Kobold ADI-1V Series User manual

Operating Instruction
Operating
Instruction
for
Universal Indicating Unit
Norm signals 0/4-20 mA, 0-10 VDC
Model: ADI-1V... 96x96 mm
96x96
ADI_1VD.pdf Stand: K02-0916
O
Or
rd
de
er
r
f
fr
ro
om
m:
:
C
C
A
A
B
Br
ri
ig
gg
gs
s
C
Co
om
mp
pa
an
ny
y
622 Mary Street; Suite 101; Warminster, PA 18974
Phone: 267-673-8117 -
Fax: 267-673-8118
Sa[email protected] - www.cabriggs.com

Identification
Options – break-down ordering code:
ADI-1V000200
Standard type ADI
Bargraph and Digital display, red
Bargraph 55 points 270°, digital display 5-digit, 14 mm 1
Type of display
Voltage-/current input 0-10 VDC / 0/4-20 mA V
Power supply
100-240 VAC +/- 10% (50-60Hz) / DC 0
10-40 VDC / 18-30 VAC 50/60 Hz 3
Analogue output
without 0
0-10 VDC, 0/4-20 mA, 16 bit reversible 4
Sensor supply
without 0
5VDC/20mA
U
5
VDC
/
20
mA
U
12 VDC / 50 mA, incl. digital input V
24 VDC / 50 mA, incl. digital input W
Setpoints
2 relay outputs 2
Housing
Housing
Panel mounting housing 0
Field housing F
Field housing with wall mounting finally rotatable S
Field housing with pipe mounting R
Special
without
0
without
0
Special please specify in clear text Y
2

Contents
1. Brief description 4
2. Assembly 5
3
El t i l ti
3
.
El
ec
t
r
i
ca
l
connec
ti
on 6
4. Description of function and operation 9
5. Setting up the device 11
5.1. Switching on 11
5.2. Standard parameterisation (flat operation level) 11
Value assignment for the triggering of the signal input of the digital display and bargraph display
5.3. Programming interlock „RUN“ 15
Activiation/Deactivation of the programming interlock or change into professional operation level
respectively back into flat operation level
5.4. Extended parameterisation (professional operation level) 16
5.4.1. Signal input parameters „INP“
Value assignment for the triggering of the signal input incl. linearisation of the digital display and
the bargraph display
5.4.2. General device parameters "FCT"
"FCT" Superior device functions like HOLD, TARA, min/max permanent, setpoint value function /
nominal value function, averaging, brightness control, as well as the control of the digital input and
keyboard layout
5.4.3. Bargraph functions „bar“
Assignment of the bargraph to superior functions like min/max, totaliser, HOLD or
sliding averaging
5.4.4. Safeafety parameters „Cod“ 25
Assignment of user and master code for locking respectively for access to defined parameters
like e.g. analog output and alarms, etc.
5.4.5. Analog output parameters „Out“26
Analog output functions
5.4.6. Relay functions „rel“ 28
Parameters for the definition of the setpoints
5.4.7. Alarm parameters „AL1…AL4“30
Actuator and dependencies of the alarms
5.4.8. Totaliser (volume metering) „tot“32
Parameters for the calculation of the sum function
6. Reset to factory settings 33
Reset parameters to delivery state
7
Alarms / Relay
7
.
Alarms
/
Relay
34
Functional principle of the switching outputs
8. Sensor alignment 35
Diagram of functional sequences for sensors with existing adjustable resistor
9. Technical data 36
10. Safety advices 38
11. Error elimination 39
3
12. EU Declaration of Conformance 40
16
19
23

1. Brief description
1. Brief description
The panel meter instrument ADI-1V is a 5-digit digital display with a 55 points bargraph display
and two galvanic insulated setpoints; designed for direct current/direct voltage signals. The
configuration
happens
via
four
keys
at
the
front
The
integrated
programming
interlock
prevents
configuration
happens
via
four
keys
at
the
front
.
The
integrated
programming
interlock
prevents
unrequested changes of parameters and can be unlocked again with an individual code. Optional
the following functions are available: a supply for the sensor, a digital input for triggering of Hold
(Tara), two analog outputs and interfaces for further evaluating in the unit. The electrical
connection is done via plug-in terminals on the back side.
Selectable functions like e.g. the recall of the min/max-value, an averaging of the measuring
signals, a nominal presetting or setpoint presetting, a direct threshold value regulation during
o
p
eration mode and furthe
r
measurin
g
set
p
oints fo
r
linearisation
,
com
p
lete the modern device
p
g
p
,
p
concept.
Technical features:
• red display of -19999…99999 digits
• red 55 points bargraph
• adjustable bar or dot operation or operation with permanent display of center point
• min/max memory
• 30 additional adjustable setpoints
• display flashing at threshold value exceedance/undercut
• zero-key for triggering of HOLD, TARA
• permanent min/max-value recording
• volume metering (totalisator)
• mathematical functions like reciprocal value, square root, squaring or rounding
• setpoint generator
• sliding averaging
•
brightness control
•
brightness
control
• programming interlock via access code
• protection class IP65 at the front
• plug-in screw terminal
• 2 relay outputs (changer)
• optional: sensor supply and digital input
• optional: analog output
4

2.1 Mounting panel housing
2. Assembly
Please read the Safety advice on page 37 before installation and keep this user manual
for future reference.
56mm
82mmwithplug-interminal
Sealing
9
6 mm
9
Fixing
ele
ment
96mm
7mm
ele
1. After removing the fixing elements, insert the device.
2. Check the seal to make sure it fits securely.
3. Click the fixing elements back into place and tighten the clamping screws by hand.
Then use a screwdriver to tighten them another half a turn.
CAUTION! The torque should not exceed 0.1 Nm!
Please state you favorite dimension symbol in your order, they can not be
exchanged afterwards!
5

2.2 Mounting field housing
2. Montage
For the assembling of ADI-1 field housing please use the M4 screws. Optionally the housing can
be delivered with wall mounting or pipe mounting For the electrically connection please pull the
be
delivered
with
wall
mounting
or
pipe
mounting
.
For
the
electrically
connection
please
pull
the
housing lead back.
S1 S2
P
OBOLD
ADI-1
P
6

3. Electrical connection
3. Electrical connection
Model ADI-1V000200 with supply of 100-240 VAC
M d l ADI
1V300200 ith l f 10
40 VDC
M
o
d
e
l
ADI
-
1V300200
w
ith
supp
l
y o
f
10
-
40
VDC
7

3. Electrical connection
Connection examples
ADI
1V d i ith t i t / lt i t
ADI
-
1V
d
ev
i
ces w
ith
curren
t
i
npu
t
/
vo
lt
age
i
npu
t
ADI-1V devices in combination with a
2-wire-sensor 4-20 mA
ADI-1V devices in combination with a
3-wire-sensor 0/4-20 mA
ADI-1V devices in combination with a
3-wire-sensor 0-10 V
ADI-1V -devices with current input / voltage input and sensor supply
8

4. Description of function and operation
4. Description of function and operation
Operation
The operation is divided into three different levels.
Menu level (delivery status)
This level is for the standard settings of the device. Only menu items which are sufficent to set the
device into operation are displayed. To get into the professional level, run through the menu level
and parameterise “prof“ under menu item RUN.
Menu group level (complete function volume)
Suited for complex applications as e.g. linkage of alarms, setpoint treatment, totaliser function etc. In
this level ffunction groups which allow an extended parameterisation off the standard settings
are availabe. To leave the menu group level, run through this level and parameterise „uloc„ under
menu item RUN.
Parameterisation level:
Parameter deposited in the menu item can here be parameterised. Functions, that can be changed
or adjusted, are always signalised by a flashing of the display. Settings that are made in the
parameterisation
level
are
confirmed
with
[P]
and
thus
safed
By
pressing
the
[O]
-
key
“
it
leads
to
a
parameterisation
level
are
confirmed
with
[P]
and
thus
safed
.
By
pressing
the
„
[O]
-
key
it
leads
to
a
break-off of the value input and to a change into the menu level. All adjustments are safed
automatically by the device and changes into operating mode, if no further key operation is done
within the next 10 seconds.
Level Key Description
Menu-level
Change to parameterisation level and deposited values.
Keys for up and down navigation in the menu level.
Change into operation mode.
Parameterisation-
level
To confirm the changes made at the parameterisation level.
Adjustment of the value / the setting.
Change into menu level or break-off in value input.
Menu-group-level
Change to menu level.
Keys for up and down navigation in the menu group level.
Change into operation mode or back into menu level.
9

4. Description of function and operation
Function chart:
10

5. Setting up the device
5. Setting up the device
5.1. Switching on
Once the installation is com
p
lete
,
y
ou can start the device b
y
a
pp
l
y
in
g
the volta
g
e su
pp
l
y
. Before
,
p,y yppyg g ppy ,
check once again that all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (88888) is displayed followed by
an indication of the software type and, after that, also for 1 second the software version. After
the starting sequence, the device switches to operation/display mode.
5 2 Standard parameterisation:
(Flat operation level)
Menu level Parameterisation level
Selection of the input signal, TYPE:
Default:sens.u
5
.
2
.
Standard
parameterisation:
(Flat
operation
level)
To parameterise the display, press the [P] key in operating mode for 1 second. The display
then changes to the menu level with the first menu item TYPE.
Available as measuring input options are 0-20 mA, 4-20 mA or 0-10 VDC signals as works
calibration (without application of the sensor signal) and SENSU (voltage) or SENSA (current))
as sensor calibration (with the sensor applied). Confirm the selection with [P] and the display
switches back to menu level.
Setting the end value of the measuring range, END:
Default: 10000
Set the end value from the smallest to the highest digit with [▲][▼] and confirm each digit with
[P]. A minus sign can only be parameterized on the highest value digit. After the last digit, the
display switches back to the menu level. If Sens was selected as input option, you can
only select between noca and cal. With noca, only the previously set display value is taken over,
and with cal, the device takes over both the display value and the analogue input value.
Setting the start/offsett vallue of the measuring range,
offs: Default: 0
11
Enter the start/offset value from the smallest to the highest digit with [▲][▼] and confirm
each digit with [P]. After the last digit the display switches back to the menu level. If
Sens was selected as input option, you can only select between noca and cal. With noca,
only the previously set display value is taken over, and with cal, the device takes over both
the display value and the analogue input value.

5. Setting up the device
Menu level Parameterisation level
Setting the decimal point, dot: Default: 0
The decimal point on the display can be moved with [▲][▼] and confirmed with [P].The
display then switches back to the menu level again.
Setting up the display time, SEC:
Default: 1.0
The display time is set with [▲] [▼]. The display moves up in increments of 0.1 sec up to 1 sec
and in increments of 1.0 sec up to 10.0 sec. Confirm the selection by pressing the [P] button.
Th di l th it h b k t th l l i
then
Th
e
di
sp
l
ay
th
en sw
it
c
h
es
b
ac
k
t
o
th
e menu
l
eve
l
aga
i
n.
Setting up the final value of the bargraph,
ba.ENd: Default: 10000
Set the final value from the smallest to the hi
g
hest di
g
it with
[
▲
]
[
▼
]
and confirm each di
g
it
g
g
[
]
[
]
g
with [P]. A minus sign can only be parameterised on the highest value digit. After the last digit,
the display switches back to the menu level.
Setting up the initial value of the bargraph,
ba.off: Default: 0
Set the initial value from the smallest to the highest digit with [▲][▼] and confirm each digit
with [P]. A minus sign can only be parameterised on the highest value digit. After the last digit,
the display switches back to the menu level.
Selection of the bargraph functions,
ba.fct: Default: bar.fo
The bargraph can be displayed with the following possibilites: bars from left to right (top to
bottom) or bars from right to left (bottom to top), bars from the middle, a dot display of the
bargraph or a dot display with a permanently displayed midpoint. Confirm the selection by
pressing
the
[P]
button
The
display
then
switches
back
to
the
menu
level
again
12
pressing
the
[P]
button
.
The
display
then
switches
back
to
the
menu
level
again
.

5. Setting up the device
Menu level Parameterisation level
Selection of analog output, Out.rA:
Default: 4-20
Three output signals are available: 0-10 VDC, 0-20 mA and 4-20 mA, with this function, the
demanded
signal
is
selected
.
demanded
signal
is
selected
.
Setting up the final value of the analog output,
Out.En: Default: 10000
The final value is adjusted from the smallest digit to the highest digit with [▲][▼]and digit by
digit
confirmed
with
[P]
A
minus
sign
can
only
be
parameterised
on
the
highest
digit
After
the
digit
confirmed
with
[P]
.
A
minus
sign
can
only
be
parameterised
on
the
highest
digit
.
After
the
last digit, the device changes back into menu level.
Setting up the initial value of the analog output,
Out.OF: Default: 00000
The final value is adjusted from the smallest digi
t
to the highest digit with [▲][▼]and digit b
y
digit confirmed with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Threshold values / Limits, LI-1:
Default: 2000
This value defines the threshold, that activates/deactivates an alarm.
Hysteresis for limit values, HY-1:
Default: 00000
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
13

5. Setting up the device
Menu level Parameterisation level
Function for threshold value undercut /exceedance,
Fu-1: Default: high
A limit value undercut is selected with Louu (for LOW = lower limit value), a limit value
exceedance with High (for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level
of 100 and allocated with function High, an alarm is activated by reaching of the threshold level.
If the threshold value was allocated to Low, an alarm will be activated by undercutting the
threshold value, as long as the hysteresis is zero.
Threshold values / Limits, LI-2:
Default: 2000
This value defines the threshold, that activates/deactivates an alarm.
Hysteresis for limit values, HY-2:
Default: 00000
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
Function for threshold value undercut /exceedance,
Fu-2: Deault high
A limit value undercut is selected with Louu (for LOW = lower limit value), a limit
value exceedance with High (for HIGH = higher limit value). If e.g. limit value 1 is on a
threshold level of 100 and allocated with function High, an alarm is activated by reaching of the
threshold level. If the threshold value was allocated to Low, an alarm will be activated by
undercutting the threshold value, as long as the hysteresis is zero.
14

5. Setting up the device
Menu level Parameterisation level
User code (4-digit number-combination, free available), U.CodE:
Default: 0000
If this code was set (>0000), all parameters are locked for the user, if LOC has been selected
before under menu item run.Bypressing [P] for 3 seconds in operation mode,
the display shhows COde. The U.Code needs tobe entered to get to
thereducednumber of parameter sets. The code has to be entered befor each
parameterisation, until the A.Code (Master code) unlocks all parameters again.
Master code (4-digit number-combination, free available), A.CodE:
Default: 1234
All parameters can be unlocked with this code, after LOC has been activated under menu item
run.By pressing [P] for 3 seconds in operation mode, the display shows COde and
enables the user to reach all parametes by entering the A.codE. Under run the
parameterisation can be activated permanently by selecting ULOC or ProF, thus at an anew
pushing of [P] in operation mode, the code needs not to be entered again.
5.3. Programming interlock „run“
Activation / deactivation of the programming lock or completion of the standard
parameterisation with change into menu group level (complete function range), run:
Default: uloc
With the navigation keys [▲][▼], you can choose between the deactivated key lock Uloc
(works setting) and the activated key lock Loc, or the change into the menu group level ProF.
Confirm the selection with [P]. After this, the display confirms the settings with "-----", and
automatically switches to operating mode. If Loc was selected, the keyboard is locked. To get
back into the menu level, press [P] for 3 seconds in operating mode. Now enter the CODE
(works setting 1234) that appears using [▲][▼]plus [P] to unlock the keyboard. FAIL
appears if the input is wrong. To paparameterise further functions ProF needs to be set.
The device confirms this setting with „-----„ and changes automatically in operation mode.
By pressing [P] for approx. 3 seconds in operation mode, the first menu group InP is shown in
the display and thus confirms the change into the extended parameterisation. It stays activated
as long as ULOC or LOC is entered in menu group RUN.
15

5. Setting up the device
5.4. Extended parameterisation (professional operation level)
5.4.1. Signal input parameters
Menu group level
Menu level
Menu level Parameterisation level
Selection of the input signal, TYPE:
Default: sens.u
There are several measuring input options: 0-20 mA, 4-20 mA or 0-10 VDC signals as works
calibration (without application of the sensor signal) and SenSU (voltage) or SENSA (current)
as sensor calibration (with the sensor applied). Confirm the selection with [P] and the display
switches back to menu level.
Setting the end value of the measuring range, END:
Default: 10000
Set the end value from the smallest to the highest digit with [▲][▼] and confirm each digit with
[P]. A minus sign can only be parameterised on the highest value digit. After the last digit, the
display switches back to the menu level. If Sens was selected as input option, you can
only select between noca and cal. With noca, only the previously set display value is taken
over, and with cal, the device takes over both the display value and the analogue input value.
Setting up the start/offset value of the measuring range,
offs: Default: 0
Enter the start/offset value from the smallest to the highest digit with [▲][▼] and confirm each
digit with [P]. After the last digit the display switches back to the menu level. If Sens
was selected as input option, you can only select between noca and cal. With noca, only the
previously set display value is taken over, and with cal, the device takes over both the
display value and the analogue input value.
16
Setting the decimal point,
dot: Default: 00
The decimal point on the display can be moved with [▲][▼] and confirmed with [P].The
display then switches back to the menu level again.

5. Setting up the device
Menu level Parameterisation level
Setting up the display time, SEC:
Default: 1.0
The display time is set with [▲] [▼]. The display moves up in increments of 0.1 sec up to 1 sec
and in increments of 1.0 sec up to 10.0 sec. Confirm the selection by pressing the [P] button.
The display then switches back to the menu level again
then
The
display
then
switches
back
to
the
menu
level
again
.
Rescaling the measuring input values, EndA:
Default: 10000
With this function, you can rescale the input value of e.g. 19.5 mA (works setting) without
applying
a
measuring
signal
If
sensor
calibration
has
been
selected
these
parameters
are
not
applying
a
measuring
signal
.
If
sensor
calibration
has
been
selected
,
these
parameters
are
not
available.
Rescaling the measuring input values, OFFA:
Default: 0
With
this
function
you
can
rescale
the
input
value
of
e
g
3
5
mA
(works
setting)
without
With
this
function
,
you
can
rescale
the
input
value
of
e
.
g
.
3
.
5
mA
(works
setting)
without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.
Setting up the tare/offset value, tArA:
Default: 0
The given value is added to the linearised value. In this way, the characteristic line can be
shifted by the selected amount.
Setting up the balance point, Adj.pt:
Default:08000
The balance point for the final value can be chosen from the measuring range by Sens.u
with 0…10 V or Sens.A with 0…20 mA in %. The preset 80.000% result from the
widespread detuning of the melt pressure sensors.
Number of additional setpoints, SPCt:
Default: 00
17
30 additional setpoints can be defined to the initial- and final value, so linear sensor values are
not linearised. Only activated setpoint parameters are displayed.

5. Setting up the device
Menu level Parameterisation level
Display values for setpoint, dIS.01 … dIS.30:
Under this parameter setpoints are defined according to their value. At the sensor calibration,
like at Endwert/Offset, one is asked at the end if a calibration shall be activated.
Analog values for setpoints, InP.01 …InP.30:
The setpoints are always set according to the selected input signal. The desired analog values
can be freely parametrised in ascending order.
Device undercut, dI.Und:
Default: -i9999
With this function the device undercut (
_
_
_
_
_
) can be defined on a definite value. Exception is
input type 4-20 mA, it already shows undercut at a signal <1 mA, so a sensor failure is marked.
Display overflow, dI.OUE:
Default: 99999
With this function the display overflow (_____) can be defined on a definite value.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–INP-“.
18

5. Setting up the device
5.4.2. General device parameters
Menu group level
Mll
Ptitill
Menu
group
level
Menu level
M
enu
l
eve
l
P
arame
t
er
i
sa
ti
on
l
eve
l
Display time, DISEC:
Default: 01.0
then
The display is set up with [▲][▼]. Thereby it switches up to 1 second in increments of 0.1
seconds and up to 10.0 seconds in increments of 1.0. With [P] the selection is confirmed and
the device changes into menu level.
Rounding of display values, round:
Default: 00001
This function is for instable display values, where the display value is changed in
increments of 1, 5, 10 or 50. This does not affect the resolution of the optional outputs. With [P]
the selection is confirmed and the device changes into menu level.
Arithmetic, ArItH:
Default: n0
With this function the calculated value, not the measuring value, is shown in the display. With
no, no calulation is deposited. With [P] the selection is confirmed and the device changes into
menu level.
Reciprocal Root
extraction
Square
Sliding average determination, AVG:
Default: 10
19
Here, the number of the meterings that need to be averaged is preset. The time of averaging
resultltsof theproduct of measuring time SEC and theaveraged metering
AVG. With the selection of AVG in the menu level DISPL, the result will be shown in the
display and evaluated via the alarms.

5. Setting up the device
Menu level Parameterisation level
Zero point slowdown, ZErO:
Default: 00
At the zero point slowdown, a value range around the zero point can be preset, so the display
shows a zero. If e.g. a 10 is set, the display would show a zero in the value range from -10 to
+10
;
below continue with -11 and be
y
ond with +11. The maximum ad
j
ustable ran
g
eofvalueis
;
y
j
g
99.
Definite contstant value,
const: Default: 0
The
constant
value
can
be
evaluated
via
the
alarms
or
via
the
analog
output
like
the
current
The
constant
value
can
be
evaluated
via
the
alarms
or
via
the
analog
output
,
like
the
current
measurand. The decimal place cannot be changed for this value and is taken over by the
current measurand. Like this a setpoint generator can be realised via the analog output by this
value. Furthermore it can be used for calculating the difference. At this the constant value is
substracted from the current measurand and the difference is evaluated in the alerting or by the
analog output. Thus regulations can be displayed quite easily.
Minimum constant value,
con.mi: Default: -i9999
The minimum constant value is adjusted from the smallest to the highest digit with the
navigation keys [▲][▼]and confirmed digit per digit with [P]. A minus sign can only be
adjusted on the highest digit. After the last digit the display changes back into menu level.
Maximum constant value,
con.ma: Default: 99999
The maximum constant value is adjusted from the smallest to the highest digit with the
navigation keys [▲][▼]and confirmed digit per digit with [P]. A minus sign can only be
adjusted on the highest digit. After the last digit the display changes back into menu level.
Display, dISPL:
Default: actua
20
With this function the current measuring value, Min-/Max value, totaliser value or the process-
controlled Hold-value can be allocated to the display. With [P] the selection is confirmed and
the device changes into menu level.
This manual suits for next models
3
Table of contents
Other Kobold Monitor manuals

Kobold
Kobold KAL-K User manual

Kobold
Kobold DAG-T4T00WSR User manual

Kobold
Kobold AUF-1 series User manual

Kobold
Kobold AUF-1 series User manual

Kobold
Kobold LPS-P User manual

Kobold
Kobold AUF-2000 User manual

Kobold
Kobold NMF Series User manual

Kobold
Kobold NCW Series User manual

Kobold
Kobold AUF-1000 User manual