KIMO RHVAC Controls FrigoPack E FU+/12 User manual

Popular Inverter manuals by other brands

Omnik New Energy Omniksol-1.5k-TL user manual

Omnik New Energy

Omnik New Energy Omniksol-1.5k-TL user manual

Agilent Technologies 33250A user guide

Agilent Technologies

Agilent Technologies 33250A user guide

4-noks ZR-SWITCH-RC instruction manual

4-noks

4-noks ZR-SWITCH-RC instruction manual

V&T V5 Series user manual

V&T

V&T V5 Series user manual

Hon Turing HT-T-S1000-12 introduction

Hon Turing

Hon Turing HT-T-S1000-12 introduction

Metabo E 140 SP Plus Original operating instructions

Metabo

Metabo E 140 SP Plus Original operating instructions

BARRON EXITRONIX Tucson Micro Series installation instructions

BARRON

BARRON EXITRONIX Tucson Micro Series installation instructions

Baumer HUBNER TDP 0,2 Series Mounting and operating instructions

Baumer

Baumer HUBNER TDP 0,2 Series Mounting and operating instructions

electroil ITTPD11W-RS-BC Operation and Maintenance Handbook

electroil

electroil ITTPD11W-RS-BC Operation and Maintenance Handbook

Silicon Solar TPS555-1230 instruction manual

Silicon Solar

Silicon Solar TPS555-1230 instruction manual

Mission Critical Xantrex Freedom SW-RVC owner's guide

Mission Critical

Mission Critical Xantrex Freedom SW-RVC owner's guide

HP 3312A Operating and service manual

HP

HP 3312A Operating and service manual

Hoymiles HM-500T user manual

Hoymiles

Hoymiles HM-500T user manual

Nitecore SPM10 user manual

Nitecore

Nitecore SPM10 user manual

AEG Protect PV installation manual

AEG

AEG Protect PV installation manual

On Board TruePower Plus 1200MS owner's manual

On Board

On Board TruePower Plus 1200MS owner's manual

Plugreen PGM-200P-230 Installation and operation manual

Plugreen

Plugreen PGM-200P-230 Installation and operation manual

Fourgroup Easy use and Programming Handbook

Fourgroup

Fourgroup Easy use and Programming Handbook

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

0. FrigoPack®EFU+/12 Connections
Top:
Diagram of control connections of
FrigoPack®EFU+/12
Bottom:
Terminal designations of
FrigoPack®EFU+/12 and
base module BM-1
VsC1: Variable speed Compressor 1
FsC2: Fixed speed Compressor 2
FrigoPack®EFU+/12 Quick-Start Guide
for classic control
Refrigeration Inverters with integrated
pressure control (FrigoSoft 1.7)
Warning: This is an abbreviated and customized version with recommendations for a rst setup of this product.
Please refer to the document "Planning Guide FrigoPack®EFU+/12“ for detailed information.
www.frigokimo.com
- 1 -FS 1.7
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
Ensure that all recommendations for compliance to mounting, electrical safety, EMC and UL regulations have
been adhered to.
1.1 Pressure transmitters
Warning: Only use approved pressure transmitters!
This refrigeration application is preset for use with the following Huba Control pressure transducers:
1. Basic information on rst set-up
Low Pressure pe: -0.5 … 7.0 bar
A REFR-P-TRANSD-LP7N+PL
High Pressure pc: 0 … 30 bar
A REFR-P-TRANSD-HP30N+PL
For alternative pressure transmitters and pressure ranges refer to Parameter SP0, p. 6 of Planning Guide.
1.2 Recommendations
•It is important to ensure that an interlocked contactor is fitted between the Refrigeration Inverter and the
compressor if a parallel bypass connection is used.
•In particular ensure that two isolated contacts of a relay are connected to the Safe-Torque-Off inputs of
FrigoPack®FU+ Refrigeration Inverter: STO-A (Terminal X10:1) / STO-B (Terminal X10.3).
• Remove start command (cable to terminal X13:2)
• Connect main power supply
• Verify that the blue LED for suction pressure lights on module BM-1. If not, then check if the wiring of the
pressure transmitter is correct.
• If a discharge pressure transmitter is used, then verify that the red LED lights on module BM-1. If not, then
check if the wiring of the pressure transmitter is correct.
• Measure the pressures with a refrigeration pressure gauge. Verify that the pressures indicated in menu
OPERATION at parameter 03: pe_RACK_pc agree with these external measurements.
1.3 Keypad functionality
1.4 Menus - Selection of user level for rst set-up
To start commissioning, the user level TECHNICIAN must be enabled. The steps shown below have to be
followed. Press key "Back" several times to access the menu "View Level".
Password for user level TECHNICIAN: 8670. The level is then activated for 10 minutes.
OK
OK OK
OK
OK
PASSWORD:
8670
Back Back
Start screen Menu levels
Key "Back"
● Navigates to previous level
● Press multiple times to enter Operator Menu
● Aborts the edit mode
Key "OK"
● Displays the next menu level
● Changes to parameter entry mode
● Accepts value entered
"Green" key
Green light on
● Compressor running
● When flashing with "Red" key: Frequency Inverter
in Configuration Mode
Key "Red"
● Resets any trip
Red light on
● Compressor stopped
● When flashing with "Green" key: Frequency Inverter
in Configuration Mode
Keys "Left" and "Right"
● Displays previous menu level
● Selects the digit to be changed
● Selects next/previous set of parameters, compressors, etc.
Keys "Up" and "Down"
● Moves up or down through selected menu level
● Increments / decrements the value of the displayed
parameter by "1"
User level
- 2 - www.frigokimo.com
FS 1.7
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
2.1 Selection of refrigerant and Variable-speed Compressor (VsC)
For setting up this inverter it is rst of all necessary to select the refrigerant and Variable-speed Compressor
(VsC1) used. Compressor selection is made in several steps (manufacturer, type (e.g. semihermetic piston
comp.), number of cylinders, motor connection, compressor ID).
2. First set-up
After pressing the green key for 2 s menu "First Setup" can be left with the "Back" key.
Menu First Setup:
Selection of refrigerant
and Variable-speed
Compressor (VsC)
Start screen
Line 1: FU+ Features
Line 2: INenn, UNenn
Line 3: Firmware version
Line 4: IP address
(optional)
Finish setup
Selection of refrigerant
Next
refrigerant
Previous
refrigerant
Selection of
manufacturer
Next
manufacturer
Previous
manufacturer
Selection of type
Next
type
Previous
type
Select number
of cylinders
More
cylinders
Less
cylinders
Selection of
motor connection
Next
connection
Previous
connection
Selection of compressor
Next
compressor
Previous
compressor
Press green key for 2 s
to conrm setup.
Access to
SD memory card
Currently active:
"Selection disabled"
- 3 - www.frigokimo.com
FS 1.7
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
SD-Card:Data__Select__
<0:Selection_disbld
SD-Card:Data__Read____
<NORMAL_OPERATION>
SD-Card:Data__Select__
<3:VsC_Type_______
SD-Card:Data__Read___
<32:Recip_Semihrmtc
SD-Card:Data__Select__
<4:VsC_Cylinders__
SD-Card:Data__Read___
<42:2 cylinders____
SD-Card:Data__Select__
<5:Supply_Voltage__
SD-Card:Data__Read____
<53:50_Hz_400_V____
OPERATION___________
REFRIGERATION SETUP_
COMPRESSOR SETUP _
SPECIAL ADJUSTMENTS_
Parameter 80: 8 0 00001 1
VsC1 FsC2 FsC3 FsC4 FsC5 FsC6 FsC7
Press key „OK“ to enter the parameter input window. Skip to next digit with arrow keys „Left“ and „Right“ . Change
value of digit with arrow keys „Up“ and „Down“ . Every digit „1“ corresponds to a FsC in the rack system, as
shown below. The value of parameter 80 entered has to be conrmed with key „OK“.
2.3 Entering Setpoints
Select menu "REFRIGERATION SETUP" for entering setpoints. Use keys as described in 2.2 for setting the
relevant parameters.
Example: In a rack system with one Variable-speed Compressor (VsC1) and two Fixed-speed Compressors
(FsC2 & FsC3) parameter 80 has to be set to: 80000011
Connect start command (cable to terminal X13:2)
to start the system!
Please contact our
applications team for any
questions in planning or
commissioning under
[email protected]
or
tel +49 (0) 9131 – 934570
KIMO RHVAC Controls GmbH | Hüttendorfer Weg 60 | D - 90768 Fürth, Germany
01117.144-172/08
2.2 Setting of number of xed-speed compressors (FsC) in the rack system
The number of xed-speed compressors (FsCs) has to be set in the next step. (If there is only one compressor,
please skip to 2.3). Go to menu COMPRESSOR SETUP.(You may also check VsC settings in this menu.)
Go to parameter 80:FsC PRIORITY CNTRL for setting the number of xed-speed compressors.
www.frigokimo.com