 18”
1.5”IPS
(Ø1.900”x0.145”w) 4” 5”
2”IPS
(Ø2.375x0.154”w) 3” 3”
Schedule80
1”IPS
(Ø1.315x0.179”w) 22” 22”
1.5”IPS
(Ø1.315x0.200”w) 4” 6”
2”IPS
(Ø2.375x0.218”w) 4” 4”
NOTES:
1: FOR LIGHTNING/SURGE PROTECTION TO BE EFFECTIVE, CONNECT
DRAIN WIRE TO A LOW-IMPEDANCE EARTH GROUND.
2: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.
MICROLEVEL & NANOLEVEL w/ATTACHED CABLE...
4-20mA + RS485
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
BLUE: RS485A
YELLOW: RS485B
DRAIN (NOTE 1)
BLACK: GROUND
WHITE: SDI-12
RED: + VCC
BLUE: RS485A
YELLOW: RS485B
ACCULEVEL SDI w/ATTACHED CABLE...SDI-12+ RS485
A-8

Keller America Inc User’s Guide Rev. 07/19 Keller America Inc User’s Guide Rev. 07/19
A-11
Signal cable
Transmitter
Vent tube
Bellows Assembly
Drying Tube Assembly
VENT TUBE TERMINATION - DRYING TUBE OR BELLOWS
Remove yellow
cap after installation
NOTES:
1: FOR TRANSMITTERS WITH LIGHTNING/SURGE PROTECTION,
CONNECT DRAIN WIRE TO A LOW-IMPEDANCE EARTH GROUND.
FOR TRANSMITTERS WITHOUT LIGHTNING/SURGE PROTECTION,
THIS PIN IS CONNECTED TO THE TRANSMITTER CASE.
2: DRYING TUBE ASSEMBLY - CLEAR TUBE FILLED WITH INDICATING
DESICCANT, ATTACHES DIRECTLY TO CABLE VENT TUBE,
INTERCEPTS WATER VAPOR. HIGHLY RECOMMENDED WHEN
OPERATING IS IN HIGH HUMIDITY CONDITIONS. MUST BE
PERIODICALLY RENEWED AS DESICCANT BECOMES SATURATED,
TURNING COLOR FROM BLUE (DRY) TO PINK (SATURATED).
REMOVE YELLOW CAP FROM FREE END AFTER INSTALLATION.
3: BELLOWS ASSEMBLY - ALTERNATIVE TO THE DRYING TUBE, THIS
ANEROID BELLOWS ATTACHES TO CABLE VENT TUBE AND
REQUIRES NO PERIODIC MAINTENANCE. RECOMMENDED WHERE A
SLIGHT SACRIFICE IN ACCURACY CAN BE TOLERATED.
A-10

Electronic copies of this user’s guide can be found at:
hp://www.kelleramerica.com/manuals-and-soware/manuals/Keller_America_Users_Guide.pdf
BORN SWISS · MADE AMERICAN · KELLERAMERICA.COM