14 TT-1443 9/07
2.2 Model K1/S1 with Series 1500 Controls
2.2.1 Configure the ATS Communication Settings
and Optional Input
Configure the transfer switch communication settings
and inputs using the Series 1500 controller’s user
interface. Refer to the transfer switch
operation/Installation Manual for detailed instructions
during the following procedure.
If the transfer switch is connected to an ethernet network
for Monitor III or some other application, contact your
local network administrator for assistance with the
ethernet settings in the following procedure.
Use the following procedure to configure the
communication parameters for each ATS, and to assign
the programmable input if an output from the generator
set was connected to an ATS input terminal in Section
1.6. The steps are arranged in the order that the setup
screens appear on the Series 1500 controller.
1. Navigate to the Communications Setup screen on
the Series 1500 controller. Press the right arrow
button to enter the setup and set the following
parameters. Be sure to save each setting.
The communication settings are summarized in
Figure 14.
2. MODBUS Server TCP. If the transfer switch is
connected to a PC through the ethernet connection
for Monitor III or some other application, set this to
Enable. Otherwise, select Disable.
3. MODBUS Server Port 0. Enable if the annunciator
or a PC is connected to port 0. See Figure 13.
4. MODBUS Server Port 1. Enable if the annunciator
or a PC is connected to port 1. See Figure 13.
5. MODBUS Address Port 0 and Port 1. Assign a
network address for the port connected to the
annunciator. The addresses must be numbered 1,
2, 3, and 4 in the order that the transfer switches are
connected to the annunciator, with number 1 being
closest to the annunciator.
If the other port is connected to a PC, assign that
port a different network address that is not used for
any of the annunciator ports in the network.
Communications
Setup Parameter
Possible
Settings
Annunciator
Connection Ethernet* Notes
Modbus Server TCP Enabled or
Disabled
X* Enable if using an Ethernet connection for Monitor III
Modbus Server Port 0 Enabled or
Disabled
X Enable for Modbus communication through serial port 0 on the
main logic board.
Modbus Server Port 1 Enabled or
Disabled
X Enable for Modbus communication through serial port 1 on the
main logic board.
Modbus Addr Port 0 001-247
default = 1
XAddress for RS-485 serial port 0 (on the logic board). Each port
must have a different address.
Modbus Addr Port 1 001-247
default = 2
XAddress for RS-485 serial port 1 (on the logic board). Each port
must have a different address.
Baud Rate Port 0 9600, 19200,
57600
X
Use 9600 or 19200 for annunciator communication.
Baud Rate Port 1 9600, 19200,
57600
XB
ud r
te in bits per second
or seri
l communic
tion between
the controller and a personal computer’s COM port.
Modbus TCP Unit ID 001-247
default = 3
—X* Factory-set to 3. A unit ID is required for Modbus over TCP
communication. The unit ID for TCP communication is
analogous to the Modbus address for serial communication
through the RS-485 ports.
IP Address — — X* Obtain from your local network administrator. Every device on
the network must have a unique IP address.
Subnet Mask — — X* Obtain from your local network administrator.
MAC Address Factory-set,
fixed
—X* Hardware address, entered at the factory. Not adjustable.
Appears only in the Communications View screen.
* Ethernet settings are applicable only if the ATS is connected to the Ethernet for Monitor III or applications other than annunciator
communication.
Figure 14 Series 1500 Communication Settings