Kimray GEN 3 Owner's manual

PNEUMATIC LEVEL CONTROLLER
GEN 3

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
All Rights Reserved.
All contents of this publication including illustrations are believed to be re-
liable. And while efforts have been made to ensure their accuracy, they
are not to be construed as warranties for guarantees, express or implied,
regarding Kimray products or services described herein or their use or ap-
plication. All sales are governed by our terms and conditions, which are
available on request.
Kimray reserves the right to modify or improve the designs or specications
of such products at any time without prior notice.
©2018 Kimray Inc.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
3
www.kimray.com
Contents
INTRODUCTION
A1 Scope.................................................................4
A2 Description.........................................................4
A3Denitions ..........................................................4
A4 Tools and Equipment .........................................4
CONFIGURATION
Mount Orientation ..................................................5
Displacer Orientation.............................................5
Pilot Action - Direct / Indirect Switch ..................5
Left hand / right hand conversion ........................5
INSTALLATION
Install Onto Vessel .................................................6
Connections ...........................................................7
Snap and throttle mode switch ............................7
OPERATION
Start up ...................................................................8
Calibration ..............................................................8
Span adjustment ...................................................8
MAINTENANCE
Parafncleanoutport ..........................................9
Repair kit replacements ........................................9
Other replacements ...............................................9
Pilot Assembly......................................................10
Mount Assembly...................................................12
Spring Assembly ..................................................14
Filter.......................................................................14
TROUBLESHOOTING
Troubleshooting ...................................................16
If you have any questions about this manual, contact
your Kimray applications support group before
proceeding.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
4
CAUTION:
Whenordered,thecontrollerconguration&construction
materialswereselectedtomeetspecicpressure,
temperature,&uidconditions.Donotsubjectthe
controllertoanyotherconditionswithoutrstcontacting
theKimrayInc,salesofceorasales/applications
representative.
A4 Tools Needed for Installation,
Conversions & Repair
This Kimray controller DOES NOT require special tools
fordisassembly,inspection&assembly.
These are the standard tools required:
1. PipeWrenchorotherWrenchtot2-1/2"Flats.
2. 7/8"wrenchforlower1/2"NPTs
3. 9/16"wrenchforGauges-or-AdjustableWrench
4. 9/16"socketforthemountscrews
5. 3/8"SocketforPilotCartridgeCaps
6. 1/4"hexkeyfor1/4"NPTplugs
7. 1/8"HexKey(includedwithunit)seebelow.
8. Thread tape
9. Anyequipmentneededfortubingconnections
TheGen3includesa1/8"hexkeywhichwilltthepilot
&leverfasteners.
Forconvenience,thehexkeycanbestoredinthe
locationshownbelow.
1/8" Hex key
CAUTION:
Theinstructionsprovidedhereinshouldbecompletely
reviewed&understoodbeforeinstalling,operatingor
repairingthisequipment.AllCAUTION&WARNING
notesmustbestrictlyobservedtopreventinjuryto
personnelordamagetoequipment.
A1 Scope
ThisdocumentcontainsinformationfortheGen3Liquid
LevelController&includesdetailedinstallation,operation
&repair/maintenanceinformationfortheproduct.
A2 Description
TheGen3LiquidLevelControllerisdesignedforusein
single-phase&interfaceliquidcontrolapplications.The
pilotiscapableofbothSnapmode(on/off)&Throttle
mode(modulating).Pneumaticoutputcanbesetto
operateasDirectActingorIndirectActing.Themounting
bodycanbeippedtoeitherLeftHandorRightHand
Mount.Thedisplacermaybeassembledinverticalor
horizontalorientation.Changingbetweentheseoptions
doesnotrequireadditionalcomponentsnorswapping
out pilots.
A3Denitions
Snap Mode:On/Off,discreteoutput.Liquidlevelranges
fromhighpointtolowpoint,largespan.
Throttle Mode:Modulating,proportionaloutput.Holds
consistent level, with very small span.
DirectActing:ForFailClosed(FC)akaPressure-to-Open
(PO)Valve.Pilotprovidesmaximumoutputwhenliquid
level reaches set point at top of span.
IndirectActing:ForFailOpen(FO)akaPressure-to-
Close(PC)Valve.Pilotprovidesmaximumoutputwhen
liquidlevelreachesbottomofspan.
LeftHandMount:Withfrontofcontrollerfacingoperator,
unitismountedonleftsideofvessel.ForBackMount
applications, use this mount option due to the location of
the cover latch.
RightHandMount:Withfrontofcontrollerfacing
operator,unitismountedonrightsideofvessel.
Set Point: The liquid level at which the controller opens
the valve. In Snap Mode, this is at the top of the span. In
Throttle Mode, the liquid level should stay consistent at
the set point.
Span:Distancebetweenthehighest&lowestliquidlevel
duringoperation.ThiscanbesetwiththeSensitivity
Fulcrum.See“SpanAdjustment”below.
Introduction

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
5
www.kimray.com
Kimrayreservestherighttomodifyorimprovethedesignsorspecicationsofsuchproductsatanytimewithoutnotice.
Conguration
Left Hand / Right Hand Conversion
1. RemoveSpringAdjustmentAssembly(F)and1/2"
NPTplug(E).
2. RemovePilotLeverAssembly(A).
3. LoosenSetScrew(D)atbottomofTorqueLever(B)
andslideTorqueLever(B)offshaft.
4. RemoveCapScrews(C)androtatetheMount(G)
180degrees.
5. ReinstallCapScrews(C)withthreadlocker,replace
TorqueLever(B),andtightenSetScrew(D).
6.ReassembleSpringAdjustmentAssembly(F)on
same side as displacer.
7. Reinstall1/2”NPTplug(E)ontheotherside.
8.ReinstallPilotLeverAssembly(A)onthesideshown
inthePilotLeverLocationtable.-
Pilot Lever
Assembly
Torque
Lever
Cap Screw
Set Screw
1/2" NPT Plug
Cap Screw
Spring
Adjustment
Assembly
Mount
A
B
C
D
C
E
F
G
Mount Orientation
TheGen3canbeorderedineitherLeftHandorRight
Handmount,butifyouneedtochangetheorientation
beforeinstalling,see“LeftHandandRightHand
Conversion”
Left Hand Right Hand
Displacer Orientation
Assembledisplacerasshownbelowforeitherverticalor
horizontal orientation.
Usethreadlockerondisplacerarmthread.
Displacer Arm
Thread Locker
Displacer Arm
Thread Locker
Pilot Action - Direct / Indirect Switch
ToswitchbetweenDirectandIndirect,movePilotLever
fromonesidetotheotheraccordingtothePilotLever
Locationtablebelow.MovetheSensitivityKnobsothatit
isfacingoutwardtowardoperator.
Pilot Lever Location
PilotConguration Throttle Snap
Direct
(ForPressureOpen/
FailClosedValve)
Same side as
spring
Opposite side
ofspring
Indirect
(ForPressureClose/
FailOpenValve)
Opposite side
ofspring
Same side as
spring
Pilot Lever
Sensitivity Knob

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
6
Kimrayreservestherighttomodifyorimprovethedesignsorspecicationsofsuchproductsatanytimewithoutnotice.
Installation
NOTE:
Alwayscheckfastenertightnesspriortoinstallation,
testing,anduse,asfastenershavethepotentialto
loosen in transit. This is recommended to ensure your
safety and proper function of the unit.
*Kimrayassemblytorquemethodbelow*
Four Bolt
Four Bolt
1
1
2
2
3
3
4
4
Three Bolt
Three Bolt
2
2
3
3
1
1
Install Onto Vessel
WARNING:
Beforebeginninginstallation,Block&Bleedvalve.
Makesureallpressureisreleasedfromvessel,and
conrmnopressureremainsinsupplygas/instrument
airlines.DonotinstallinalocationwhereMaxAllowable
WorkingPressurecouldbeexceeded.Readandfollow
instructions.
NPTConnection:ApplyPTFEtapeorpipecompound
tothemalethreadsofthethreadedmount.Tighten
sufcientlytosealthethreadsusingawrenchontheats
ofthemountingpiece.
Donotuseawrenchonthealuminumenclosure/cover
totightentheconnection.Makesuretheenclosureis
alignedverticallywiththepilotontopwhennished.
FlangedConnection:Useasuitablegasketbetweenthe
mountandthevesselconnectionange.
NOTE:
WhenaSeatGasketisdisturbedduringdisassemblya
newGasketshouldbeinstalledduringre-assemblyto
ensurepropersealing.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
7
www.kimray.com
Connections
WARNING:Donotinstallortightenanyttings,
gauges,oranyotherconnectionswhilethereispressure
on the line.
Removeplasticplugsfrom1/4”NPTopenings.Use1/4”
or3/8”tubing(notprovided).
Throttle Mode:Connectsupplygaslterandpressure
gaugetoanyofthethreeportslabeled“T”andplugthe
remaining“T”port.Connectsupplylinetolter.Use“S”
portsforVent.
Snap Mode:Connectsupplygaslterandpressure
gaugetoanyofthethreeportslabeled“S”andplugthe
remaining“S”port.Connectsupplylinetolter.Use“T”
portsforVent.
Supply for
Snap Mode
Supply for
Throttle Mode
Installation
Vent:ConnectaVentLineorBreatherPlugtooneofthe
threeVentports,andinstallplugsinremainingtwoports.
Output:Connectpressuregaugetoeitherportlabeled
“OUT”,whereitiseasiestforoperatortosee.Connect
outputlinetoremaining“OUT”port.
CAUTION:Ensuresupplygasiscleananddry.
Vent for
Snap Mode
Vent for
Throttle Mode
Output
Snap and Throttle Mode Switch
Toswitchfromonemodetotheother,swapall“T”
(Throttle-toprow)portconnectionswith“S”(Snap-
bottomrow)portconnections(includingsupplygaslter)
andmovePilotLeverfromonesidetotheother.See
PilotLeverLocationtablebelow.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
8
Start-up
WARNING:
Verifyallpressureconnectionsaretightbefore
pressurizingthesystem.
WARNING:
Never stand directly in front of or over a controller when
the system is pressurized.
WARNING:
DonotexceedMaximumAllowableWorkingPressureor
maximuminstrumentsupplypressure.Never loosen or
tightenanyttingwhilethereispressureontheline.
Pressurize the system.Ifanyleaksaredetected,bleed
offpressureandaddress.Failuretotakethecontroller
out of service immediately may create a hazardous
condition.
Calibration
Calibratethecontroller’ssetpointwithnoliquidonthe
displacer.
Supply
Gauge Output
Gauge
Set Point
Adjustment
Knob
Throttle Mode:
DirectActing-FailClosed(akaPO)Valve:Withthe
outputat0psi,turnthesetpointadjustmentknob
counterclockwisetoproduceabout10psi.Next,turn
clockwiseuntiltheoutputreaches0psi.
IndirectActing-FailOpen(akaPC)Valve:Withthe
outputat0psi,turnthesetpointadjustmentknob
clockwiseuntilfulloutputpressureisproduced.
Operation
Snap Mode:
DirectActing-FailClosed(akaPO)valve:Withthe
outputat0psi,turnthesetpointadjustmentknob
counterclockwiseto“snapon”,producingthefulloutput
pressure.Thenturntheknobclockwiseuntiltheoutput
pressurereturnsto0psi.
IndirectActing-FailOpen(akaPC)valve:Atfull
outputpressure,turnthesetpointadjustmentknob
counterclockwiseto“snapoff”theoutputpressureto
0psi.Thenturntheknobclockwiseuntilfulloutput
pressure is reached.
Span Adjustment
Sensitivity Fulcrum
Throttle Mode:
Forthrottlemode,startwiththesensitivityfulcrumatthe
centerhashmarkofthepilotlever.Notethecurrentspan.
Ifspanistoolarge,movethesensitivityfulcruminward
oroutwardtoanotherhashmark.Ifresultingspanis
larger,movesensitivityfulcruminoppositedirectionand
note new span. If smaller, continue to move sensitivity
fulcrum further in the same direction until constant level
or minimum span is achieved.
Snap Mode:
Forsnapmode,startwiththesensitivityfulcrumatthe
innermosthashmark.Thisshouldyieldthesmallestspan.
Adjustthefulcrumoutwardasneeduntilthedesired
span is achieved.
Set Point Adjustment
RaiseSetPoint:TurntheSetPointAdjustmentKnob
clockwise
LowerSetPoint:TurntheSetPointAdjustmentKnob
counterclockwise

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
9
www.kimray.com
ParafnCleanoutPort
TheGen3isequippedwithanaccessporttogivethe
abilitytoinspectandcleanouttheareainsidetheMount,
withouthavingtoremovetheunitfromthevessel.
Thiscanhelpifthereareparafnsorothersolidsthat
buildupovertimeinsidetheMount,restrictingmovement
oftheDisplacerRod.
WARNING:Makesureallpressureisreleased
fromthevesselbeforelooseningthecleanoutportplug.
Repair Kit Replacements
Repairkitscontainallsealsandwearcomponents
recommendedtobereplacedduringscheduled
maintenanceintervalsfortheentireunit,including
Pilot,Well-Wetted,andAdjustmentSpringAssembly
Components.Thefollowingsectionsinstructhow
toreplacethesecomponents.Alistofrepairkit
componentscanbefoundinthekitsheetRK:F001.
Other Replacements
Ifanyothercomponentsthatwereinspectedneedtobe
replaced,usetheTechnicalSpecsdocument08:05.1to
determinewhichpartnumber(s)areneededandcontact
yourlocalKimrayauthorizedstoreordistributortoorder.
WARNING:
Aleakingcontroller is an indication that service is
required.Failuretotakecontroller out of service
immediately may cause a hazardous condition.
WARNING:
Beforebeginningrepair,Block&Bleedvalve.Makesure
allpressureisreleasedfromvessel,andconrmno
pressureremainsinsupplygas/instrumentairlines.
TolocateanauthorizedKimrayrepairfacilityortond
yourlocalKimrayauthorizedDistributorvisitKimray.com.
Whenconductingrepairs,onlyusegenuineKimrayrepair
kitsandreplacementparts.Repairkitsanddetailed
repairinstructions&videosareavailableatKimray.com
Performmaintenanceonaregularbasis.Aninitial
inspectionintervalof6monthsisrecommended.
Dependingontheserviceconditionsandtheconditionof
thecontroller,theinspectionintervalmaybedecreased
or increased.
Thepilotcanberepairedwithoutremovingthecontroller
fromthevesselaslongasthesupplyair/gaspressure
hasbeenbleddownandfullyreleased.
Maintenance

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
10
Maintenance - Pilot Assembly
Pilot - Disassembly
Step1–Remove3socketscrews(1/8"hexkey)holding
pilottoenclosure.Removepilotbypryingunderatsand
thenpullingpilotout.
Step2–Removeanddiscard4O-ringsaroundoutside
ofpilotcartridge.
Step3–Placeatsonlowerpilotcartridgeintoviseor
hold in place with wrench.
Step4–Unthreadandcarefullyremoveangedtoppilot
capto(3/8"socket).
Step5–Carefullyremoveupperdiaphragmassemblyto
avoiddamagingconicalspring.Ifdiaphragmisstuck,do
notprywithscrewdriver.Useplierstopulloutdiaphragm
assembly.
Toremovepilotplug,turnpilotassemblyoverandit
willfallout.Inspectpilotplugandseatsurfacesshown
forscratches,pitting,oranyotherpotentialleakpaths.
Cleanoffanydebris.
Step6–Holdingatsofpilotcartridgeinplace,unthread
andremovebottompilotcap(3/8"socket).
Step7-Removelowerdiaphragmassemblyandlower
spring.Ifdiaphragmisstuck,donotprywithscrewdriver.
Usepliersonstemofactuatortopulloutdiaphragm
assembly.
Step8-Cleanoutallcommunicationholes.
Pilot - Reassembly
Step1–Cleanpilotcartridgeandinstallpilotplug,small
diameterrst,intothesideofthecartridgewiththeupper
seat.
Step2–Placeconicalspringonupperdiaphragm
assembly.Applygreasetoassemblywherespringrests.
Step3–Placeboosterspringintopcap.Applygreasein
topcapwherespringsets.
Step4–Placediaphragmassemblyinpilotblocksuch
thatconicalspringcontactspilotplug.
Step5–Screwthetopcap(3/8"socket)intothepilot
cartridge.Ensurethatspringiscenteredontheupper
diaphragmassembly.Torquetopcapto25-30in·lbs.
Step6–Placelowerspringonlowerdiaphragm
assemblyandinstallintolowerportionofpilotcartridge.
Step7–Installlowercap(3/8"socket)overlower
diaphragmassembly.Torquelowercapto25-30in·lbs.
Step8–Install4newO-ringsintogroovesonoutsideof
cartridge.ApplygreasetoO-rings.
CAUTION:Donotallowgreasetogetonanyother
componentsorintocommunicationholes.Ifgreasegets
intopilotplug/seats,orblockscommunicationpaths,the
pilotmightnotoperatecorrectly.
Step9–Insertpilotcartridgeintoenclosure.
Step10–Install3socketscrews(1/8"hexkey)toretain
pilot.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
11
www.kimray.com
Maintenance - Pilot Assembly
Pilot
Pilot Screw
Top Cartridge Cap
Upper Diaphragm Assy.
Booster Spring
Pilot Plug
O-Ring
Bottom Cap
O-Ring
O-Ring
O-Ring
Booster Pilot Spring
Lower Diaphragm Assy.
Diaphragm Spacer
Cartridge Body
Lower Spring
Lower Seat
Upper Seat

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
12
Maintenance - Mount Assembly
Mount - Disassembly
Step1–Mountcontrollerinviseorstandifavailable
Step2–Removedisplacerarmandextensionsfrom
mount.
Step3–Openandremovecover.Inspectcovergasket
for rips or tears.
Step4–Relieveforceonspringbyrotatingspring
adjusterknobclockwise.Removespringandupper
springplate.
Step5–Removetorqueleverbylooseningsetscrewon
underside.
Step6–Removemountscrewsandliftenclosureoff
ofmount,leavingmountinviseifavailable.Remove
andinspectgasketbetweenenclosureandmountfor
damage.
Step7–Removerstbearinghubandshaft.Flipmount
andremovesecondbearinghub.Removesocketplug
fromendofmount.RemoveanddiscardO-ringsfrom
threads.
Step8–Removeangedbearingsfromhubs.Inspect
angedbearingsforwearordamage.Removeand
discardO-ringsandback-upringsinsidehubs.
Step9–Inspectshaftforwearordamage.Cleanout
inside of mount.
Mount - Reassembly
Step1–InstallO-ringoverthreadedhubs&socketplug.
Toavoidsealdamage,donotpushO-ringoverthreads.
RollO-ringoverthreads.Installsocketplug.Tightento
30-35ft·lbs.
Step2–Insertcomponentsintobothhubsinthe
followingorder:back-upring,O-ring,angedbearing.
Step3–Installabearinghubononesideofmount.
Insertshaftwithatsfacingsideofmountthatattaches
toenclosure.Installsecondbearinghubovershaft.
Tightenbothbearinghubsto30-35ft·lbs.
Step4–Alignmountgasketandenclosureover
mountingholes.ApplyblueLoctitetomountscrewsthen
install.
Step5–ApplyblueLoctitetodisplacerarmand
extensionthreads(ifapplicable)andinstallinshaft.
Step6–Slidetorqueleveroveratsofshaftwithset
screwfacingdownward.Tightensetscrew.
Step7–Installspringandupperspringplate.
Step8–Installandclosecover.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
13
www.kimray.com
Maintenance - Mount Assembly
Back Up
Bearing Hub
Flanged Bearing
Torque Lever
Socket Plug
Displacer Arm
O-Ring
Gasket
Torque Shaft
Mount
O-Ring
O-Ring
Back Up
Flanged Bearing
Bearing Hub
O-Ring
O-Ring
Set Screw

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
14
Maintenance - Spring Assembly
Spring Assembly - Disassembly
Step1–Rotatespringadjustingknobclockwiseto
relieveforceonspring.
Step2–Removespringandupperspringplate.
Step3–Remove½”NPTspringbushing.Unthread
springassemblyfromlowerspringplateandremove
from enclosure.
Step4–Removespringadjustingknobfrombushing.
RemoveandreplacePTFEwasherandO-ringonspring
adjustingknob.
Spring Assembly - Reassembly
Step1–Installspringadjustingknobinto½”NPT
bushing.
Step2–Installbushingandspringassemblyinto
enclosure.
Step3–Threadlowerspringplateontoadjustingknob.
Installspringandupperspringplate.
Step4–Rotatespringadjustingknobtosetcontroller
levelperCalibrationinstructionsonpg.8.
Adjusting Knob
Bushing
Lower Spring Plate
Washer
Upper Spring Plate
Spring
O-Ring

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
15
www.kimray.com
Maintenance - Filter
Filter - Disassembly
Step1–Shutoffsupplypressuretocontrollerandbleed
supply line
Step2–Removethesupplylinefromthelterand
removethelterfromthecontroller
Step3–Cleanoutlterelement.Usingcompressedair
inthedownstream(male)connectionwillhelptoensure
debrisisdislodged.
Step4–Reinstalllter.
Directionofairow
tocleanlterelement

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
16
TROUBLESHOOTING
Troubleshooting
Problem PossibleCauseandSolutions
Notsendingsignalorventingwhenitshould
1. Insufcientsupplygaspressure.Ensurethatsupply
gasisowingtocontrollerandisbetween15-45psi.
2. Blockageincontrollerpassages.Inspectports,lter,
andventplugsforanydebris,cleanifneeded.Ensurethat
atleastoneventportallowsow.Ensuresupplygasis
clean and dry.
3. Undersizeddisplacer.Ifspecicgravitydifferential
isbelow0.2,buoyantforcefromdisplacermaynotbe
sufcienttoactivatepilot.AlargerKimraydisplacermaybe
necessary.Whenusingalargerdisplacer(3x12or2x20)
ifspecicgravitydifferentialisbelow0.1,differentialmust
beincreasedto0.1orgreaterforcontrollertooperate
properly.
4. Damagedseals.Isolateandbleedpressurefrom
pilot.InspectpilotO-ringsanddiaphragms.Replaceif
necessary.
5. Displacerrodnotabletomovefullrange.Solidsor
otherobstructioninsideofvessel,restrictingmovementof
displacer.Bleedallpressurefromvesselandcheck/clean
outobstructioninsidevessel.
Controllerdoesnotrespondquicklyenough
1. Impropercalibration.Adjustsensitivityfulcrumper
Calibrationsectioninthisguide.
2. Improperlysizedtubing.Ensuretubingdiameterisat
least1/4”.3/8”diameterispreferable.Minimizelengthof
tubingbetweencontrollerandvalve.
3. Valveisinappropriatelysized.Doublechecksizingof
valvetoensureadequateowrateforprocessconditions.
Pilotbleedscontinuously
1. Pilotplugand/orseatdirty.Cleanpilotplugandseat,
andensurelterisclean.Instrumentgasmayneedup-
streamltrationormoistureremoval.
2. Damagedseals.Isolateandbleedpressurefrompilot.
InspectpilotO-ringsanddiaphragms.Replaceifneces-
sary.
Mountleakingaroundshaftorplugs 1. Damagedseals.Bleedpressurefromvesseland
replaceO-ringsandbackupringsonmountttings.

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
17
www.kimray.com
Page left blank

PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
18
Page left blank

‡ Configuration of Back Pressure Valve is a trademark of Kimray, Inc.
Kimray is an ISO 9001- certied manufacturer.
Kimray quality assurance process maintains strict controls
of materials and the certication of parts used in the Kimray severe service control valve.
Please visit our website for up to date product data www.Kimray.com
PNEUMATIC LEVEL CONTROLLERPNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
Forquestionsorcomments,contactyourlocalKimrayauthorizeddistributor,orvisitwww.kimray.com.
Kimray Inc.
52 NW 42nd Street
Oklahoma City, OK 73118
Customer Service: 405.525.6601 | service@kimray.com Product/Tech Support: 405.525.4264 | prodtechsupport@kimray.com

© 2018 Kimray, Inc. RM:0021
Issued 3/21