manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Kidde
  6. •
  7. Fire Alarm
  8. •
  9. Kidde FX-270 Assembly instructions

Kidde FX-270 Assembly instructions

© 2020 Carrier 1 / 2 P/N 3101089-EN • REV 007 • ISS 21OCT20
FX-270 Single Action Pull
Station Installation Sheet
Operation
This FX-270 Single Action Pull Station combines a single action pull
station with a single input analog addressable mini module mounted on
the back of the unit. The pull station requires a single action
(i.e., pulling the handle) to initiate an alarm.
The device address is set using the two rotary switches located on the
back of the mini module. One device address is required.
The mini module is configured for alarm latching operation. When the
handle is pulled, an alarm signal is sent to the control panel and the
alarm condition is latched at the pull station. The pull station must be
manually reset prior to resetting the panel.
LEDs
The FX-270 provides two status LEDs. The LEDs are visible from the
back of the FX-270.
Figure 1: LED location
(1) Red LED: Alarm/active
(2) Green LED: Normal
Installation
Install and wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
WARNING: This pull station does not operate without electrical power.
As fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
Note: The pull station is shipped from the factory complete with a
single input mini module attached. The module contains no
user-serviceable parts and should not be disassembled.
To install the pull station:
1. To meet the Americans with Disabilities Act (ADA), mount the
electrical box 48 inches max. from the floor and attach the pull
station using screws provided with the electrical box.
2. Set the module address. Refer to the panel technical reference
manual for a list of valid addresses.
Use a screwdriver to adjust the two rotary switches on the front of
the module. Set the TENS rotary switch (0 through 12) for the 10s
and 100s digit and the ONES rotary switch for the 0 through 9
digit. For example: device address 21, set the TENS rotary switch
to 2 and set the ONES rotary switch to 1 (see Figure 2).
3. Verify that all field wiring is free of opens, shorts, and ground faults
before connecting to the module terminals.
4. Make all wiring connections to the terminal block as discussed in
“Wiring” and shown in Figure 4.
5. Open the pull station by using a slotted screwdriver to twist the
cover release screw counterclockwise while pulling the cover away
from its backplate.
6. Mount the pull station in the electrical box.
7. If use of the glass rod is desired, pull the glass rod release lever
and install the glass rod through the mounting bracket on the front
of the pull station.
8. Set the toggle switch to the NORMAL position and snap the cover
into its locked position.
Figure 2: Module address
(1) Insert screwdriver here
Figure 3: Pull station installation
(1) Compatible electrical box
(2)
Cover release screw
(3) Toggle switch
(4) Backplate
(5) Glass rod release lever
(6) Screw
Wiring
Caution: For system supervision, do not loop the circuit wires around
the terminals. Break the wire run at each terminal.
Wire the device as shown in Figure 4. Be sure to observe the polarity
of the wires.
For additional wiring information, refer to the documents listed on the
control panel label.
All wiring is power-limited and supervised.
firealarmresources.com
2 / 2 P/N 3101089-EN • REV 007 • ISS 21OCT20
Figure 4: Pull station wiring
(1) SLC in - from previous device or control panel
(2) SLC out - to next device or EOLR
Specifications
Voltage
IDC maximum
Communication line
maximum
10 VDC at 350 µA
20.6 V peak-to-peak
Current
Standby
Activated
350 µA
500 µA
Wire size
12 to 18 AWG (0.75 to 2.5 mm²)
Compatible electrical boxes
North American 2-1/2 in. (64 mm)
deep single gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep box with single gang
mud ring
Special order surface mount
boxes
27193-10 - Cream enamel finish
27193-11 - Red enamel finish
Replacement glass rods
USA, P/N 270-GLR (pkg. 20 rods)
CAN, P/N 27165 (pkg. 12 rods)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing at
90°F (32°C)
Storage temperature range
–4 to 140°F (–20 to 60°C)
Regulatory information
Environmental
class
UL: Indoor dry
North American
standards
UL 38, CAN/ULC-S528
Contact information
For contact information, see www.kidde-esfire.com.
firealarmresources.com

Other Kidde Fire Alarm manuals

Kidde Gemini II User manual

Kidde

Kidde Gemini II User manual

Kidde Genesis EG1 Series Assembly instructions

Kidde

Kidde Genesis EG1 Series Assembly instructions

Kidde DM3000E Assembly instructions

Kidde

Kidde DM3000E Assembly instructions

Kidde VM-1 Product manual

Kidde

Kidde VM-1 Product manual

Kidde PE9UK User manual

Kidde

Kidde PE9UK User manual

Kidde FX-64 Product manual

Kidde

Kidde FX-64 Product manual

Kidde Scorpio CPD 7051 Series Instruction manual

Kidde

Kidde Scorpio CPD 7051 Series Instruction manual

Kidde VS Series Product manual

Kidde

Kidde VS Series Product manual

Kidde FX-278 Assembly instructions

Kidde

Kidde FX-278 Assembly instructions

Kidde GSA-M278 Assembly instructions

Kidde

Kidde GSA-M278 Assembly instructions

Popular Fire Alarm manuals by other brands

System Sensor ECO1002ABLINK Installation and maintenance instructions

System Sensor

System Sensor ECO1002ABLINK Installation and maintenance instructions

AVOTEC STAR F24/CPD Technical manual

AVOTEC

AVOTEC STAR F24/CPD Technical manual

Siemens Synova FC330A operating manual

Siemens

Siemens Synova FC330A operating manual

Honeywell Notifier LCD2-80 instruction manual

Honeywell

Honeywell Notifier LCD2-80 instruction manual

Fire-Lite Alarms LCD-40 Series manual

Fire-Lite Alarms

Fire-Lite Alarms LCD-40 Series manual

Ziton ZP700 Series Installation sheet

Ziton

Ziton ZP700 Series Installation sheet

E2S GNExCP7-PB-S instruction manual

E2S

E2S GNExCP7-PB-S instruction manual

Fire-Lite C304(A installation instructions

Fire-Lite

Fire-Lite C304(A installation instructions

Fire Pro Sigma XT Installation and operation manual

Fire Pro

Fire Pro Sigma XT Installation and operation manual

Dellcos FM-CO user manual

Dellcos

Dellcos FM-CO user manual

Simplex Contact Closure DACT Installation and programming instructions

Simplex

Simplex Contact Closure DACT Installation and programming instructions

Simplex SafeLINC 4100 Operator's manual

Simplex

Simplex SafeLINC 4100 Operator's manual

Pertronic SYSTEM SENSOR FAAST LT Series Installation and maintenance guide

Pertronic

Pertronic SYSTEM SENSOR FAAST LT Series Installation and maintenance guide

Advanced Mx Pro5 Mx-5100 manual

Advanced

Advanced Mx Pro5 Mx-5100 manual

KILLARK XAL-53 Installation, operation and maintanance

KILLARK

KILLARK XAL-53 Installation, operation and maintanance

Autocall 4007ES Operator's manual

Autocall

Autocall 4007ES Operator's manual

Cooper Notification RSS-24MCC installation instructions

Cooper Notification

Cooper Notification RSS-24MCC installation instructions

Ziton ZR432-2P Installation sheet

Ziton

Ziton ZR432-2P Installation sheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.