Air Circuit Breakers
System ofUSERS’ Manual
80 kA
:
:/
Sr.No.:
I=
:
UeI= Ics cuIcw
UW2-40H
4 Pole 100%N4000 A12 kV80 kA70 kA55 kA500 / 550 V400 / 440 V660 / 690 V80 kA 1.0 s50 kA 3.0 s
UeI= Ics cuIcw
UW1-16N
3 Pole 100%N1600 A12 kV50 kA42 kA36 kA500 / 550 V400 / 440 V660 / 690 V50 kA 1.0 s26 kA 3.0 s
UeI= Ics cuIcw
UW1-25H
4 Pole 100%N2500 A12 kV80 kA65 kA55 kA500 / 550 V400 / 440 V660 / 690 V80 kA 1.0 s44 kA 3.0 s
Weights:Before proceeding with unpacking, it is important to know the gross weight of the breaker for properselection of handling equipment. Approx. Gross Weight of breaker with packing , adaptors & accessories (kg) 1.1 Visual InspectionBefore Unpacking,A) Inspect the carton for any damage. In case of visible damage to the carton, contact nearest L&T branch office before unpacking.B) Verify the breaker version and rating written on the carton with your order. ::RatingVersionSerial No. :Cat. No.:Fr1 3P EDO1600AAIR CIRCUIT BREAKERSYSTEM OF # 40 deg C * N08 : In Frame-1 available from 400-2000A, In Frame-3, available upto 4000A Note: All weights are with Vertical configuration of Cradle adaptorsN S kgIn (A)2000I400 -12501600 IIWeightFixedD/O4P (200% N)4P (200% N)S H S H8585132132132132127127181181195195N S HS HkgIn (A)I400-20002500Rating Specification ParametersRating Specification ParametersFrameFrameVersionVersionRated Uninterrupted current at 50deg.CRated Uninterrupted current at 50deg.CWeightFixedD/O4P (50% N)4P (50% N)11511285857979127127S HS H IIN400 - 3200 400018118113213213213213218119519550% N200% N H VIII3200 - 50002232231371372000 - 2500IIIS H123123185185Drawout
ACB
N S H NN08*/D10*/S H N/S N08/N10/H N S N08/N10/H
kg
In (A) 400-5000
4000
2500 400 - 2500 3200
I
400-1600 2000
III
II
Frame
Version
Weight Fixed
ACB 3P
4P (100%N)
3P
4P (100%N)
S H
N08*/H V
S H
60 62 69 64
64 69 69
69
76 83 8383 83 83
83 130 130
104 109 127 115
112 127 127 127 168 181 195 195
181181 181 248 248
87 91 103 98
94 103 103 103 113 125 125125 136 136
125 198 198
73 76 85 79
79 85 85
85
120 132 132132 132 132
132 143 143
Rated Uninterrupted current at 50deg.C
Rating Specification Parameters
6300#
H V
138 138
285 285
227 227
170 170
Step 3: Remove Transportation CushionStep 4: Rack-out the breaker & remove breaker from cradle (Details in Section 2.3)Step 5: Remove Cradle fixing bracket and nuts 1 and 2 (8 Nos.) as shown belowfrom both left and right sidesEnsure that no loose hardwares are left out in the cradlePacking - Cradle fixing bracketStep 1: Cut & remove the strapsStep 1: Cut & remove the strapsStep 2: Lift the carton and remove any accessories taped to thebreaker or kept loose on the palette.Step 2: Lift the carton and remove any accessories taped to thebreaker or kept loose on the palette.Step 3: Remove Breaker mounting nuts (8 Nos.) as indicated by arrows from both left and right sides21
oTemperature Range : -40 to 85 C.Do not stack more than 4 breakers one above the other.Ensure that higher frame ACBs are not stacked above lower frame ACBs.
UeI= Ics cuIcw
UW2-25N
4 Pole 100%N2500 A12 kV50 kA42 kA36 kA500 / 550 V400 / 440 V660 / 690 V50 kA 1.0 s26 kA 3.0 s
UeI= Ics cuIcw
UW2-25N
4 Pole 100%N2500 A12 kV50 kA42 kA36 kA500 / 550 V400 / 440 V660 / 690 V50 kA 1.0 s26 kA 3.0 s
2a - Type designation for Electrical Charging device (ECD)2b - Operating voltage for ECD4a - Type designation for Under- voltage release (UVR)4b - Operating voltage for UVR5a - Type designation for Closing release (CR)5b - Operating voltage for CR6a - Type designation for Shunt release (SR/SRW)6b - Operating voltage for SR/SRW12 - ON-OFF indication13 - Spring status indication04 400A06 630A08 800A10 1000A12 1250A16 1600A20 2000A25 2500A32 3200A40 4000A50 5000A63 6300ARated Uninterrupted Current (In)
UW2-25N
Version forBreakingCapacity29a -29b - Rated Uninterrupted Current29c - Rated impulse withstand voltage 29d - Utilization Category29e - Suitability for isolation29f - Standards compliance29g - Rated Service breaking capacity29h - Rated operational voltage29j - Rated short-time withstand current29k - No. of Poles & Pole details29l - Serial number of ACB29m - QR Code N 50 kA S 65 kA H 80 kA V 100 kA N08 50 kA @ 800V N10 50 kA @ 1000V
CHARGED
DISCHARGED
O
I1213UV Release415~,400VShunt Release 415~,400VClosing Release 415~,400V
Charging Device240V~,240V
3030 - Bar coded Information about the Product
Label on side of Breaker/Cradle:
29h29d29m29a29c29g29e29f29j29b29k29l
1 Frame-1 2 Frame-2 3 Frame-3Frame SizeN08 50 kA @ 800V
D10 36kA @ 1000V
N10 50 kA @ 1000V
(Microswitch)
CONNECTED
TEST
DISCONNECTED
1526 Door Racking Interlock34 Guide for16 Smart Racking Shutter16 15 Racking Handleocations25 Withdrawal Rails27 Breaker Pull-out Handle ation
Rack-out the breaker to Disconnected position. Note: After removing the racking handle (15), the racking shutter automatically recloses only in distinct ‘Connected’ / ‘Test’ and ‘Disconnected’ positions (17). Hence, Breaker cannot be closed in any Intermediate positions to ensure User safety. Keeping OFF button (11a) pressed, open the Racking Shutter (16). In case Breaker is out of the panel or the panel door is open, gently press Racking Interlock (26) to defeat it.Note: Once racking shutter is opened, the breaker can not be closed, even by an electrical closing command.Pull the breaker out using pull-out handles (27). In Maintenance position, Breaker can be removed from the cradle by two persons (Fr.1) or by using a crane (Fr.2 & 3). Please refer 1.3 Handling.CAUTIONExcessive, forceful Racking-out beyond Disconnected position may lead to Product damage. For D/O Breakers remove the Transportation Cushion (2 Nos.) & it’s instruction label,before doing racking operation of the breaker.DISCONNECTEDCONNECTEDTake out the handle
Insert the racking handle & rotate anti-clockwise
RemoveTransportation CushionRemoveCaution Flap
* With Special Cover**40 deg C# With Maintenance Electrical Life = Mechanical Life
Up to 690V ACUnit
V
V
kV
kV
Compliance
2 Hz to 13.2 Hz, +/-1mm displacement
13.2 Hz to 100 Hz, 0.7g acceleration
15g for 11 ms (Half-sine wave pulse)
IS/IEC 60947-2, EN 60947-2, IEC 60947-2
Upto 800/1000
-250C to 700C
IK 08 / IK 10*
IP 53 / IP 54*
4
B
1250
12
4
3 & 4 (50, 100, 200% N)
Yes
Ue
Ui
Uimp
Uimp
Vibration Withstand Level (IEC 60068-2-6, IEC 60947-1 (Annex Q))
Operating Temperature (IEC 60068-2-1, IEC 60947-1 (Annex Q))
Degree of Impact Protection (Breaker Front)
Shock Withstand Level (IEC 60068-2-27, IEC 60947-1 (Annex Q))
Symbol
Number of Poles
Suitability for Isolation
Intrinsic Degree of Protection (Breaker Front)
Pollution Degree Suitability
Utilization Category
Common Parameters
Rated Operational Voltage at 50/60 Hz
Rated Insulation Voltage at 50/60 Hz
Rated Impulse Withstand Voltage - Main Circuit
Rated Impulse Withstand Voltage - Auxiliary Circuit
Neutral Unit Symbol
A In
N S H N S H S H N S H N S H S H H V H V
kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
kA 42 55 65 42 55 65 55 65 42 55 70 42 55 70 55 70 70 85 70 85
kA 36 50 55 36 50 55 50 55 36 50 55 36 50 55 50 55 65 75 65 75
kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
kA 26 36 44 26 36 44 36 44 26 44 50 26 44 50 44 50 65 75 65 75
kA 105 143 176 105 143 176 143 176 105 143 176 105 143 176 143 176 176 220 176 220
kA 88 121 143 88 121 143 121 143 88 121 154 88 121 154 121 154 154 187 154 187
kA 76 105 121 76 105 121 105 121 76 110 121 76 110 121 110 121 143 165 143 165
Width - 3P mm W
Width - 4P 100% mm W
Depth mm D
Height mm H
Width - 3P mm W
Width - 4P 100% mm W
Depth mm D
Height mm H
mm
mm
100% mm
3P kg 60 62 69 67 64 69 69 69 76 76 83 83 83 83 83 83 130 130 138 138
4P 100% kg 73 76 85 79 79 85 85 85 120 120 132 132 132 132 132 132 143 143 170 170
3P kg 87 91 103 94 98 103 103 103 113 113 125 125 125 125 136 136 198 198 227 227
4P 100% kg 104 109 127 112 115 127 127 127 168 168 181 181 181 181 195 195 248 248 285 285
500010000
Drawout
ACB
Fixed
ACB
Drawout
ACB
Dimensions
Ph-N
Ph-Ph
Pitch
no. of cycles
cycles/hour
Mechanical Life - With Maintenance
Frequency of Operations - Mechanical
Electrical Life - Without Maintenance#
Frequency of Operations - Electrical
Fixed
ACB
no. of cycles
cycles/hour
Closing time
Break Time ms
Rated uninterrupted Current at 50 deg. C
Rating specific parameters
Pitch I/C - O/G
Rated Short
Time Withstand
Capacity
0.5 sec
Icw1.0 sec
3.0 sec
Ics
Rated S.C
Making Capacity
415/440V ~ 50/60 Hz
Icm500/550V ~ 50/60 Hz
660/690V ~ 50/60 Hz
FRAME
Version
Rated Ultimate
S.C. Breaking
Capacity
415/440V ~ 50/60 Hz
Icu500/550V ~ 50/60 Hz
660/690V ~ 50/60 Hz
Rated Service
S.C. Breaking
Capacity
415/440V ~ 50/60 Hz
kA500/550V ~ 50/60 Hz
660/690V ~ 50/60 Hz
I II III
400-1600 2000 2500 400-2500 3200
100% Icu
25
60
347 447 647
4000 400-5000 6300**
447 647
447 581 847
447 581 847
324 324 334
100 133 200
Gross Weight
(Max.)
2040
105
100 133 200
60
5000 5000 2000
421 421 431
433
20000 15000 10000
430
347
# With Maintenance Electrical Life = Mechanical Life
Symbol
III
N S H S/H N/S/H S/H H / V
In (A) 400-2000 2500 400-3200 4000 3200-5000
Fixed Width 4P 50% W (mm) 447 447 581 581 747
D/O Width 4P 50% W (mm) 447 447 581 581 747
Pitch Ph-N 50% N mm 100 100 133.3 133.3 150
Fixed 4P 50% N kg 79 79 85 85 132 132 137
D/O 4P 50% N kg 112 115 127 127 181 195 223
Rating Specificatio n P arameters
Frame
Version
Rated Uninterrupted Current at 50deg.C
Weight
I II
Dimensions
I III
N & S S & H S & H H
In (A) 400-1250 1600 2000 2000-2500
200% W (mm) 447 581 581 647
200% W (mm) 447 581 581 647
Pitch Ph-N 200%N mm 100 133.3 133.3 200
Fixed 4P 200%N kg 85 132 132 123
D/O 4P 200%N kg 127 181 195 185
Weight
II
Fixed ACB
Frame
Drawout ACB
Version
Rated Uninterrupted Current at 50deg. C
Dimensions
Neutra l Unit Symbol
A In
N08 D10
kA 50 _
kA _36
_
kA 50 36
kA 36 36
kA 105 _
kA _75.6
Width - 3P mm W
Width - 4P 100% mm W
Depth mm D
He ight mm H
Width - 3P mm W
Width - 4P 100% mm W
Depth mm D
He ight mm H
mm
mm
100% mm
3P kg
4P 100% kg
3P kg
4P 100% kg 181
130
143
200
20
105
100 200
100 133
115 248
400-4000
I III
50
N10
50
50
N08
50
_
N08
50
447
_105
_
II
400-3200400-2000
1000V ~ 50/60 Hz
Closing time
Break Time
ms
Ra te d uninterrupte d Current at 50 deg. C
Ra te d Short
Time Withstand
Ca pacity
1 sec
Icw
3 sec
Ics
Ra te d S.C
Making Capacity
FRAME
Vers ion
Rated Ultimate
S.C. Brea king
Ca pacity
50
_
50
50
105105
50
50 50
Ra ting specific pa ra me ters
Gross Weight
(Max.)
Pitch I/C - O/G
800V ~ 50/60 Hz
Icm
1000V ~ 50/60 Hz
Drawout
ACB
Fixed
ACB
Drawout
ACB
Fixed
ACB
Frequency of Opera tions - Mechanica l
Ele ctrica l Life - Without Ma intena nce#
Frequency of Opera tions - Electrica l
no. of cycles
cycles/hour
Ph-N
Ph-Ph
Pitch
no. of cycles
cycles/hour
Mecha nical Life - With Maintena nce
800V ~ 50/60 Hz
Icu
1000V ~ 50/60 Hz
20000
347 647
847
15000
64
79
98 198
83
132
1000 1000500
30 30 20
133
60
10000
1000
125
100% Icu
100% Icu
Dimensions
334
421 431
324
447
581
324
421
447
430
447
581
25
60
433
Ra te d Service
S.C. Brea king
Ca pacity
800V ~ 50/60 Hz
kA
347 647
847
200%N
50%N
800V/1000V AC

This manual suits for next models

9

Popular Circuit Breaker manuals by other brands

Siemens QR2 quick start guide

Siemens

Siemens QR2 quick start guide

GE AM-13.8-500-7 INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

GE

GE AM-13.8-500-7 INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

Eaton VR+ Series Supplemental instructions

Eaton

Eaton VR+ Series Supplemental instructions

ABB SACE Emax 2 manual

ABB

ABB SACE Emax 2 manual

Eaton ZB-XPLH Instruction leaflet

Eaton

Eaton ZB-XPLH Instruction leaflet

Eaton SOL20 Series installation instructions

Eaton

Eaton SOL20 Series installation instructions

ABB SACE Emax 2 manual

ABB

ABB SACE Emax 2 manual

Siemens 3VA9 7 0JA1 Series operating instructions

Siemens

Siemens 3VA9 7 0JA1 Series operating instructions

Siemens Sentron 3VA9988-0BA2 Series operating instructions

Siemens

Siemens Sentron 3VA9988-0BA2 Series operating instructions

Eaton IZM quick start guide

Eaton

Eaton IZM quick start guide

Moeller LZMB Series installation instructions

Moeller

Moeller LZMB Series installation instructions

Siemens SB Series Information and Instruction Guide

Siemens

Siemens SB Series Information and Instruction Guide

Siemens 3VF 9 424-1FA .0 operating instructions

Siemens

Siemens 3VF 9 424-1FA .0 operating instructions

Eaton Power Defense IZMX16 Instruction leaflet

Eaton

Eaton Power Defense IZMX16 Instruction leaflet

Gewiss MSXD 125 quick start guide

Gewiss

Gewiss MSXD 125 quick start guide

WEG DWB400 quick guide

WEG

WEG DWB400 quick guide

Eaton Cutter-Hammer SPB-50 instructions

Eaton

Eaton Cutter-Hammer SPB-50 instructions

Delixi NAVIGATOR DZ47L Series user manual

Delixi

Delixi NAVIGATOR DZ47L Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.