  9. KIMO RHVAC Controls FrigoPack E FU+/12 User manual

KIMO RHVAC Controls FrigoPack E FU+/12 User manual

0. FrigoPack®EFU+/12 Connections
Top:
Diagram of control connections of
FrigoPack®EFU+/12
Bottom:
Terminal designations of
FrigoPack®EFU+/12 and
base module BM-1
VsC1: Variable speed Compressor 1
FsC2: Fixed speed Compressor 2
FrigoPack®EFU+/12 Quick-Start Guide
for classic control
Refrigeration Inverters with integrated
pressure control (FrigoSoft 1.7)
Warning: This is an abbreviated and customized version with recommendations for a rst setup of this product.
Please refer to the document "Planning Guide FrigoPack®EFU+/12“ for detailed information.
www.frigokimo.com
- 1 -FS 1.7
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
Ensure that all recommendations for compliance to mounting, electrical safety, EMC and UL regulations have
been adhered to.
1.1 Pressure transmitters
Warning: Only use approved pressure transmitters!
This refrigeration application is preset for use with the following Huba Control pressure transducers:
1. Basic information on rst set-up
Low Pressure pe: -0.5 … 7.0 bar
A REFR-P-TRANSD-LP7N+PL
High Pressure pc: 0 … 30 bar
A REFR-P-TRANSD-HP30N+PL
For alternative pressure transmitters and pressure ranges refer to Parameter SP0, p. 6 of Planning Guide.
1.2 Recommendations
•It is important to ensure that an interlocked contactor is fitted between the Refrigeration Inverter and the
compressor if a parallel bypass connection is used.
•In particular ensure that two isolated contacts of a relay are connected to the Safe-Torque-Off inputs of
FrigoPack®FU+ Refrigeration Inverter: STO-A (Terminal X10:1) / STO-B (Terminal X10.3).
• Remove start command (cable to terminal X13:2)
• Connect main power supply
• Verify that the blue LED for suction pressure lights on module BM-1. If not, then check if the wiring of the
pressure transmitter is correct.
• If a discharge pressure transmitter is used, then verify that the red LED lights on module BM-1. If not, then
check if the wiring of the pressure transmitter is correct.
• Measure the pressures with a refrigeration pressure gauge. Verify that the pressures indicated in menu
OPERATION at parameter 03: pe_RACK_pc agree with these external measurements.
1.3 Keypad functionality
1.4 Menus - Selection of user level for rst set-up
To start commissioning, the user level TECHNICIAN must be enabled. The steps shown below have to be
followed. Press key "Back" several times to access the menu "View Level".
Password for user level TECHNICIAN: 8670. The level is then activated for 10 minutes.
OK
OK OK
OK
OK
PASSWORD:
8670
Back Back
Start screen Menu levels
Key "Back"
● Navigates to previous level
● Press multiple times to enter Operator Menu
● Aborts the edit mode
Key "OK"
● Displays the next menu level
● Changes to parameter entry mode
● Accepts value entered
"Green" key
Green light on
● Compressor running
● When flashing with "Red" key: Frequency Inverter
in Configuration Mode
Key "Red"
● Resets any trip
Red light on
● Compressor stopped
● When flashing with "Green" key: Frequency Inverter
in Configuration Mode
Keys "Left" and "Right"
● Displays previous menu level
● Selects the digit to be changed
● Selects next/previous set of parameters, compressors, etc.
Keys "Up" and "Down"
● Moves up or down through selected menu level
● Increments / decrements the value of the displayed
parameter by "1"
User level
- 2 - www.frigokimo.com
FS 1.7
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
2.1 Selection of refrigerant and Variable-speed Compressor (VsC)
For setting up this inverter it is rst of all necessary to select the refrigerant and Variable-speed Compressor
(VsC1) used. Compressor selection is made in several steps (manufacturer, type (e.g. semihermetic piston
comp.), number of cylinders, motor connection, compressor ID).
2. First set-up
After pressing the green key for 2 s menu "First Setup" can be left with the "Back" key.
Menu First Setup:
Selection of refrigerant
and Variable-speed
Compressor (VsC)
Start screen
Line 1: FU+ Features
Line 2: INenn, UNenn
Line 3: Firmware version
Line 4: IP address
(optional)
Finish setup
Selection of refrigerant
Next
refrigerant
Previous
refrigerant
Selection of
manufacturer
Next
manufacturer
Previous
manufacturer
Selection of type
Next
type
Previous
type
Select number
of cylinders
More
cylinders
Less
cylinders
Selection of
motor connection
Next
connection
Previous
connection
Selection of compressor
Next
compressor
Previous
compressor
Press green key for 2 s
to conrm setup.
Access to
SD memory card
Currently active:
"Selection disabled"
- 3 - www.frigokimo.com
FS 1.7
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
Parameter 80: 8 0 00001 1
VsC1 FsC2 FsC3 FsC4 FsC5 FsC6 FsC7
Press key „OK“ to enter the parameter input window. Skip to next digit with arrow keys „Left“ and „Right“ . Change
value of digit with arrow keys „Up“ and „Down“ . Every digit „1“ corresponds to a FsC in the rack system, as
shown below. The value of parameter 80 entered has to be conrmed with key „OK“.
2.3 Entering Setpoints
Select menu "REFRIGERATION SETUP" for entering setpoints. Use keys as described in 2.2 for setting the
relevant parameters.
Example: In a rack system with one Variable-speed Compressor (VsC1) and two Fixed-speed Compressors
(FsC2 & FsC3) parameter 80 has to be set to: 80000011
Connect start command (cable to terminal X13:2)
to start the system!
Please contact our
applications team for any
questions in planning or
commissioning under
[email protected]
or
tel +49 (0) 9131 – 934570
KIMO RHVAC Controls GmbH | Hüttendorfer Weg 60 | D - 90768 Fürth, Germany
01117.144-172/08
2.2 Setting of number of xed-speed compressors (FsC) in the rack system
The number of xed-speed compressors (FsCs) has to be set in the next step. (If there is only one compressor,
please skip to 2.3). Go to menu COMPRESSOR SETUP.(You may also check VsC settings in this menu.)
Go to parameter 80:FsC PRIORITY CNTRL for setting the number of xed-speed compressors.
www.frigokimo.com

Popular Inverter manuals by other brands

R3Di RS3600 user manual

R3Di

R3Di RS3600 user manual

Zeon Tech Dynamo iPower manual

Zeon Tech

Zeon Tech Dynamo iPower manual

Kaco Powador operating instructions

Kaco

Kaco Powador operating instructions

Hitachi SJ100 Series quick start guide

Hitachi

Hitachi SJ100 Series quick start guide

Alena Energy BySolarPower BSP 5S user manual

Alena Energy

Alena Energy BySolarPower BSP 5S user manual

Thermasol PROI Seres Installation & operation manual

Thermasol

Thermasol PROI Seres Installation & operation manual

SG GROUP 3100W instructions

SG GROUP

SG GROUP 3100W instructions

Growatt MOD TL3-XH Series Installation & operation manual

Growatt

Growatt MOD TL3-XH Series Installation & operation manual

TECO MV510 Series Maintenance manual

TECO

TECO MV510 Series Maintenance manual

Delios DLS 450C instruction manual

Delios

Delios DLS 450C instruction manual

Coopers of Stortford 8793 instructions

Coopers of Stortford

Coopers of Stortford 8793 instructions

Heiko JZ050-A1 Service manual

Heiko

Heiko JZ050-A1 Service manual

GAI-Tronics TS959 manual

GAI-Tronics

GAI-Tronics TS959 manual

HTP Invertig 131 DC/HF owner's manual

HTP

HTP Invertig 131 DC/HF owner's manual

Sungrow SG1250UD installation manual

Sungrow

Sungrow SG1250UD installation manual

Fosera EVO Series user manual

Fosera

Fosera EVO Series user manual

HP 16520a Reference manual

HP

HP 16520a Reference manual

A2Z Ozone Systems Aquatic 2 operating manual

A2Z Ozone Systems

A2Z Ozone Systems Aquatic 2 operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.