Kobold DAG-T4T00WSR User manual

Operating Instructions
for
Universal display
Model: DAG-T4T00WSR

DAG-T4T00WSR
page 2 DAG-T4 K05/0323
1. Contents
1.Contents ........................................................................................................ 2
2.Note .............................................................................................................. 4
3.Instrument Inspection .................................................................................... 5
4.Regulation Use ............................................................................................. 5
5.Operating Principle ........................................................................................ 6
5.1Signal input .......................................................................................... 6
5.2Offset-Function .................................................................................... 6
5.3Alarms .................................................................................................. 7
5.4Blocking initial of the alarm .................................................................. 8
5.5Auto range function (AVTO.R) .............................................................. 8
5.6Totalizing function ................................................................................ 9
5.7Totalizing/Integration time base (t.base) .............................................. 9
5.8Totalizing/Integration scale factor (t.ScF) ............................................. 9
5.9Batch totalizing function ....................................................................... 9
5.10F1 and F2 function keys....................................................................... 9
5.11Totalizing function and alarms ........................................................... 10
5.12Overflow alarm ................................................................................... 10
5.13Minimum and maximum ..................................................................... 11
5.1424 VDC auxiliary voltage source ........................................................ 11
6.Mechanical Connection ............................................................................... 11
7.Electrical Connection .................................................................................. 12
7.1Recommendations for the installation ................................................ 13
8.Operation .................................................................................................... 13
9.Commissioning............................................................................................ 13
10.Description of the parameters ..................................................................... 15
10.1Operation cycle .................................................................................. 15
10.2Alarm cycle ........................................................................................ 15
10.3Input Signal level parameters ............................................................ 17
10.4Totalizing cycle .................................................................................. 18
10.5Calibration cycle ................................................................................ 18
10.6Password protection .......................................................................... 19
11.Error messages, default and calibration ...................................................... 21
11.1Error messages ................................................................................. 21
11.2Calibration and factor setting ............................................................. 21
12.Technical Information .................................................................................. 22
13.Order Codes ............................................................................................... 22
14.Dimensions ................................................................................................. 22
15.Disposal ...................................................................................................... 23
16.EU Declaration of Conformance ................................................................. 24

DAG-T4T00WSR
DAG-T4 K05/0323 page 3
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: [email protected]
Internet: www.kobold.com

DAG-T4T00WSR
page 4 DAG-T4 K05/0323
2. Note
Please read these operating instructions before unpacking and putting the unit
into operation. Follow the instructions precisely as described herein.
The instruction manuals on our website www.kobold.com are always for currently
manufactured version of our products. Due to technical changes, the instruction
manuals available online may not always correspond to the product version you
have purchased. If you need an instruction manual that corresponds to the
purchased product version, you can request it from us free of charge by email
([email protected]) in PDF format, specifying the relevant invoice number and
serial number. If you wish, the operating instructions can also be sent to you by
post in paper form against an applicable postage fee.
Operating instructions, data sheet, approvals and further information via the QR
code on the device or via www.kobold.com
The devices are only to be used, maintained and serviced by persons familiar
with these operating instructions and in accordance with local regulations
applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the
machines fulfil the EC machinery directive.

DAG-T4T00WSR
DAG-T4 K05/0323 page 5
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of
the delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.
Scope of delivery:
The standard delivery includes:
Universal display model: DAG-T4T00WSR
4. Regulation Use
Any use of the universal display, model: DAG-T4T00WSR, which exceeds the
manufacturer’s specification, may invalidate its warranty. Therefore, any resulting
damage is not the responsibility of the manufacturer. The user assumes all risk
for such usage.

DAG-T4T00WSR
page 6 DAG-T4 K05/0323
5. Operating Principle
The universal panel meter DAG-T4T00WSR is a quite versatile process indicator
with totalizing function. With a wide list of input types - thermocouples, thermo-
resistance, voltage and current the DAG-T4T00WSR is capable of measuring the
majority of the variables and sensors encountered in industrial processes.
Among others it contains two alarms (six functions), sensor offset, configuration
of parameters protected by password, USB communication, indication in degrees
Celsius (°C) or Fahrenheit (°F).
5.1 Signal input
Type CODE Measurement range
Thermocouple J Range: -110 °C to +950 ºC (-166 °F to +1742 ºF)
Thermocouple K Range: -150 °C to +1370 ºC (-238 °F to +2498 ºF)
Thermocouple T Range: -160 °C to +400 ºC (-256 °F to 752 ºF)
Thermocouple N Range: -270 °C to +1300 ºC (-454 °F to 2372 ºF)
Thermocouple R Range: -50 °C to +1760 ºC (-58 °F to 3200 ºF)
Thermocouple S Range: -50 °C to +1760 ºC (-58 °F to 3200 ºF)
Thermocouple B Range: 400 °C to +1800 ºC (752 °F to 3272 ºF)
Thermocouple E Range: -90 °C to +730 ºC (-130 °F to 1346 ºF)
RTD (Pt100) Range: -200 °C to +850 ºC (-328 °F to 1562 ºF)
0 to 20 mA
Linear analogue signal
Indication programmable from -1999 to 30000.
4 to 20 mA
0 to 50 mV
0 to 5 VDC
0 to 10 VDC
Table 01: Input types
5.2 Offset-Function
Allows fine adjustments to the PV (Process value) indication, correcting
measurement errors that appear, for example, after the replacement of the
temperature sensor.

DAG-T4T00WSR
DAG-T4 K05/0323 page 7
5.3 Alarms
The KOBOLD- digital universal panel meter DAG-T4T00WSR has two alarm
outputs:
ALARM1 - Relay SPST - Available on terminals 5 and 6.
ALARM2 - Relay SPST- Available on terminals 3 and 4.
The alarms can assume the functions described on Table 02:
Alarm off.
Alarm of the Absolute Minimum
Value. It triggers when the
value of the PV is below the
value defined by the alarm
Setpoint (SPA1 or SPA2).
SPA1
PV
Alarm of the Absolute
Maximum Value. It triggers
when the value of the PV is
above the value defined by the
alarm Setpoint.
SP
A
1
P
V
Alarm of the Differential Value. In this function the parameters “SPA1” and
“SPA2” represent errors (difference) between the PV and one reference value
(AlrF).
A
LrF
P
V
A
LrF+SP
A
1ALrF–SPA1
A
Lr
F
P
V
A
LrF
–
SP
A
1
A
Lr
F
+ SPA1
SPA1 positive SPA1 negative
Alarm of the Minimum Differential Value. It triggers when the value of the PV is
below the point defined by:
ALrF-SPA1 (using alarm 1 as an example).
A
LrF
PV
A
LrF
–
SPA1
A
LrF
PV
A
LrF
–
SPA1
SPA1 positive SPA1 negative
Alarm of the Maximum Differential Value. It triggers when the value of the PV is
above the point defined by:
ALrF+SPA1 (using alarm 1 as an example).
A
LrF
PV
A
LrF + SPA1
A
LrF
PV
A
LrF + SPA1

DAG-T4T00WSR
page 8 DAG-T4 K05/0323
SPA1 positive SPA1 negative
Alarm of the Absolute Minimum Value. It triggers when the value of the totalizer
(TOT) is below the value defined by the alarm Setpoint.
Alarm of the Absolute Maximum Value. It triggers when the value of the totalizer
(TOT) is above the value defined by the alarm Setpoint.
Alarm at overflow of totalizer.
Alarms of Sensor Break (Sensor Break Alarm). It is activated when the Input
presents problems such as interrupted sensor, bad connection, etc.
Table 02: Alarm functions
Note: The figures are also valid for Alarm 2 (SPA2).
5.4 Blocking initial of the alarm
The initial blocking option inhibits the alarm from being recognized if an alarm
condition is present in the process when the indicator is first energized. The alarm
will be enabled only after the occurrence of no alarm condition.
The initial blocking is useful, for example, when one of the alarms is set up as a
minimum value alarm, which may cause the activation of the alarm soon upon the
process start-up; an occurrence that maybe undesirable in many cases.
The initial blocking feature is not valid for the functions t.lo, t.Hi, t.ofl and ierr.
5.5 Auto range function (AVTO.R)
The indication limits can be set by using operator’s knowledge about the process.
By knowing the relation between the current process variable value and the
desired indication in two points the indication limits can be easily set.
The known PV values are set through P1.Set and P2.Set parameters which are
presented when the Auto Range function is enabled: avto.r= yes.
If the function Auto Range is used the parameters inLL and inHL are
automatically defined.
This function is only available for analog linear input signals.

DAG-T4T00WSR
DAG-T4 K05/0323 page 9
5.6 Totalizing function
This function allows continuous integration of instant PV values.
This continuous integration is stored in a non volatile internal memory and can
also be presented at the indicator display by choosing TOTAL screen which is
identified by the symbol TOT. This symbol is always presented when the TOTAL
is being presented.
The TOTAL value is presented with up to 9 digits (999999999) but when this
value is bigger than 99999 it is splitted in two separate screens indicating the
most and least significant parts and identified with the symbols TOT HIGH and
TOT LOW on the display.
The TOTAL value can be erased through the keyboard or can be reset every time
the indicator is powered up.
5.7 Totalizing/Integration time base (t.base)
The instant PV value integration is executed at a fixed time interval which is
defined by a configuration parameter.
The Time Base options are “second”, “minute”, “hour” and “day”.
5.8 Totalizing/Integration scale factor (t.ScF)
Before being added to the total, the instant PV value is multiplied by the Scale
Factor.
5.9 Batch totalizing function
This function allows the operator to execute the totalization only when a pre-
configured function key is pressed.
This function allows the user to add or subtract the instant PV value to/from the
total accumulated value.
5.10 F1 and F2 function keys
The F1- and F2-Keys can execute several different functions which should be set
by the user when configurating the indicator.
Key not used to any special function.
Executes Batch Function - Addition
Executes Batch Function - Subtraction
Reset Total value
Present maximum read value
Present minimum read value
Reset minimum and maximum values

DAG-T4T00WSR
page 10 DAG-T4 K05/0323
Two different functions can be assigned to F1 and F2 keys. The function to be
executed, Primary or Secondary, is determined by the amount of time the
function key is being pressed. If the function key is pressed for less than 1
second the Primary function is executed.
If the key is pressed for more than 3 seconds then the Secondary function is
executed.
The combination of the keys F1 and F2 pressed simultaneously can also execute
a Special Function. All Special Functions are available to the operator as follows:
F1_1: F1 Key, Primary Function.
F1_2: F1 Key, Secondary Function.
F2_1: F2 Key, Primary Function.
F2_2: F2 Key, Secondary Function.
F12_1: F1+F2 Keys, Primary Function.
F12_2: F1+F2 Keys, Secondary Function.
5.11 Totalizing function and alarms
The totalization alarm functions and allow the user to notify when a
total value is reached.
The alarm defined as Totalization Minimum Value Alarm ) is set when the
totalization value goes below the configured setpoint.
The alarm defined as Totalization Maximum Value Alarm () is set when the
totalization value goes above the configured setpoint.
As the totalization value can indicate up to 99999 99999 (or -9999 99999) the set
point values behave the same way. If the adjusted SP goes above 99999 (or
below -9999) the second SP part is displayed allowing the operator to see values
up to 99999 99999 (or -9999 99999).
The flags HIGH and LOW identify if the part being displayed is the SP most
significant part (HIGH) or the least significant part (LOW).
The totalization alarm (SP) is defined through the values SPA1 and SPA2. This
two parameters behave different from other parameters. The Back key allows the
operator to change the SP decimal digit to be set.
5.12 Overflow alarm
This alarm function is set when the totalized value surpasses 9999999999, which
is the maximum indication value.

DAG-T4T00WSR
DAG-T4 K05/0323 page 11
5.13 Minimum and maximum
The indicator is continuously storing the extreme input indication measurements,
or the minimum and maximum values. These values can be displayed at any time
by the operator by pressing the keys F1 and F2. Notice that the function Keys
should be set to and .
To reset the maximum and minimum values and start another monitoring cycle,
just execute the function , which can be assigned to the keys F1 and F2.
When the indicator is powered off this information is not stored.
5.14 24 VDC auxiliary voltage source
The standard version of the DAG-T4T00WSR provides an auxiliary power supply
(24 VDC) for exciting field transmitters (terminal 13 on the rear panel).
6. Mechanical Connection
The indicator is meant for panel mounting. The sequence of steps is:
Prepare a cut out of 93.0 by 45.5 mm on the panel
Remove the mounting clamp from the indicator
Insert the indicator into the cut out from the front side of the panel
Place the clamp on the indicator again, pressing until firm grip to the panel

DAG-T4T00WSR
page 12 DAG-T4 K05/0323
7. Electrical Connection
The terminals configurations are shown in Figure 01.
Figure 01: Input connections and power supply
Figure 02: Thermocouple, Pt100 and 50 mV signal connection
Figure 03: Current (mA) and Voltage (V) signal connection
This indicator offers an auxiliary 24 VDC +/-15% at 50 mA power supply which is
typically applied to power up two wire 4 to 20 mA field transmitters. The Figure
04 presents the wiring for this application.
Figure 04: Auxiliary 24 VDC usage example
DAG-T4T00WSR

DAG-T4T00WSR
DAG-T4 K05/0323 page 13
7.1 Recommendations for the installation
To minimize the pick-up of electrical noise, the low voltage DC connections and
the sensor input wiring should be routed away from high-current power
conductors. If this is impractical, use shielded cables. In general, keep cable
lengths to a minimum.
The input signal conductors shall be positioned throughout the factory separate
from the output and the power supply conductors, in grounded conduits if
possible.
The power supply of the electronic instruments shall come from a proper source
for the instrumentation network.
It is recommended to use RC FILTERS (0,1uF in series with 100 ohms) to
suppress the noise generated by contactors coils, solenoids, etc.
8. Operation
The indicator front panel, together with its elements, can be seen on:
Indicators
Push buttons
Figure 02: Identification of the front panel parts.
Display: Shows the process variable (PV), the configuration parameter prompts
and their respective values/conditions.
Indicators A1 and A2: signalize the occurrence of an alarm condition.
Key P: Used to walk through the parameters in the menu cycles.
Increment key and Decrement key: Used to change parameter values.
Key : Go back to the previous displayed parameter. This key changes its
behavior starting to set the decimal digit to set.
9. Commissioning
When the controller is powered up, its firmware version is displayed for 3
seconds, after which the DAG-T4T00WSR starts normal operation, when the
value of PV is displayed and the outputs are enabled.
Before the indicator is ready to be used in a given process, it requires some basic
configuration, consisting of assigning values to the parameters according to the
desired behavior. The user shall understand the importance of each parameter
and determine a valid condition or a valid value for each one of them.

DAG-T4T00WSR
page 14 DAG-T4 K05/0323
The configuration parameters are grouped in levels according to their affinity. The
5 parameter levels are:
1 – Operation
2 – Alarms
3 – Input
4 – Totalizer
5 – Calibration
The “P” key provides the access to the levels and to the parameters of these
levels.
Keeping the P key pressed, at every 2 seconds, the indicator jumps from one
level to another, presenting the first parameter of each level:
Measurement PV>>>>>>>>>>PV …
To enter a particular level, simply release the P key when the first parameter in
that level is displayed.
To walk through the parameters in a level, press the P key with short strokes. To
go back to the previous parameters, use the Key.
The display alternates the presentation of the parameter prompt and its value.
The parameter value is displayed with a light blinking to differentiate it from the
parameter prompt.
Depending on the level of parameter protection adopted, the parameter
precedes the first parameter in the level where the protection is active. See
section Protection configuration.

DAG-T4T00WSR
DAG-T4 K05/0323 page 15
10. Description of the parameters
10.1 Operation cycle
Indication Display of PV:
The value of the measured variable (PV) is shown on the main display
(
red
)
.
Totalizing value:
When this value is bigger than 99.999 it is splitted in two separate
screens indicating the most and least significant parts and identified
with the s
y
mbols TOT HIGH and TOT LOW on the displa
y
SetPoint
Alarm
Alarm SP:
Value that defines the alarm activation point.
For the alarms set up with the functions of the type Differential or
Band, these parameters define the maximum differences accepted
between PV and a reference value defined in the parameter .
For the alarm function , this parameter is not used.
Parameters show in this level only when enabled in the parameters
and .
10.2 Alarm cycle
Alarm Functions. It defines the functions of the alarms among the
options in Table 02 (page 5).
Alarm
Reference
Reference value used by the alarms with differential function, minimum
differential or maximum differential.
Alarm
Referen
z
Totalization alarm SP decimal point.
SetPoint
Alarm
Alarm SP: Value that defines the point of activation of the alarm
outputs. For the alarms programmed with the functions of the type
Band and Differential, these parameters represent the deviations.
For the and alarm functions, this parameter has no
meanin
g
.

DAG-T4T00WSR
page 16 DAG-T4 K05/0323
SP enable
It allows the parameters and to be displayed also in
the indicator operation cycle.
: Shows the parameters in the operation cycle.
: DOES NOT show the parameters in the
operation c
y
cle.
Blocking
A
larm
Alarms Initial Blocking (see section 4.5).
: Enables the initial blocking
: Inhibits the initial blocking
Hysteresis of
A
larms
Alarm Hysteresis. It defines the difference between the value of PV at
which the alarm is triggered and the value at which it is turned off.
Flash
It allows signalization of an alarm condition occurrence by flashing the
indication of PV on the indication display.
:Enables alarm signalization by flashing PV.
: Disables the flashing PV.

DAG-T4T00WSR
DAG-T4 K05/0323 page 17
10.3 Input Signal level parameters
Type
Input Type. Selection of the input type, used by the indicator. Refer to
Table 01 on page 4.
Filter
Digital Input Filter – Used to improve the stability of the measured
signal (PV). Adjustable between 0 and 20. At 0 (zero) it means filter
turned off and 20 means maximum filter. The higher the filter value, the
slower is the response of the measured value.
Decimal Point
It determines the position of the decimal point on the display.
Unit
It defines the temperature unit to be used:
indication in Celsius.
indication in Fahrenheit.
Offset
Parameter that allows the user to make fine adjustments to the
indicated PV value.
Auto Range
Enables the scaling of the PV by applying the input signal.
PV value to the first process known point when Auto Range function is
enabled (
PV value to the second process known point when Auto Range function
is enabled ).
Input Low
Limit
It defines the lower value of the indication range when the input types of
0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V are used
().
input High
Limit
It defines the upper value of the indication range when the input types
of 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V are used
().
Defines the function to be executed by F1 and F2 keys:
No associated function
Executes Batch Function - Addition
Executes Batch Function - Subtraction
Reset Total value
Present maximum read value
Present minimum read value
Reset minimum and maximum values

DAG-T4T00WSR
page 18 DAG-T4 K05/0323
10.4 Totalizing cycle
Defines the indicator operation mode.
Totalizing function enabled
Totalizing function disabled
Batch operation
Totalizer Decimal Point Position
Defines the decimal point position when presenting the total value.
Totalizer time
base
Defines the time totalizing function time base.
seconds
minutes
hours
days
TotalizerScale
Facto
r
Totalizer Scale Factor.
Can be set from 0,001 to 65,0.
LowCut
Totalizer low cut value.
Defines the lowest PV instant value limit considered for totalization and
does not inte
g
rate an
y
value below.
Power Up
Reset
Power up Reset
Defines if the total value is restored or reset on indicator power up
Reset Totalizer
No reset of the Totalizer
10.5 Calibration cycle
All types of input are calibrated in the factory. In case a recalibration is required; it
shall be carried out by a specialized professional. In case this cycle is
accidentally accessed, do not perform alteration in its parameters. The factory
calibration can be restored in the parameter rstr.
Password. Entering the Access password. This parameter is presented
before the protected cycles. See item Protection of Configuration.
Calibration. Enables the possibility for calibration of the indicator. When
the calibration is not enabled, the related parameters are hidden.
Input Low Calibration. Indication of the low scale calibration signal
applied to the input.
Input High Calibration. Indication of the full scale calibration signal
applied to the input.

DAG-T4T00WSR
DAG-T4 K05/0323 page 19
Restore.It restores the factory input calibration and the indicator factory
parameters, disregarding any modifications carried out by the user.
Cold Junction. Temperature of the indicator cold junction.
Password Change. It allows the definition of a new access password,
always different from zero.
Protection. Sets up the Level of Protection. See Table 03.
Frequency. Frequency of the local electrical network.
Serial number 4 most significant digits.
Serial number 4 least significant digits.
10.6 Password protection
The DAG-T4T00WSR indicator provides means for protecting the parameters
configurations, not allowing modifications to the parameters values, avoiding
tampering or improper manipulation. The parameter Protection () in the
Calibration level determines the protection strategy, limiting the access to
particular levels, as shown in the table below.
ProtectionLevel ProtectedLevels
1 Only the Calibration level is protected.
2 Totalization and Calibration levels are
protected.
3 Input, Totalization and Calibration levels
are protected.
4 Alarms, Input, Totalization and Calibration
levels are protected.
Table 03: Levels of Protection of the configuration

DAG-T4T00WSR
page 20 DAG-T4 K05/0323
ACCESS PASSWORD
The protected levels, when accessed, request the user to provide the Access
Password for granting permission to change the configuration of the parameters
on these levels.
The prompt precedes the parameters on the protected levels. If no
password is entered, the parameters of the protected levels can only be
visualized.
The Access Password is defined by the user in the parameter Password Change
(), present in the Calibration Level. The factory default for the
password code is 1111.
PROTECTION OF THE ACCESS PASSWORD
The protection system built into the controller blocks for 10 minutes the access to
protected parameters after 5 consecutive false attempts of entering the correct
password.
MASTER PASSWORD
The Master Password is intended for allowing the user to define a new password
in the event of it being forgotten. The Master Password doesn’t grant access to all
parameters, only to the Password Change parameter (). After defining
the new password, the protected parameters may be accessed (and modified)
using this new password.
The master password is made up by the last three digits of the serial number of
the controller added to the number 9000.
As an example, for the equipment with serial number 07154321, the master
password is 9 3 2 1.
The indicator serial number can be obtained by pressing for 5 seconds.
Table of contents
Other Kobold Monitor manuals

Kobold
Kobold LPS-P User manual

Kobold
Kobold NMF Series User manual

Kobold
Kobold AUF-2000 User manual

Kobold
Kobold AUF-1 series User manual

Kobold
Kobold AUF-1000 User manual

Kobold
Kobold AUF-1 series User manual

Kobold
Kobold NCW Series User manual

Kobold
Kobold KAL-K User manual

Kobold
Kobold ADI-1V Series User manual
Popular Monitor manuals by other brands

Iiyama
Iiyama Prolite E433 user manual

Evervictory Electronic Company Limited
Evervictory Electronic Company Limited TR-7150CS user manual

Mars
Mars C900 FL-TG user manual

JVC
JVC BM-H1900SU - Color Production Monitor instructions

Toshiba
Toshiba 55UL3C63DT quick start guide

ETB Instruments
ETB Instruments DigiDash 2 quick start guide