Lamtec FMS Series User manual

Commissioning FMS Firing Management System
TÜV type-approval
0085 AS 0254
DIN DVGW Test mark NG-2510 AS 0324
Sensors and Systems
for Combustion Engineering

Table of Contents
2
Access levels 19
General Information 5 - 15 Entering the password 19
Validity of these instructions 5 Changing password 20
Standards 5 Changing parameters 20
For your safety 6 List of parameters
Follow the legislation on safety of appliances 6 (level 0 and 1 parameters only) 21 - 29
Purpose 7 - 8 Leakage test 30 - 31
Intended purpose of FMS 4 / FMS 5 7 - 8 Mode of operation
Application-internal output regulator (optional) 8 Integrated leakage test (option)
Application-internal O regulator (optional) 10
2Leakage test flow chart 30
Integrated leakage test (option) 30
Using these instructions 9 - 10
Purpose of these instructions 9 Venting
Preliminary clarification 9 Leakage test line over-roof 31
Finding the appropriate section 9 Calculation formula 31
Conventions 9 - 10 Suggested circuit for venting the gas line
Fault correction 10 over-roof in conjunction with the
combustion management system 31
FMS Operating principle 11 - 15
FMS digital inputs 11 Output regulator (optional) 32 - 38
FMS operating sequence 11 - 12
Pre-ventilation suppression Method of operation 32 - 34
through an external signal 12 Procedure description 32
Automatic pre-ventilation suppression 12 Weather control 32
Setting the pilot burner, serving mode 13 Set-point switch-over 33
Program monitoring time 13 Startup circuit 33
Restarting 13 Thermostat and control region 34
Leakage test (option) 13 Manual control 34
4 curve sets (option) 13
Flying curve change (option) 13 Setting the regulator 35 - 38
Automatic fuel change 13 Interpreting the display 35
Range limits 13 Control region 35
Internal load 14 Regulator behaviour 36 - 38
Manual operation 14 Examples 38
Parameterisation 14
Correction 14 Before commissioning 39
Facility for direct connection
of Namur transmitter (option) 14 Adjusting motor limit switch 39
Freedom from error of feedback signals 14
Pre-ventilation limit 14 FMS Commissioning 40 - 72
Energy-saving mode for running text display 15 Function test 40 - 41
Separate ignition point 15 Significance of FMSdigital input display 41
Integrated power control unit (option) 15
Integrated O regulation 15
2Setting control elements 42
Operation of control elements for potentiometer
Settings 16 - 30 adjustment and limit switch settings 42
Inputs 16 - 18 Programming curves 43 - 48
Significance of ID number 16 Programming the compound 43
Inputs 16 Entirely new curve, clear memory 43
Configuration sticker 16 st
Programming 1 point
Configuration number 16 (separate ignition point) 44
Condition on delivery 17 - 18 Programming with burner running 44 - 45
Assignment of sockets to inputs 17 Programming with burner stationary 45
Configuration cards (examples) 17 nd th
Programming 2 to 19 point 45
Processor card 18 Programming last top point 46
Power supply card 18 Store curve 46
Plug-in p.c. card for a continuous output 18 Check monitoring values 46
Adding points 47
Parameters 19 - 20 Changing curve point 48
Parameter setting 19

Table of Contents
3
Instrumentation for commissioning 72
O regulation 49 - 62
2Adjusting load ratings individually 73
Automatic functions control Entering an initial curve 73
during operation 49 - 50 Approaching control elements from one side 74
Adjusting the integrated O regulator (optional) 49
2Entering settings 74
Checks during burner start-up 49 Entering top setting 74
O monitoring bands 49
2Ignition delay when setting 74
O boundary curves 49
2Pre-setting load automatically 74
Dynamic probe test 50 Entering the compound curves
Probe blockage 50 with the burner stationary 75
Correction output monitoring 50 Keeping the re-circulation damper
Regulation strategy 51 - 53 closed in pre-ventilation 75
With pre-setting for load changes 52 Setting the pilot burner (servicing mode) 75
Extended regulation strategy (air shortage) 53 Switching the burner on again
via the target value 75
Connection to O meter 54
2
Via analogue interface 54
Operator controls and display 55 - 56 System Operation 76 - 89
Mode switching 55 Mode display 76 - 78
Calling up O regulation text messages 56
2Significance of modes on the FMS 76 - 77
O regulator modes 77
Commissioning 57 - 61 2
"ES" Mode progress (set-control) 78
Setting the correction range 57 Continue programming 78
Inputting the O target value curve 58
2
Calling up the correction range set 59
Calculation and setting of 4 Curve sets FMS (option) 79
control parameters-(manual) 59 Interconnection with 4 curve sets option 79
Lag time (parameters 898/900) 60
P-factor (parameter 899) 60 Checksums
Setting base value for "Deactivated Running time meter 80
control” and "Air shortage” 61 Recalling the checksums
Calling up the base value for O regulation
2and the safety times 80
deactivated/air shortage 61 Calling up running time meter 80
Automatic 61
Operation 62 Messages / Faults 81 - 89
The meaning of the additional modes 62 What happens in the event of FMS fault 81
Calling up O regulation text messages 62
2Reading off a fault 81
Resetting a fault 81
Correction 63 - 66 Calling up fault history 81
Set correction input 63 - 65 O regulation perturbed 82
2
Setting the correction range 65 Air shortage perturbation 82
Recall set correction range 65 Resetting O errors 82
2
Altering the correction range 66 Calling up O regulation error history 82
2
Correction modes 66 Fault codes 83 - 89
Run to shut-off limits 67 - 70 FMS Fault Correction
Run to shut-off limits 67 Aids 90 - 115
Checking the shut-off limits at the General Faults (A) 90 - 94
three/point step output of the FMS 67 Three-point step control output (B) 95 - 96
Checking the shut-off limits at
continuous output of the FMS 68 Continuous output (C) 97
Tolerance limits direction air deficiency 69 Load signal (D) 98 - 99
Indication for an example protocol 69 Feedback (E) 100 - 103
Checking the O influence 69
2Correction input (F) 104 - 105
Example protocol 70 Digital inputs (G) 106
Control unit faults (H) 107
Tips & Tricks 71 - 75 Leakage test 108
Programming 1st point
(ignition load point) 71 Parameters (P) 109 - 118
Programming with burner running 71 - 72
Programming with burner stationary 72
Reversing the programming 72

Table of Contents
4
with leakage test 131
FMS Fault Correction Oil operation with pilot burner
Aids O regulation 117 - 118 and ignition flame monitor 132
2Oil poeration without pilot burner 133
Parameter (P) 117 - 118
Relay module R16 134 - 137
Servicing 119 - 120 Circuit diagram type 660 R 0016 V3 134
Changing EPROMs 119 Block diagram type 660 R 0016 V4 135
Changing a data EPROM Contact plan, relay module type 660 R 0016 V3 136
or a program EPROM 119 Contact plan, relay module type 660 R 0016 V4 137
Re-entering range limits 119
Installing new software version 120 Safety interlock chain 138
Example safetz interlock chain 230V 138
Procedure for installation of Wiring of the analogue inputs 139
new software in the FMS 120
Replacing the relais module 660 R 0016 120 FMS 4 / FMS 5
Connection diagram 140 - 144
Appendix 121 - 147 Type 664 F 0010 / Type 665 F 0010 140
EMC of wiring 121 Type 664 F 0020 / Type 665 F 0020 141
Connection of screening 121 Type 664 F 0030 / Type 665 F 0030 142
PE bus bar 121 Type 664 F 0040 / Type 665 F 0040 143
Switch cabinet wiring 121 Type 664 F 0050 / Type 665 F 0050 144
Screening of leads from the field 121
FMS 4 / FMS 5
Feedback on TPS channels 122 Connection diagram
Positive connection 122 with output regulator 145
Example of positive
potentiometer connection 122 Direct connection of
Error-proof feedback 122
Examples of potentiometers 122 Namur transmitter (option) 146 - 147
Examples of servomotors 122 Extract from circuit diagram 146
External switching of the fuel control element 123 Technical data 146
Selecting a suitable sensor
for rev. speed monitoring 147
Replacing a servomotor,
replacing a potentiometer 124 - 125 Relay module
Replacing a servomotor with LAMTEC connection diagram 148
precalibration 124 Type 660 R 0013 / Type 660 R 0131 148
Replacing a complete servomotor 125 Type 660 R 0019 148
Replacing the potentiometer in a servomotor 125
Connection diagram
Switch and key combinations Modem for remote control 149
on the VMS / FMS front panel 126
Switch and key combinations General Notes 150
O regulation 127
2Technical data 151 - 152
Notes on air pressure monitor Accessories
Not on operation with and Spare Parts 156 - 157
re-circulation control elements 128 Accessories and Spare Parts for
Interconnection of the air pressure monitor 128 FMS Combustion Management System 156 - 157
Paramterisation of the
re-circulation pre-ventilation time 128
Interconnection of monitors Declaration of Conformity 158 - 159
of the re-circulation ducts 128 EC Declaration of Conformity 158
Notes on start without pre/ventilation 129 Appendix to the EC Declaration of
Conformity or EC Manufacturer's Declaration 159
Process sequence charts 130 - 133
Gas operation with pilot burner, Protocol example 160
leakage test and ignition flame monitor 130 O target value curves 161
2
Gas operation without pilot burner

5
General Information Validity of these Instructions
Validity of these instructions These instructions apply to the FMS 4 and FMS 5 Combustion Management
System in any configuration.
The software-related information relates to the software version V3.1
(recognisable from the sticker inscription on the program EPROM).
Standards The units conform to the following standards and regulations:
FMS EN 298
EN 230
where applicable
where applicable
where applicable
where applicable
EMC Directive, Low Voltage Directive
Gas Appliance Directive
Integral leakage test:
EN 1643
Test mark
gas side DIN DVGW PÜZ NG-2510 AS 0324
CE-0085 AS 0254
EN 676
EN 267
EN 12 952-8 u.-11
EN 12 953-7 u.-9

6
General Information For your safety
Follow the legislation The legislation on safety of appliances states:
on safety of appliances Follow the instructions !
Proceed only in accordance with this FMS commissioning supplement
(booklet No. D LT 6079)
Use the appliance solely for the specified purpose.
It must be operated only by trained personnel. The appliance must be
operated and serviced only by persons with the required knowledge and
training. Follow the burner manufacturer's safety rules.
Associated automatic flame guard
The unit is approved for use only with an external automatic flame guard.
The automatic flame guard type F 250 made by Hartmann & Braun is used
for testing purposes.
However, any other automatic flame guard tested in accordance with
DIN EN 298 and/or DIN EN 230 and approved for continuous operation may
be used instead of this.
Electrical connection to appliances not mentioned in these instructions
Only after consultation with the manufacturers or a qualified expert.
If an automatic flame guard not approved for continuous operation is
connected, approval of the system for continuous operation will lapse.
Liability for proper functioning of the appliance passes to the owner
or operator.
Liability for correct functioning of the appliances in every case passes to the
owner or operator, should the appliance be incorrectly operated, serviced or
repaired by persons without the requisite knowledge, or if operation is
inconsistent with the specified intended purpose.
In the event of modifications to the unit the type approval lapses. The unit's
inputs and outputs and associated modules must only be wired according
to the specifications in these instructions.
LAMTEC GmbH & Co KG will not be liable for damage or injury arising out of
a failure to observe the instructions above. The warranty and liability provisions
of the terms and conditions of sale and supply of LAMTEC GmbH & Co KG
shall not be extended by virtue of the instructions above.
Where reference is made to legislation, government regulations and
standards, these are based on the legal system of the Republic of Germany.
To be used only in a grounded power line network!

7
General Information Purpose
Intended purpose The FMS 4 / FMS 5 Combustion Management System is a control unit for
FMS 4 / FMS 5 combustion systems.
Brief description
The FMS 4 adjusts up to four control elements as a function of a control
variable (generally the burner load) according to freely programmable
curves.
The FMS 5 adjusts up to 5 control elements as a function of a control
variable according to freely programmable curves).
2 sets of curves (e.g. for oil or gas) can be filed as standard, with the
option for 4 or 8 sets of curves.
Examples of possible control elements:
- Combustion air damper - Re-circulation fan
- Combustion air fan - Flue gas damper
- Fuel quantity - Flue gas fan
- Atomiser steam
Up to 20 points can be programmed for each channel. The display is
relative between 0 and 999.
The FMS has two correction inputs for shifting the setting curves, allowing
a feedback control (e.g. O control unit) to be connected up.
2
Each output is freely configurable, either three-point step control element
output for direct actuation of a motor or constant output (on the FMS 5
th
the 5 channel is always constant). The constant output can be set to any
of the following variables:
- Current signal 0 … 20 mA
- Current signal 4 … 20 mA
- Voltage signal 0 … 10 V
The FMS 4 also has a so-called monitor output. In addition an internal
value (such as the load position of the burner or position of the gas control
element) can be outputted by means of 4 … 20 mA signal).
The FMS has one serial interface for remote control/ display via PC
(Windows software available separately) and for connection to other
system components via BUS (e.g. fault message system, O control).
2
Connections for Interbus-S, Profibus, Modbus and CAN-
BUS are available as options. Other BUS systems on request.
The FMS constantly monitors its own functioning and that of the control
elements connected.
Each analog input (control variable and feedback or correction) is freely
configurable via plug-in cards.
Alternatively:
- Potentiometer (1 5kS) - Step input (DPS)
- Current signal 0/4 … 20 mA - Namur transmitter as a two-wire system
- PT 100 - inductive sensor with switch terminals in
three-wire system
The unit is of error-proof construction.

General Information Purpose
Application - internal
output regulator
(optional)
Application - internal
O regulator
2
(optional)
The FMS contains a burner control unit with process control program.
Outputs:
-actuation of gas valves
-actuation of oil valves
-actuation of the ignition valve and ignition transformer
-fan release
-oil pre-heating
-fault signal
-signal outputs for oil and gas operation
(in the off condition, oil operation is always indicated)
The external signals to the control unit are via floating contacts or chains of
contacts.
The following signals can be pre-set:
-3 separate safety interlock circuits
-fault unlocking
-air pressure monitor
-gas pressure monitor (min.)
-flame signa
This software option makes it possible to calculate the burner's required load
setting continuously for a specified target value (referred e.g. to temperature or
pressure), through comparison with the actual value. This load setting can be
notified internally to the electronic compound as the specified value.
This software function makes it possible to regulate one or several actuators
independently of a switched-on O actual value. By using a self-optimising
2
regulator strategy, it is also possible to regulate burners with frequent load
changes.
l (pilot flame monitor and ignition flame monitor)
-pre-ventilation and ignition release
-pre-ventilation suppression
-control release
-re-circulation release
-burner on
-fuel selection
8

9
General Information Using these instructions
Purpose of these instructions These instructions are concerned exclusively with commissioning and
servicing.
Further information, for example design examples, possible uses, software
settings etc., is given in separate booklets.
Special information dealing with optional equipment on this unit is
explained in separate booklets.
Preliminary clarification To make the best use of these instructions, proceed as follows:
Check whether the settings of your FMS meet the system requirements.
You will find the settings on the sticker on the unit.
- Which physical quantities (current, resistance) and values does your
FMS need on its inputs?
- Which physical quantities (current, voltage, relay signal) and values
does the system expect on the outputs of the FMS ?
- Do the settings of the FMS match your requirements with regard to
operating behaviour (pre-ventilation, feedback etc) ?
Should these matters not be clear, please read the section "Settings”
(page 16-29)
Finding the appropriate section Determine what operation you wish to perform on the FMS.
When initially putting into operating or tracing the cause of a fault, a
function test is first recommended. You must then decide whether you
wish to program with the burner stationary or running and whether or not an
entire curve is to be programmed.
Identify your current requirement from the table of contents and turn to the
appropriate page.
Conventions Sub-headings
Serve as a guide if you can already handle the FMS and merely want to
refer to certain information again.
Lines in italics after the sub-headings
describe what the current state of the system should be. If this is not the
case, the subsequent operations will not show the desired result.
Lines in bold type
indicate an action which you are to perform.

10
General Information Using these instructions
The figures and letters in brackets (1), (2), (3), (4), (5), (6), (7), (8), (A)
and (B) relate directly to the picture of the front panel. They identify the
part on which the specified action is to be performed or on which a reaction
can be seen.
The lines in ordinary typeface below the procedural instruction describe
the reaction of the system or unit following the operation.
The figures at the right-hand margin denote a paragraph in the
"Fault Correction” section of these instructions. If the reaction indicated
does not occur, please refer to this. It describes the possible causes of
faults and how to rectify them.
___________________________________________________________________
The word in italics between two lines and the sign
are notes for a better understanding of the operation or notes on how to
avoid incorrect operation.
___________________________________________________________________
___________________________________________________________________
The lines in bold italics between two lines and the triangle
draw attention to dangers. The instructions given there must be followed.
___________________________________________________________________
If you now follow the operations step by step, paying attention to the
instructions, you will automatically be working correctly.
If any of the reactions indicated do not occur, there is a fault with the unit or
the system. You should correct the fault first before proceeding.
Fault correction Follow the instructions identified by the figures given after the fault codes
and after the procedural instructions. You may find the solution to your
problem there.
This section, however, makes no claim to completeness. Should the
actions described there not have the desired effect, the unit or parts of the
unit (e.g. front panel etc.) must be changed. If the fault still occurs you are
dealing with a fault specific to the system.
___________________________________________________________________
Tip: You can download the up-to-date version of these instructions from
http://www.lamtec.de as PDF File.
You will find the version from the letter of the booklet no.
(see the backside of this document).
Example:
DLT 6066 cD
booklet No. version language
___________________________________________________________________
CHANNEL 1 CHANNEL 2 CHANNEL 3 CHANNEL 4
ENTER
POWER OIL GAS ALARM
SETPOINT
FEEDBACK
SETPOINT
FEEDBACK
ACTUAL VALUE
FEEDBACK
ACTUAL VALUE
FEEDBACK
SETPOINT
CHANNEL 5
xxxxxx
xxx
5
4
6
A
B
7 8
3
SETTING
AUTOMATIC
CLEAR
MEMORY
O -CONTROL
2
PARAMETERISATION
MONITORIN
DISPLAY
FEUERUNGS-MANAGEMENT-SYSTEM FMS
LAMTECLAMTEC
xxx
2
1
DISPLAY CHANNEL 5
(DIGITAL INPUTS)
LOAD RATING
(CORR. INPUT)
STATUS
(CORR. RANGE)
SETPOINT
ii
i
!
i

11
General Information FMS Operating Principle
FMS Digital Inputs For the FMS to function according to the requirements of a combustion
system, the condition signals from the system must be relayed to the FMS.
These signals include:
Pre-ventilation suppression Air pressure monitor
Gas safety interlock circuit Gas pressure > min.
Oil safety interlock circuit Ignition flame
Boiler safety interlock circuit Burner on
Ignition position acknowledgement Fault reset
High firing rate acknowledgement Re-circulation On
Fuel selection Control release
Flame signal Set-point switch over
(only with integral load control unit)
For use in burner control, the FMS emits 9 digital signals, which are
converted by relay module (type 6 60 R 0016) into twelve output signals
for 230 V:
Main gas 1 Ignition valve
Main gas 2 Ignition transformer
Oil Release ignition gas line
Heated oil distribution Fan
Oil operation signal Pre-ventilation / post-ventilation
Gas operation signal Fault signal
___________________________________________________________________
FMS operating sequence The operating sequence described relates to a usual configuration of the
(for diagram of example, unit. The various parameter settings can result in a somewhat different
see appendix) sequence.
___________________________________________________________________
A signal is first sent to terminal 2 (burner ON), indicating when the burner is
to start. The FMS then interrogates the safety interlock chain for the
selected fuel and the air pressure monitor contact. If the fuel is selected via
the fuel safety interlock circuits, the FMS performs a plausibility check. If it
does not detect a satisfactory condition, a corresponding text message is
emitted and the process control stops.
If all signals are OK, the fan output is activated and the ducts run to their
bottom stop as a check. The "pre-ventilation/post-ventilation” output is
activated. Once all ducts have reached their bottom stop, they open for
aeration. Any leakage test configured runs in parallel.
In the case of control elements, aeration is used to enter and to check the
range limits. The fuel control element, after reaching its top position, runs
back into the ignition position. All other ducts remain in the open position.
The FMS now interrogates the high firing rate acknowledgement and the air
pressure monitor. If these signals are OK, the parameterised aeration time
runs. If a duct is configured for re-circulation, this opens with a time delay.
On reaching the parameterised re-circulation delay time, the pre-ventilation
time stops. As soon as the re-circulation duct has reached the aeration
position, the aeration time continues. Once this time has elapsed the
ducts run into the programmed ignition position (re-circulation fully
closed). Once all ducts have reached ignition position, the FMS
interrogates the ignition position acknowledgement. In gas operation the
gas pressure monitors must also be in a satisfactory condition prior to
ignition.
The ignition transformer is now activated alone for the duration of the
pre-ignition time (transformer start-up time).

12
General Information FMS Operating Principle
Start without pilot burner:
The main valves open and remain activated together with the ignition
transformer for the duration of the safety period. During this time the flame
signal appears.
Start with pilot burner:
The ignition valve and main gas 1 are opened. The pilot flame forms and
st
the flame signal appears. Once the 1 safety period has elapsed, the pilot
burner burns on its own. The main gas 2 then opens and remains activated
nd
in parallel with the ignition valve for the duration of the 2 safety period.
When this period has elapsed the ignition valve closes again.
When ignition is completed the re-circulation duct and the flue gas damper
run to the programmed point. Correction is activated. All ducts may run to
the programmed base load point (depending on the setting selected).
The FMS remains in the base load position until control release (terminal 4)
is given.
Following control release the FMS follows the prevailing external load.
A current signal proportional to the position of the compound is emitted as
internal load (not on FMS 5).
Withdrawal of the signal/control release during operation allows the
compound to run at base or ignition load (configurable).
Withdrawal of the terminal 2 signal is followed by shutting off. The main
valves close. (In gas operation, main gas 1 first, followed by main gas 2
with an approx. 5-second delay, in order to allow the monitoring line
between the solenoid valves to burn out. In the event of a fault shut-off,
however, they both close immediately).
If configured for post-ventilation, the air ducts open again for this period.
After the configured after-burning time the FMS again checks for a period
of 5 seconds whether the flame has gone out. If not, a fault shut-off
occurs.
The FMS then goes into "OFF” mode.
Pre-ventilation suppression The pre-ventilation range can be skipped by means of the pre-ventilation
through an external signal suppression signal (terminal 1). If the signal is present straight away at
burner start-up (terminal 2 signal), the control elements run directly to the
ignition position. In order to enter the range limits, however, pre-ventilation
should be performed once after "Clear Memory”.
Pre-ventilation suppression can only occur, however, if this function is
activated via parameters.
Automatic pre-ventilation When activated by parameters, the FMS starts after regulator switch-off
suppression automatically without pre-ventilation. Pre-ventilation is only carried out now after
fault switch-off or power failure. Using this function is subject to the regulations
applicable to the facility.

13
General Information FMS Operating Principle
Setting the pilot burner,
servicing mode
Program monitoring time
Restarting
Leakage test (option)
4 curve sets (option)
Automatic fuel change
Flying curve change
(option)
Range limits
A so-called servicing mode can be set via parameters. The control unit then
runs until the stabilisation period. In this mode 5 successive starts are
possible without the need for pre-ventilation and without a leakage test.
th
The 5 start is automatically followed by pre-ventilation and/or a leakage test.
It can be determined by way of parameters how long the FMS may take
after a start signal (terminal 2) until ignition occurs. If this length of time is
exceeded, a fault shut-off occurs. If the content of the parameter is set to
0, no fault occurs (= program monitoring time = T).
Automatic restart can be activated via parameters. The control unit attempts
a one-off restart in the event of any fault marked with * after a factory-set
period(standard:10sec).Thisrestartcanbepreventedbysettingtheperiod
to0.
n the case of firing systems according to EN 676 the parameter must
be set to "0”.
Thestandardsettingiswithoutrestart.
The control unit may optionally also perform the leakage test on the gas
valves. The leakage test can per performed before ignition and/or after
shut-off
The leakage test is performed by way of the main valves. The use of filling
and discharge valves is also possible by means of relay switching.
The FMS offers the facility for using two curve sets for each fuel
(e.g. summer/winter operation) or a mode with and without speed.
When using Option 4: Curve sets, it is possible to switch within one fuel
selection from one curve-set to the other (flying curve change). Fuel
change can only be performed via "Off”.
When switching the fuel selection switch over (terminal 75), the FMS first
moves automatically to the base load position. Then the system switches
off. Only then are the fuel selection and thus the curve set changed over. If
the "Burner on” signal is still present, the burner starts with the new fuel.
(This function is not available with Option 4: Curve sets).
st
In the 1 pre-ventilation after "Clear memory”, the FMS determines the
maximum range of travel for each control element and stores this
automatically. If no ranges limits have yet been determined, the setting (in
the case of constant outputs the feedback setting) in pre-ventilation
stands at 0 and 999 points respectively. At all further starts a check is
made to see that these range limits are correct. Should the limit switches
be shifted or the frequency converter setting changed after programming,
the range limits must be re-entered.
If the range limits cannot be determined automatically, they can also be
entered manually by way of parameters. If the FMS has no existing range
limits, it automatically takes the top and bottom point of the curve as the
limit. It then does not go beyond this.
____________________________________________________________
I
____________________________________________________________
!

14
General Information FMS Operating Principle
The internal load is the load value at which the compound currently stands.
It therefore corresponds indirectly to the output of the burner.
The internal load is displayed in addition to the external load signal.
In the "load value” position therefore both the external load (left-hand) and
the internal load (right-hand) are displayed.
The value of the internal load can be outputted via the monitor output, in
order to connect further units (e.g. O control, only on FMS 4). When
2
connecting other units, it must be remembered that the signal in itself is
not error-proof.
When switching over to "Load value” with the burner running the burner
load can be set via the FMS. The load value can then be adjusted with the
channel 1 toggle switch.
The system follows this load value in the compound.
Operating a switch other than channel 1 causes the unit to exit manual
mode again.
The person commissioning the unit can adjust various functions of the
FMS
by way of parameters (e.g. post-ventilation time). The parameters are
classified into various safety levels. With the exception of the lowest safety
level these are accessible only with a password. The parameterisation can
be undertaken both on the unit itself and by means of a PC and Windows
software.
The FMS has 2 correction inputs. An analog signal (0/4 … 20 mA) can be
connected to these for shifting the set curves (e.g. for O correction or air
2
temperature correction). The assignment of the correction to the individual
output channels and the mode of operation can be adjusted via
parameters.
If the FMS cannot perform a correction because a control element stop has
been reached, it adjusts the internal load and hence the compound until
the correction can take effect as required.
An output for controlling the speed of a combustion air fan or a
re-circulation fan etc. can be monitored by switching the pulse output of a
Namur transmitter directly to the FMS.
Continuous outputs and three-point step outputs have different feedback
requirements. In the case of continuous outputs comparisons are made
between output and feedback values in or to check the plausibility. The
units therefore do not have to be intrinsically error-free in order to form the
feedback signal. For availability reasons (minimisation of interference) the
reproducibility of the values should be as good as possible.
For technical reasons this method cannot be used in the case of
three-point step outputs. For this reason TÜV approved potentiometers
must be connected directly as feedback to the FMS. These
potentiometers must positively render the position of the damper.
Normally during pre-ventilation each control element runs as far as ist
uppermost stop. Now, by means of parameters, a limit can be set for each
channel that is not exceeded during pre-ventilation.
Internal load
Manual operation
Parameterisation
Correction
Facility for direct connection
of Namur transmitter
(option)
Freedom from error
of feedback signals
Pre-ventilation limit

15
General Information FMS Operating Principle
Energy-saving mode for The brightness of the display can be adjusted to the ambient light
running text display conditions by means of parameters.
In addition the display can be set to automatically revert to the lowest
brightness level if not operated within a given period of time.
Separate ignition point In the standard version the ignition point is situated outside the accessible
range in order to set a separate fuel/air ratio. By means of parameters,
however, the ignition point can be adjusted so that it lies on the compound
curve.
Integrated power control unit An integrated power control unit is also available as an option. Where this
(option) is used the actual temperature or the actual pressure is directly switched
instead of the load signal. The control parameters are adjusted via
parameters. It is also possible to change the setting (daytime/night time
The integral output regulator is a PID controller with special combustion
technology functions. It can be used as a fixed-value regulator or as a
weather-dependent regulator. The following signals can be set:
-Actual value (analogue)
-External temperature or some other analogue signal for target value shifting
(only in weather-dependent regulators)
-Target value switching (via zero-potential contact)
Combustion enabling by the output regulator takes place internally in the FMS
Boundary values that switch the burner on and off, need to be set via parameter
regulation -optimises combustion systems
2-saves fuel
-minimises pollutants
The main purpose of O regulation is to compensate for perturbations that
2
affect combustion. In addition, the O regulation system monitors the
2
combustion's fuel/air ratio. A message is output at once if it strays outside
the permitted limits.
The following are the main perturbing factors that affect combustion:
Air: Temperature Contamination:Burner
Pressure Boiler
Humidity
Fuel: Calorific value Mechanical systems:
Temperature Mechanical
Viscosity hysteresis
Density (free play)
Gas pressure fluctuations
The O control unit is implemented as a free-standing software module.
2
The unit compares the residual oxygen content in the exhaust gas of a
combustion system measured by means of the LT1/LT2 Lambda
transmitter (actual value) with the optimum residual oxygen content (target
value). The target values are stored in the instrument in the form of an
installation-specific curve. The control unit applies a correction until the
actual value corresponds to the target. The calculated output value of the
O control module is transmitted to the compound module as a correction
2
input signal.
operation) and to control the atmospheric conditions by switching in the
outside temperature.
setting. In this case, the startup signal is removed internally from the FMS via the
output regulator module.
The operator is alerted by the display (running text) that the output regulator
refuses to enable a startup.
Integrated O

16
Settings Inputs
Significance of ID number The ID number comprises 8 characters, e.g. 664 V 0010
The two figures before the letter denote the unit, in this case a FMS 4.
The letter denotes whether the unit is a VMS or a FMS. The penultimate
figure provides information on the unit hardware.
It also determines which connection diagram applies (see appendix).
Inputs The inputs can be configured on the backplane by means of plug-in
configuration cards. Any of the following can be connected up to each
input:
- a potentiometer in the range from 1-5 kS
- a current signal 0 … 20 mA or 4 … 20 mA
- a step signal ("OPEN CLOSE" commands)
- a frequency signal (Namur transmitter), for details see appendix
- a PT 100 element
- flame sensor module (in preparation)
- a potentiometer module (in preparation)
There is a plug-in card for each configuration. This is inserted into the
respective socket in order to configure the input.
Configuration sticker The factory setting is entered on a sticker on the side of the unit.
This corresponds either to the customer data or, if nothing was specified,
the standard setting (see condition on delivery).
The EEPROM checksums and thereby the software version are also
entered on this sticker, together with the configuration number and hence
the hardware setting.
Configuration number The configuration number is a 15-digit number, constructed according
to a fixed code.
BUS-card
input voltage
Channel 1 assignment
red. feedback channel 4
red.
red.
red.
Correction input 1
Channel 5 feedback
Load input
Channel 2 assignment
Channel 3 assignment
Channel 4 assignment
Channel 5 assignment
feedback channel 3
feedback channel 2
feedback channel 1
Correction input 2
Channel 4 feedback
Channel 3 feedback
Channel 2 feedback
Channel 1 feedback
a x b x x x x x c x x d x x x x e x f x K y y y y y
BUS-card
x = 1 ^Interbus-S
2 ^SUCOnet K-Bus
3 ^
4 ^ Profibus
5
0 ^not present
CAN-Bus
^ Modbus
K = Channel assignment
y = 1 ^Recirculation
2 ^Fuel
3 ^Air
4 ^Flue gas
5 ^mech. Compound
6 ^Steam
a, b, c or d =
Feedback, correction and load
x = 1 ^Potentiometer input 1kW...5kW
2 ^continuous signal 0/4...20mA
3 ^TPS input
4 ^Pulse input (Namur)
5 ^PT 100-input
6 ^Flame sensor input
(only on red. feedback channel 4)
7 ^continuous signal 0/4...20mA
potential separated
8 ^
0 ^unoccupied
constant signal with 24 V supply
Input voltage
x = 1 ^230 VAC
2 ^115 VAC
3 ^24 ACV
4 ^24 VDC
5 ^Special voltage

Settings Condition on delivery
Condition on delivery All units are set according to the order. Settings not evident from the
ID number or configuration number must be indicated separately.
In particular:
Outputs
- whether continuous or three-point step
- whether 0 … 10 V, 0/4 … 20 mA
- position of the outputs in the event of fault
Inputs, load, feedback
- Whether potentiometer or 0/4 … 20 mA or step
- Whether inputs are used doubled (redundant) and if so, which
(possible only if the integrated power control unit is not used)
- Whether special plug-in configuration cards
(PT 100, Namur transmitter) are used
Correction input
- Whether 0 … 20 or 4 … 20 mA or direct temperature connection
- Mode of operation, on which channel, upward or downward shift
(modifiable only via software)
Assignment of Backplane
sockets to inputs
Configuration cards
(examples)
Feedback 1
Corr. Input 1
Corr. Input 2
Load input or load
control unit value
Feedback 2
Feedback 3
Feedback 4
Feedback 5
Red. Feedback 1
Red. Feedback 2
Red. Feedback 3
Red. Feedback 4
or atmosphere control
or flame sensor module
17
R4 = 0WR4 = 0WR4 = 0W
R8 = 2K2
R10 = 2K2
R15 = 0W
R12 = 0WR12 = 0W
R11 = 0W
R16 = 0W
R17 = 0W
R15 = 0W
Potentiometer
Configuration TPS
configuration
0/4 … 20mA
configuration
TM1
R17
R18
R16
R13
R14
R15
R5
R11
R12
R10
R7
R9
R8
R4
D1
T1
C1
R6
R2
R3
D2
R1
D2
D1
R10
R12
R16
R4
R15
R8
R11
R18
R9
R7
R13
R14
R17
R1
R3
R5
R2
R6
C1
TM1
T1
TM1
R10
R12
R11
R5
R16
R18
R17R13
R15
R14
R9
R7
R4
R8
R2
R6
C1
T1
D1
D2
R3
R1

Settings Condition on delivery
Processor card
Note:
Continuous channels must all be fitted with additional cards from
channel 1 onwards
Power supply card
Plug-in p.c. card for The standard control outputs are three-point step
a continuous output (except for a possible 5-channel. This is always continuous).
Each TPS output can be reconfigured to make it continuous by plugging in
an additional card.
The jumpers serve only for hardware switching between current output
and voltage output.
The selection of 0 or 4 … 20 mA is done through the software by means
of parameters.
18
T 902
EEprom for curves
and parameters
Monitoring processor
EEprom for curves
and parameters
Main processor
Program processor
Main processor
Program EPROM
Over-voltage
processor
Sockets for contiuous additional cards
TPS
Configuration Channel 1
Transformer
Fuse 2
1 AT mA
80 C 537
Channel 2 Channel 3 Channel 4
Bridge
voltage
output
0 … 10V
Bridge
current
output
0/4...20mA
T 902

Settings Parameters
Parameter setting The parameter level can be accessed by turning to the "Parameter”
selector switch position. When working on level 1-4, this works only with
the burner stationary (i.e. no signal on the digital inputs). Only level 0 is
accessible with the burner running.
___________________________________________________________________
As a rule, the factory parameter settings are precisely tuned for the
installation for which the unit has been designed. Therefore, it is only
necessary to change parameter settings in exceptional cases.
___________________________________________________________________
Access levels The parameters are divided into four different access levels according to
function and safety classification:
Operating level (Level 0)
!Accessible without password, non-critical parameters that may possibly
have to be altered during operation.
Customer level (Level 1)
!Accessible with modifiable password (on delivery set at "0000”), access
to parameters, adjustment of which calls for technical knowledge, which
are tailored to the system and which are not altered during operation.
Service level (Level 2)
!Accessible with a fixed password, but only to personnel specially trained
in parameterisation. Access to all parameters that are not fixed on the
basis of standards and technical regulations.
Production levels (Levels 3 and 4)
!Access to all parameters (only possible through LAMTEC)
Each parameter level is protected by its own checksum. This checksum
serves to show that no changes have been made (see page 78).
Entering the password Selector switch (1) to status
Push switch (4), channel 2 and 3, up
and at the same time
push switch, channel 4, down
- the input field for the password appears on the display.
Set the appropriate password via the switch.
Acceptance key (3)
Parameters on the corresponding level are released.
Selector switch (2) to parameterisation
xxx
LAMTECLAMTEC
xxx
xxx
xxx
2
3
4
1
19
!!
!
i

Settings Parameters
Changing the password ____________________________________________________________
Only possible at customer level (level 1)
____________________________________________________________
From level 1, once accessed:
Turn selector switch (1) to Status
Simultaneously push keys (4) channel 2 and 3 upwards
and channel 4 downwards
- the display shows the password input field
Set the new password for the level
Turn selector switch (1) to Digital inputs
Press the Acceptance key (3)
- new password is set
Changing parameters Select the required parameter with Channel 3 key
Change its value with Channel 4 key
- The values are accepted immediately without further confirmation
An explanatory text for the parameters can be called up by pressing
the Acceptance key (3)
____________________________________________________________
For larger values, changes can be in x100 steps with Channel 1 key and
in x10 steps with Channel 2 key.
____________________________________________________________
xxx
LAMTECLAMTEC
xxx
xxx
xxx
3
4
1
20
i
xxx
LAMTECLAMTEC
xxx
xxx
xxx
3
i
Other manuals for FMS Series
1
This manual suits for next models
5
Table of contents
Other Lamtec Controllers manuals