6
4 User level
User level is intended for the quick access to the most common parameters for a user.
o enter user level and to go through this level press the key .
o return from user level you must go trough all the parameters or by pressing shortly the keys .
You can configure freely the structure of user level:
• you can define which parameters and menus will be in user level,
• you can define on which position these parameters(menus) will be placed,
• the parameters and menus are displayed only in case that their showing has the meaning (e.g. the parameters of controlling
are shown only in case that output is set as the control output).
Overview of all the parameters and menus of user level
Display Procedure
PCn1 Indicates the power in % of the control output . It is displayed only then if the output 1 is set as the control output.
PCn2 Indicates the power in % of the control output 2. It is displayed only then if the output 2 is set as the control output.
AoFF Menu for switching OFF of permanent alarm. Set YES and confirm to switch OFF the permanent alarm.
Aut
Starting / ending of autotunning/automatic setting of PID parameters:
• oFF, autotunning /automatic setting of PID parameters is turned OFF.
• ht, starting of autotunning/automatic setting of PID parameters for heating
• CL, starting of autotunning/automatic setting of PID parameters for cooling.
L-r
Selection for setting of stp value:
• L, stp value is local (it is set in the controller).
• M-S, remote setting of stp value via communication line, it is used for system Master-Slave.
• CSCD, remote setting of stp value via communication line, it is used for cascade controlling
dIF Difference of remote stp value for system Master-Slave.
Range: -499 to 499 °C.
CdLo Low limit range of remote setting stp value for cascade controlling.
Range: -499 to CdhI °C.
CdhI High limit range of remote setting stp value for cascade controlling.
Range: CdLo to 2499 °C.
Pb1A Proportional band of the output , the first set of PID parameters.
Range: 1 to 2499 °C.
It1A Integral value of the output , the first set of PID parameters.
Range: oFF, 0.1 to 99.9 minutes.
dE1A Derivative value of the output , the first set of PID parameters.
Range: oFF, 0.01 to 9.99 minutes.
Pb1b Proportional band, the second set of PID parameters.
Range: 1 to 2499 °C.
It1b Integral value, the second set of PID parameters.
Range: oFF, 0.1 to 99.9 minutes.
dE1b Derivative value, the second set of PID parameters.
Range: oFF, 0.01 to 9.99 minutes.
hYS1 Hysteresis of the output , this single parameter is set only for ON/OFF control.
Range: 1 to 249 °C.
Pb2A Proportional band of the output 2.
Range: 1 to 2499 °C.
It2A Integral value of the output 2.
Range: oFF, 0.1 to 99.9 minutes.
dE2A Derivative value of the output 2.
Range: oFF, 0.01 to 9.99 minutes.
hYS2 Hysteresis of the output 2, this single parameter is set only for ON/OFF control.
Range: 1 to 249 °C.
o2Lo
Low limit of signalling. Output is activated when process value is lower than the set signalling limit.
Range:
• -499 to o2hI °C for ot2 = SGPr.
• -999 to 0 °C for ot2 = SGdE.
o2hI
High limit of signalling. Output is activated when process value is higher than the set signalling limit.
Range:
• o2Lo to 2499 °C for ot2 = SGPr.
• 0 to 999 °C for ot2 = SGdE.