QC2002/QC2008
Fire Alarm Control Panel
Operating Manual

2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
CONTENTS :
System Characteristics................................................................1
Indicators and Switches Description .......................................... 2
Wiring Diagram Description and Location of Fuse .................... 4
Trouble Shooting ....................................................................... 5
Housing Specications............................................................... 6
Main Specications.................................................................... 7

1
2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
System Characteristics :
- Alarm verication up to 5 seconds for real re conrmation
and avoid false alarm from environment interference.
- Zone test mode to perform alarm and fault functional test.
- Fault indications for wire disconnection, AC power
- QC2002 could up to 08 zones, QC1802 ups to 30 zones.

2
1
Zone Fire
Zone Indicator note
Zone Fault
FIRE indicator
AC Power LED
Standby Power LED
General Fault LED
Switch On LED
Switch Reset on LED
Switch Bell on LED
Switch Buzzer on LED
Evacuate Emergency Switch
Reset Switch
Bell Silence Switch
Buzzer Silence Switch
Switch Evacuate on LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
23
4
5
67
8910 11
2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
Indicators And Switches Description :
FIRE ALARM CONTROL PANEL
AC Power On
Standby
Power
FIRE
Switch
On
General
Fault
RESET
R
BELL
SILENCE
BUZZER
SILENCE
EVA
SW BUZZER
SW BELL
SW RESET
EVACUATE
1
23
4
5
6
78
910 11 12
13 14 15 16

3
Zone Fire: Steady light ON means Fire status, light ON means.
Zone Indicator note: To show the name of covered area.
Zone Fault: Light ON means that circuit has trouble.
FIRE indicator: When the panel has received a fire signal,
the LED will light ON.
AC Power LED: Light ON means panel working voltage is normal.
Standby Power LED: Light ON means panel working voltage
is supplied by battery only
General Fault LED: Check for comms fault at all
Switch On LED: indicates it is under mode.
Switch Reset on LED: indicates it is under reset mode.
Switch Bell on LED: indicates it is under Bell Silence mode.
Switch Buzzer on LED: indicates it is under Buzzer Silence mode.
Evacuate Emergency Switch: When press switch once,
Led ON and on Bell, Buzzer
Reset Switch: Pressing this switch resets the panel.
Bell Silence Switch: When press switch once,
LED ON and disable the sounder
Buzzer Silence Switch: When press switch once,
Led ON and disable the buzzer
Switch Evacuate on LED: indicates it is under evacuate mode.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
Indicators And Switches Description :

4
2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
Wiring Diagram Description
Power Module
Alarm Output
+Z1-
+Z1-
AUX
AUX
- +
- + - + - +
- + - +
Bell 1
Bell 1
Bell 2
Bell 2
C NO NC
-Z2+
-Z2+
+Z3-
+Z3-
-Z4+
-Z4+ C NO NC
Location of Fuse
F1
F3
F2
Load Power (RES AUX)
Sounder
Battery Power
10kΩ
Zone Module
To Output Device

5
Trouble Symptom
Solution and Suggestion
Zone Fault LED ON
a. Check the panel if there is any non-connected zone and
EOL resistor.
Zone Fire LED ON
a. Disconnect the wire of faulty zone and measure the
faulty zone resistance, normally it should read 10KΩ.
b. Disconnect the faulty zone wire and then reset the
panel, replaced by 10KΩ and x the trouble before
reconnect the wire
AC Power LED OFF
Check the input power and fuse if they are comply to the
specication.
Standby Power LED ON
Check the input power and fuse if they are comply to the
specication.
General Fault LED ON
If only a general is indicated on the main panel and none
of the above
conrming trouble indicators are on, then check the
following for possible fault:
b. Disconnect the wire of faulty zone and replaced with
10KΩ, the fault signal should disappea.
c. If above steps released fault means the panel is normal,
please check the external wiring before connect
back to panel.
d. Use vom-meter to measure the faulty zone resistance,
normally it should read 10KΩ.
2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
Trouble Shooting

W
Zones Height/mm
W
idth/mm Depth/mm
Remark
4L
6L
8L
QC2002
100
100
100
100
240
240
240
240
300
300
300
300
2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
3
4
5
67
8910 11
FIRE ALARM CONTROL PANEL
AC Power On
Standby
Power
FIRE
Switch
On
General
Fault
RESET
R
BELL
SILENCE
BUZZER
SILENCE
EVA
SW BUZZER
SW BELL
SW RESET
EVACUATE
6
Housing Specications
D
H

2012 Ver.1 Khai An Technology Development Trading Company Limited
www.khaian.vn
QC2002/QC2008
7
Main Specications
Description
Power
Battery Capacity
Charging voltage & current
Loop voltage & current
External resistance
# of detector connected (Heat)
# of detector connected (Smoke)
# of fire indicating lamp connected
# of bell connected
Relay output
End of line resistor
Housing
220 VAC 50/60Hz (Others also available)
24 VDC/2.4A
28 VDC 100mA~400mA
24 VDC; short circuit under 5V
Max. 50Ω
Mechanical – up to design
Electronic – max. 30 per zone
Max. 30 per zone
# of zone x 1.5
# of zone x 1.5
Contact rating (24 VDC 3A)
10KΩ (One for each zone)
1.2 m/m steel plate

2012 Ver.1 Khai An Technology Development Trading Company Limited