PV and Mains hybrid charging: PV charging is a priority, and when
the PV energy is insufficient, the Mains charging supplements.
When the PV energy is sufficient, the Mains charging stops.
NOTE:
Only when the Mains bypass output is loaded, the PV charging and
the mains charging can work at the same time. When the inverter
is in use, only the PV charging can be started.
06 Charge source priority
07 Max charger current
80A default
Max charger current (AC charger + PV charger)
Setting range: 0~80A
08 Battery Type
[08]
Use User-defined; all battery parameters can be set.
09 Battery Absorption charge voltage
56.4V
10 Battery Absorption charge time
5 Minutes
11 Battery float charge voltage
53.6V
12 Battery over discharge voltage
48V default
13 Battery over discharge delay time
5 SEC default
14 Battery under voltage alarm
50.4V
15 Battery discharge limit voltage
50.0V
16 Battery equalization enable
DIS Equalizing charge is disabled