© 2021 Carrier. All Rights Reserved. LenelS2 is a part of Carrier. 4 QR50L-1039E — 4.004
Intelligent Controller LNL-X4420 Quick Reference
Pressing reset switch S2 causes the LNL-X4420 to reboot.
X = ON or OFF. All other switch settings are unassigned and reserved for future use.
* In the factory or Lenel default modes, downloaded configuration/database is not saved to flash memory.
FactoryDefaultCommunicationParameters
Interface 1 (NIC1)
• Network: static IP address: 192.168.0.251
• Subnet Mask: 255.255.0.0
• Default Gateway: 192.168.0.1
• DNS Server: 192.168.0.1
• Primary Host port: IP server, Data Security: TLS if Available, port 3001, communication address: 0
• Alternate Host Port: Disabled
Bulk Erase Configuration Memory
The bulk erase function can be used for the following purposes:
• Erase all configuration and cardholder database (sanitize board, less third party applications)
• Update OEM default parameters after OEM code has been changed
• Recover from database corruption causing LNL-X4420 board to continuously reboot
If clearing the memory does not correct the initialization problem, contact LenelS2 OnGuard Technical Support.
Bulk Erase Steps
Important: Do not remove power during steps 1-6.
1. Set S1 DIP switches: 1 & 2 "ON" and 3 & 4 "OFF."
2. Apply power to the LNL-X4420 board. LED 1 on for about 15 seconds while LNL-X4420 boots up.
3. After the LNL-X4420 boots up, watch for LEDs 1 & 2 and 3 & 4 to alternately flash at a 0.5 second rate.
4. Within 10 seconds after the above pattern starts, change switches 1 or 2 to "OFF." If these switches are not
changed, the LNL-X4420 board will power up using the OEM default communication parameters.
5. LED 2 will flash indicating that the configuration memory is being erased. Full memory erase takes up to 60
seconds, usually a lot less.
When complete, only LEDs 1 & 4 will flash for about 3 seconds.
6. The LNL-X4420 board will complete its initialization in 2 seconds after LEDs 1 & 4 stop flashing.
1 2 3 4 Definition
OFF OFF OFF OFF Normal operating mode.
ON X OFF OFF After initialization, enable default User Name (admin) and
Password
(password). The switch is read on the fly, no need to re-boot. For more
information refer to IT Security on page 8.
OFF ON OFF OFF Use factory default communication parameters. *
ON ON OFF OFF Use Lenel default communication parameters. *
Contactsystem
manufacturerfordetails. See Bulk Erase Configuration
Memory on page 4.
ON ON OFF OFF Bulk Erase prompt mode at power up. See Bulk Erase Configuration
Memory on page 4.
X X X ON Makes the LNL-X4420 report and function like an LNL-4420. To be
used in situations where the host software has not been updated to
support the LNL-X series product line.