Code Name Rang Factory
Default
Description
G. AL Alarm parameter set
AL - 1 Alarm 1 -1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 / GW636) 1000
(2)
ALT1 Alarm 1 type I, LO I
ALY1 Alarm 1 action error 0 ~ 9999 10
ALN1 Alarm 1 start delay time 0.0 ~ 599.9s 0.0s
ALF1 Alarm 1 close delay time 0.0 ~ 599.9s 0.0s
AL - 2 Alarm 2 -1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 GW636) 2000
ALT2 Alarm 2 type I, LO I
ALY2 Alarm 2 action error 0 ~ 9999 10
ALN2 Alarm 2 start delay time 0.0 ~ 599.9s 0.0s
ALF2 Alarm 2 close delay time 0.0 ~ 599.9s 0.0s
G. PV Measurement parameters
PVDU Time unit selection OFF, MMSS (GW621 / GW626)
OFF, MMSS (GW631 / GW636) OFF
OFF: display is in seconds
MMSS: minutes and seconds
MMSS: hours, minutes and
seconds (3)
A, D Ratio (multiplication) -1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 / GW636) 1The input value can be converted
and displayed as the required
unit value by setting the ratio (4)
B, E Ratio factor 1 ~ 9999 (GW621 / GW626)
1 ~ 999999 (GW631 / GW636) 1
C Initial counter value -1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 / GW636) 0Make the measurement start
with the desired value
DP Point position 0 ~ 3 (GW621 / GW626)
0 ~ 5 (GW631 / GW636) 0
The position of the decimal point
of the measured value and its
associated parameters (5)
G. PV Measurement parameters
FILT Digital filter coefficient 0 ~ 9 0 As function size of digital filter
is larger more powerful it is (6)
ATZ1 IN-1 Automatic reset time 0 ~ 9999s 2s When there is no pulse input
during this time the value is
forced to be 0.
ATZ2 IN-2 Automatic reset time 0 ~ 9999s 2s
MDLY Measure delay time with
power on 0.1 ~ 99.9s 0.1s Set the appropriate time to wait
for the input signal
MEMO Power out storage ON, OFF OFF
ON: remember the
measurements taken before the
power outage
OFF: power off no record
G. TST Test parameter set
TEST Output test -1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 / GW636) 0The key operation simulation of
measurement value check