• Check the voltage and frequency on the control panel. The voltage is the standard voltage set by the manufacturer, the load frequency of 50 cycles generator
set is about 52 cycles, the load frequency of 60 cycles machine is about 62 cycles, (the cycle of electronic ming or electronic injecon generator set can be
preset on a ideal number close to the standard cycle).
• There are 3 ways to adjust the voltage: If there is voltage regulaon potenometer on the control panel, then regulate the voltage through the potenometer;
inching regulaon can be made with one potenometer in the automac voltage transformer xed in the terminal box of AC generator;
• Change the voltage output through changing the coil of AC generator, the coil head is in the terminal box.
• When the machine is generang voltage, put phase meter one end of the open circuit switch to check the phase. This should be performed by qualied
professionals.
• Stop: Push down the emergency stop buon or “STOP” buon on the main control, the machine will stop running.
• When checking the remote control of start-up, release the emergency stop buon and remote control stop buon, then turn the control switch to the
“AUTO” posion. Input the remote control signal, the engine will be started, eliminate the remote control signal, the engine will stop.
• Aer receiving the stop instrucon, the control system will make the engine run for a period of me before stopping it automacally according to cooling
me.
• The machine will stop anyme by pressing the emergency stop buon or “STOP” buon on control panel.
• Before starng the machine again, reset the emergency stop buon clockwise; meanwhile set the control on the “STOP” posion, reset the fault buon to
eliminate the fault.
• The machine cannot be started up if the fault indicator light is sll on. Press down the reset buon on the control to restore the control system.
• Make sure the fault has been eliminated before trying to start up machine.
• Manual start-up: Make sure the emergency stop buon and stop buon of remote control have been reset. Set the control to the manual stop posion,
press down the start-up buon unl the machine is started. The diesel engine will automacally start up for 3 mes unl it is started, if it cannot run, the
control system will be locked on “Fail to Start” and the failure indicator will light.
• Demount the head or pipe of the exhaust line and disperse the white fog and exclude other faults, and then install the exhaust line again and start up the
machine.
Normal manual start-up/stop, auto-start control panel
• Check if there is any abnormal noise or shock.
• Check if the liquid and exhaust system are leaking.
• Check if there any abnormal indicaon on the control panel, especially very high temperature or very low oil pressure, the oil pressure should go into the
normal range 10 seconds aer start-up.
• Set the output open circuit switch to the ''ON'' (handle facing upward).
• Add the load
• The inial added load is up to the cooling water temperature of the motor, when the cooling water temperature of the engine is below 20°C, the inial load
can be added to 50% of the standard output, when the cooling water temperature of the engine reaches 80°C, the inial load can be added to 70-100% of
the standard output power (this depends on the machine type, some generator sets with big output (100KVA) can accept 100% inial load).
• Stop: Turn down the output open circuit switch of AC generator (pull down), the machine is without load, then the machine run for several minutes more to
cool. Then, press down the emergency stop buon or “STOP” buon of the control to stop the machine immediately.
• In case of some urgency for prompt stop, press the emergency stop buon without cung o load.
Start up of the diesel engine
• Press the emergency stop buon or set the control switch the “STOP” posion, the machine can be stopped at anyme.
• To restart the machine, reset the emergency stop buon by turning the buon clockwise and press the fault reset buon to eliminate the fault.
• The machine cannot be started up if the fault light is sll on. Press down the reset buon on the control to restore the control system. Make sure the fault
has been eliminated before trying to start up machine.
• Auto Start-up: Check if the emergency stop buon and all stop buons of remote control have reset. Set the control to the “AUTO” posion.
• Set the output switch of generator set to the “ON” posion.
• The machine is ready for auto start-up, press the “START” buon of the remote control, input the start signal, the machine will start to run, and the machine
will stop by eliminang the start signal.
Auto start-up/stop, auto start-up panel
MAINTENANCE AND REPAIR
• For standby generator sets, maintenance should be performed once a week.
• For standby generator sets which are never started, maintenance should be performed once every 2 weeks and the machine should be run for 5 minutes.
Daily maintenance and maintenance aer every operaon
Warning: Do not operate the machine with low load for long periods of me.
• Standby machines without load should be checked on a monthly basis and they should be run for 5 minutes and operated with 50% load for 1-2 hours.
Check the following every 6 months or 250 hours
• Check all fault protecon equipment.
• Clean all the exhaust holes of the baeries.