7.9 The Serial Interface
All measuring and setting data of the device can be read and/or changed by
means of the serial interface and a suitable electrically isolated interface adapter
(HND-Z031, HND-Z032). In order to avoid transmission errors, there are several
security checks implemented.
The following standard software packages are available for data transfer:
- HND-Z034: Software for temperature display and/or read out of logger
data.
- BUS-S20M: 20-channel software to display the humidity (channel 1), the
temperature. (channel 2, 3)
The following interface functions will be supported:
Channel DLL-
Code Name/function
1 2 3 4 5 6
x x x x x x 0 Read nominal value
x x x x x x 3 Read s
stem status
x 12 Read ID number
1
1
1
1
1
1
22 Read min. alarm limit
1
1
1
1
1
1
23 Read max. alarm limit
2
32 Read confi
uration fla
2
160 Set confi
uration fla
x x x x x x 199 Read meas. t
pe in displa
x x x x x x 200 Read min. displa
ran
e
x x x x x x 201 Read max. displa
ran
e
x x x x x x 202 Read unit of displa
x x x x x x 204 Read decimal point of displa
x 208 Read channel coun
x x 216 Read offset correction
x 218 Read corr. factor
1000..1200
3
3
3
3
3
3
224 Read lo
er data
c
clic lo
er
4
225 Read lo
er c
cle
5
226 Set lo
er c
cle
6
227 Start lo
er recordin
7
228 Read count of lo
er data
7
229 Read lo
er state
3
231 Read lo
er stop time
x
233 Read real-time clock
x 234 Set real-time clock
7
236 Read lo
er size
x 240 Reset unit
x 254 Read pro
ram identification
8
260 Read lo
er data
man. lo
er
1) only when alarm is activated for referring channel
2) configuration flags: 50: 0 = logger off 1 = logger on
51: 0 = man. logger 1 = cyclic logger
3) only when logger function = CYCL, data present and logger stopped.
4) only when logger function = CYCL
5) only when logger function = CYCL and no data in memory
6) only when logger function = Stor, or logger function = CYCL and no data in memory
7) only when logger is activated (CYCL or Stor)
8) only when logger function = Stor and data in memory
For HND-FF31
Channel 1: rel atmospheric humidity
Channel 2: temperature T1
Channel 3: temperature T2
Channel 4: dew point temperature Td
Channel 5: dew point distance Td
Channel 6: enthalpy h
For HND-FF32/HND-FF33
Channel 1: flow speed
Channel 3: temperature T2
Channel 2, 4, 5, 6: not supported.
For NiCr-Ni (without HND-FF31/32/33)
Channel 3: temperature T2
Channel 1, 2, 4, 5, 6: not supported.
Logger handling still works with
channel 1.