koino K50 SERIES User manual

100
PID CONTROLLER
Digital PID Controller
User’s Manual
HEATING & COOLING DUAL CONTROLER
K50-SERIES

101
PID CONTROLLER

102
PID CONTROLLER
Pay attention to the followings!
Safety requirements!
WARNING
CAUTION
Thank you for purchasing the K50 series from Koino.
The K50 series is a precision industrial controller that uses an advanced
2 degree-of-freedom (DOF) algorithm.
The K50 series consists of 5 models, which are K52, K53, K54, K57, and K59.
This manual explains the installation, the functions, the operation,
and the handling of the products.
Please read the manual thoroughly before using the products.
If any difficulties arise while using our products, please contact our
Safety requirements are intended to prevent accidents and dangers through the proper use
of the products, so please heed them at all times.
The safety requirements are divided into “cautions” and “warnings”, which
indicate the following.
△
!
△
!
Serious injury or death may be caused if instructions are not observed.
Failure to observe these instructions may cause damage to the instrument or some injury
to the user.
●Use the products under the conditions specified in this manual.
●Please heed the cautions and warnings listed in this manual.
●The contents of the manual may be changed without notice.
●The product is designed to be used installed on a control panel.
●This manual is copyrighted, and may not be copied in part or in whole without permission.
●The manufacturer takes no responsibility for direct or indirect damages caused
by careless operation or operation under unpredictable or risky environments.

103
PID CONTROLLER
WARNING
△
!
CAUTION
△
!
1. Use a separate safety device when this product is used to control a device
that could harm lives or expensive property in the event of a malfunction
or a breakdown. (This may cause fires, deaths, or damage to property)
2. Do not use this controller at place where there are flammable or
explosive gas. (It may cause a fire or explosion.)
3. Before turning the power on, please check that wiring is correct to the
number of terminal. (It may cause a fire)
4. Turn off the power during wiring and maintenance to avoid an electric shock.
5. Do not touch the terminals when it is power on.
(It may give an electric shock.)
6. This controller must be mounted on the panel to avoid an electric shock.
7. Do not attempt to disassemble, modify and repair.
1. Please conduct an inspection when water has entered the product.
(It may cause short circuits, fires, and malfunction.)
2. This controller should be used indoors.
(It may shorten the controller’s life or give an electric shock.)
3. Observe the rated voltage and specification.
(It may cause a fire or shorten the controller’s life.)
4. Be careful that any of foreign materials do not inflow into the controller.
(It may cause a fire or malfunction of the controller.)
5. Do not give direct vibration or shock to the controller.
(It may cause of malfunction of the controller.)
6. Do not use chemical detergent or solvent, but use a dry towel in cleaning the controller.
(It may cause an electric shock or a fire.)
7. Please check the polarity of power before wiring and connecting the sensor.
(It may cause an electric shock or explosion.)

104
PID CONTROLLER
Contents
1. Ordering Information
2. Input ranges & Output constitutions
3. Dimensions & Panel cutouts
4. Terminal Arrangements & wirings
5. Ratings & Specifications
6. Name & Function
7. Check points before using
8. Initial installation & Min. operation procedures
9. Entering into "set menu" and Setting method
10. Flow chart (Parameter structure)
11. Easy function & Safety function
12. Functions of each setting group
[0] Control group setting
[1] Set value(SV) group setting
[2] Auto tuning(AT) group setting
[3] P.I.D group setting
[4] Heater break alarm(HBA) group setting
[5] Alarm(ALARM1,2) group setting
[6] Retransmission group setting
[7] Communication group setting
[8] Output group setting
[9] Input group setting
105
107
110
113
115
116
117
118
119
121
122
124
124
125
125
126
128
129
131
131
134
135

105
PID CONTROLLER
K 5 □-□□□
①Size
②Control mode
③Optional function
④Power supply voltage
④Power supply voltage
① Size
Code Model Size Remarks
2 K52-SERIES 48(W) × 96(H) × 77(D) Option : 0, 1, 2
3 K53-SERIES 96(W) × 48(H) × 77(D) Option : 0, 1, 2
4 K54-SERIES 48(W) × 48(H) ×99(D) Option : 0, 1, 2, 3, 4, 5, 6
7 K57-SERIES 72(W) × 72(H) × 77(D) Option : 0, 1, 2
9 K59-SERIES 96(W) × 96(H) ×77(D) Option : 0, 1
②Control mode
Code Description Remarks
S Dual Heating and Cooling control
Code Description Remarks
0 100 ~ 240 V AC General-purpose usage
1 24 V AC or DC Alternating or Direct current usage
1. Ordering Information

106
PID CONTROLLER
③Optional function
Model Code Description Remarks
K52, K53
SERIES
Basic
function
RELAY output 1, Alarm output 2,
Basic function +
(Option code)
SCR(4~20mA), SSR(Voltage pulse) 1,
RET(4~20mA Retransmission output)
0 D.I (SV2, 3) External digital input Ex) K52, K53-S00
1 Communication (RS-485, Modbus) Ex) K52, K53-S10
2 HBA(CT) Heater break alarm Ex) K52, K53-S20
K54
SERIES
Basic
function
0
RELAY output 1 (ALARM or MAIN),
SCR(4~20mA), SSR(Voltage pulse) 1
Basic function +
Option code
(0 : No option)
1 RET(4~20mA Retransmission), Alarm 2 Ex) K54-S10
2 HBA(Heater break alarm), Alarm output 2 Ex) K54-S20
3 D.I(SV2, 3) External input, Alarm output 2 Ex) K54-S30
4RET(4~20mA Retransmission),
Communication (RS-485, Modbus) Ex) K54-S40
5HBA(CT) Heater break alarm,
Communication (RS-485, Modbus) Ex) K54-S50
6D.I(SV2, 3) External input,
Communication (RS-485, Modbus Ex) K54-S60
K57
SERIES
Basic function
0
RELAY output 1, Alarm output 2,
SCR(4~20mA), SSR(Voltage pulse) 1
Basic function +
Option code
(0 : No option)
1
Communication (RS-485, Modbus),
RET(4~20mA Retransmission),
HBA(CT) Heater break alarm
Ex) K57-S10
2D.I(SV2, 3), RET(4~20mA Retransmission),
HBA(CT) Heater break alarm Ex) K57-S20
K59
SERIES
Basic function
0
RELAY output 1, Alarm output 2,
SCR(4~20mA), SSR(Voltage pulse) 1,
RET(4~20mA Retransmission)
Basic function +
Option code
(0 : No option)
1Communication (RS-485, Modbus),
HBA(CT) Heater break alarm Ex) K59-S10

107
PID CONTROLLER
2. Input ranges and output constitutions
2-1. Input ranges ※The K50 series has multiple inputs, which may be set and changed by the user.
Input type Signal Setting
Code Temperature range Accuracy Remarks
Thermocouple
(T.C)
K1 -200 ~ 1370
±0.3% of F.S +1Digit
* F.S is max. value to min.
value of each range
* Digit is minimum of display
①0~400℃range : ±10%
of F.S+1Digit
2 -199.9 ~ 999.9
J15 -200 ~ 1000
3 -199.9 ~ 999.9
E16 -200 ~ 1000
4 199.9 ~ 999.9
T 5 -199.9 ~ 400.0
R 6 0 ~ 1700
B ①7 0 ~ 1800
S 8 0 ~ 1700
L17 -200 ~ 900
9 -199.9 ~ 900.0
N 10 -200 ~ 1300
U 11 -199.9 ~ 400.0
C (W5) 12 0 ~ 2300
D (W3) 13 0 ~ 2400
RTD
JPt100
(JIS,KS)
20 -199.9 ~ 500.0
22 -200 ~ 500
Pt100
(DIN,IEC)
21 -199.9 ~ 640.0
23 -200 ~ 640
Voltage
(VDC/mVDC)
0~100 mV DC 33 0 ~ 100mV DC
-10~20 mV DC 32 -10 ~ 20 mV DC
1~5V DC 30 1~5V DC
Current 4~20mA DC 30
When using current input, use
the resistor 250on input
terminal.
How to change the interior switch when using 1~5V input
①Remove the jumper cover
on the underside of the T50,
or remove the rear case.
②Detach the jumper using
tweezers and move it to
the 1-2 pins to the left.
③Once this has been com-
pleted, put the jumper
cover back on, as shown
on the picture above.
※When using 1~5V input (30),
the interior jumper switch must be
relocated.
OTHER TYPES 1~5V DC INPUT ONLY

108
PID CONTROLLER
2-2. Output constitutions
K50 SERIES can use up to three different alarm outputs for 21 different types.
ln addition, the unique output confguration of the system allows the user to designate the output port freely, and the alarm 1~3 outputs
can be exchanged or used together.

109
PID CONTROLLER
2-2. Confguration of control output
Setting of heating and cooling control PID control mode

110
PID CONTROLLER
1) K52 (48×96 mm) Dimensions
45±0.5
92±0.5
Min. 20
Min. 30
K52 / K53 (48×96)
Panel cutouts
(Unit : mm)
2) 2) K53 (96×48 mm) Dimensions
3) K54 (48 ×48 mm) Dimensions
(Unit : mm)
45-0
+0.5
45-0
+0.5
Min. 17
Min. 17
K54 (48 ×48) Panel cutouts
3. Dimensions and panel cutouts

111
PID CONTROLLER
4) K57 (72 × 72 mm) Dimensions
5) K59 (96×96 mm) Dimensions
(Unit : mm)
K39 (96×96)
Panel cutouts
92±0.5
92±0.5
Min. 20
Min. 30
K57 (72×72) Panel cutouts
(Unit : mm)
68 ±0.5
68 ±0.5
Min. 20
Min. 30
HBA option (Heater break alarm)
Current transformer (CT) : CTL-6-S or 800:1 CT use
Panel cutouts

112
PID CONTROLLER
Installation
■K54-SERIES
■K52 / K53 / K57 / K59-SERIES
①Bore a hole in the panel, referring to the panel cutouts on the previous page.
②Insert this device into the front of the panel.
③From the rear of controller, slide the bracket over the housing.
④Push the bracket in until the device has been fixed securely onto the panel.
⑤Secure using screws on the two locations at top and bottom as shown on Figure 2.
①Bore a hole in the panel, referring to the panel cutouts on the previous page.
②Insert this device into the front of the panel.
③Insert 2 brackets, one each on the B/K holes on the top and the bottom of the device.
④Secure using screws on the two locations at top and bottom.
[Picture 1]
[Picture 1] Top side [Picture 2] Bottom side [Picture 3] Fixing completion
[Picture 2]
Turn the screw 3-4
times after contact
with panel.
Turn the screw 2-3
times after contact
with panel.
Hole of fixing screw Hole of fixing screw
B/K hole B/K hole
Direction
Fixing screw

113
PID CONTROLLER
4. Terminal arrangements and wirings
1) K52 (48×96 mm), K53 (96×48 mm)
2) K54 (48 ×48 mm)

114
PID CONTROLLER
3) K57 (72×72 mm)
4) K59 (96×96 mm)

115
PID CONTROLLER
5. Ratings and specifications
Model K50-SERIES
Power supply 100~240V AC 50~60Hz (Operating voltage range 85~265V AC)
24V AC or DC (Operating voltage range 20~28V DC)
Power consumption 6VA (Max.)
Sensor input
Thermocouple (TC) : K, J, T, E, R, B, S, L, N, U, C(W5), D(W3)
Resistance temp. detector (RTD) : KPt100(KS), JPt100(JIS), Pt100(DIN)
Current input : 4~20mA DC
Voltage input : 1~5V DC, -10~20mV DC, 0~100mV DC
Accuracy ±0.3% of FS +1Digit
Input impedance
Current input (250Ω), Voltage input (including TC) 1MΩmin.
(RTD allowable wiring resistance :
10Ωmax., but, 3 wires have a equal resistance)
Input sampling period 250ms (changeable according to SG-PID algorithm)
Control output
Relay 1c 250VAC, 3A(resistive load) Electrical life 100,000 min.
(PID output or ON/OFF output)
Voltage (S.S.R) DC15V 25mA (Built-in short protection circuit)
Voltage pulse (PID output)
Current (S.C.R) 4~20mA DC, allowable load impedance 600Ωmax. (PID output)
Control type Super 2 degree-of-freedom PID (SG-PID algorithm),
S-Fuzzy, Auto-Tuning
Digital Input ON : 1KΩmax., OFF : 100KΩmin. (SV1, 2, 3 external control input)
Retransmission output 4~20mA DC, allowable load impedance 600Ωor less.
Resolution 1/4600 PV, SV, MV[%], SPS
Alarm ALARM1, 2 1a 250V AC 3A (Resistive load)
HBA(C.T) com. HBA : 1~50A AC (Resolution 0.5A)
Communication output
2 wires RS485 totally independent insulated / Max. speed : 9,600bps
Max. connect no. 99 devices (32 devices recommended)
Support protocol : PC-Link, TL-Link, Modbus-ASCII, Modbus-RTU
Ambient temperature
and humidity
-10~50℃/ 25~85% RH
(with no condensation or icing)
Weight
(incl. B/K & accessories)
●K52, K53, K57-SERIES : 230g ●K54 : 140g ●K59 : 320g
※When option + 30g

116
PID CONTROLLER
◈Description
Name Function
①Process value Display the process value. (red color)
②Auto tuning lamp Flash every 0.5 second during auto tuning.
③Set value display Display the set value, codes, and modes.
④Control output lamp Lights when the control output is ON.
⑤SV-2 display lamp Lights when the SV 2 is displayed.
⑥Alarm output lamp Lights during the alarm is ON.
⑦Function key Use to move the menus, to store, and to operate.
⑧Shift key Use to shift the digits.
⑨Set value down key Use to decrease set value and to move the menu.
⑩Set value up key Use to increase set value and to move the menu.
SET
6. Name & Function (ex. K54-SERIES )
①Process value (PV)
Display (Red color)
③Set value (SV)
Display (green color)
⑩Set value Up key
⑨Set value Down key
⑧Shift key
⑦Storage & function key
④Control output lamp
⑤SV-2 display lamp
⑥Alarm output lamp
②Auto tuning (AT) lamp

117
PID CONTROLLER
7. Check Points before Using
1) Default values at the point of manufacture
2) 7 Segment display indications
3) Initial display on power supply (K54-SERIES basis)
The default input and output values of the product at the point of manufacture are as follows.
Input : K-Type (Sel. code 1) Output : SSR mode (Sel. code 1)
※In the case of the basic model of K34-S00 only, when SSR(1) or SCR(2) is chosen as the
output mode, Alarm 1 output will be in main relay. (Refer to page 8 for details)
Model Name
Option indication
Output type indication
Input type indication
Firmware version display
0 : Basic type (No option)
1 : RET, ALARM1, 2
2 : HBA(CT), ALARM1, 2
3 : DI(SV1, 2), ALARM1, 2
4 : RET, RS-485
5 : HBA(CT), RS-485
6 : DI(SV1, 2), RS-485
0 : RELAY ON/OFF control
1 : SSR (VOLT-PULSE) PID control
2 : SCR (4~20mA) PID control
3 : RELAY PID control
01 : K-Type (-200~1370 ℃)
02 : K-Type (-199.9~999.9 ℃)
33 : mV DC (0~100mV)

118
PID CONTROLLER
8. Initial installation and minimum operation procedures
The following are the instructions for initial installation and minimum operation procedures.
Please read the contents of this manual, including the general functions outlined here, as thoroughly as possible before operating the device.
To ensure safety and prevent wrong operation, once auto-tuning has been completed, "level-2"
(setting menu display limit) will be set automatically.
At the same time, setting menu output group(8.out) and input group(9.in) are not displayed.
If needed reset, please change to "level-3"(setting menu display limit)and operate.
Please refer to the "3) setting menu display limit" at page 22.
1)Check the external wiring diagram and specifications
(power supply and terminal arrangement)
2)Check input and output specifications!
The default setting for the K50 series at the point of manufacturer are as follows.
Input : K(CA) Type (setting code 1)
Output : SSR mode (setting code 1)
If you wish to change the input or the output type, please select the option
you desire on the input group and the output group menus.
※The input type settings must be configured first before changes to other set values are made.
When the input type is changed, all other parameters (set values) are reverted to their
factory default.
3)Select the desired set value (SV).
4)Please set auto-tuning or P, I, D values to suit the operating environment.
Auto-tuning is recommended except under special circumstances

119
PID CONTROLLER
9. Entering into "set menu" and Setting method
products are universalized input and output.
Please set up input and output type frstly and use when
install our unit.
1) Input & Output type setting
more than 3 sec.
Press
once shortly
Press once shortly
Press
once shortly
Press once shortly
②Output type setting: Select the desired output type.
①lnput type setting: Select the desired input sensor type.
(setting code 1~33/ refer to lnput ranges)
※
lf the P value is set to OFF even when the P.I.D control out put 1,2. or 3 is selected,
it operates in the ON/ OFF mode.
Other manuals for K50 SERIES
1
This manual suits for next models
5