•Before operating the Uniti be sure to read this Setup Guide and the full users manual..
•Even though the inverter is programed before shipping it is critical to program your inverter or charge con-
troller's settings for correct operation, improper programming of your system equipment may invalidate
your battery warranty and could degrade system performance.
Unit Eco Freedom Lite
Basic Inverter Settings.
01 Output Source Priority
SOL
PV priority mode, switching to the Mains when the PV fails or the battery is
lower than the set value of the parameter.
02 Output Frequency
60.0 Hz
03 AC Input Voltage Range
APL
Wide mains input voltage range of 230V Machine: 90~280V
Mains input voltage range of 230V machine: 90~280V
04 Battery Power to Utility Setpoint
50.8V
When the parameter [01]=SOL/SBU, the battery voltage is higher than set
value, and the output is switched from mains to the inverter. Setting range:
44V~52V
05 Utility to Battery Power Setpoint
56.0V
When the parameter [01]=SOL/SBU, the battery voltage is higher than set
value, and the output is switched from mains to the inverter. Setting range:
48V~60V