
Page 19
Approach Method of Charge Verification
(Expansion Valve Systems, > 60°F Outdoor Temp.)
The approach method should be used to veri y the charge
a ter the normal operating pressures have been con irmed
to be within the ranges given in table 5. Do not use the apĆ
proach method i system pressures do not match the presĆ
sures given in table 5. The approach method is not valid or
grossly overĆ or undercharged systems. A ter you have
taken the outdoor ambient and liquid line temperature
readings with the unit operating in high peed, subtract
the outdoor ambient temperature rom the liquid line temĆ
perature to determine the Approach Temperature. (Liquid
line °F - Outdoor Ambient °F = Approach temperature)
The resulting di erence (Approach Temperature) should
agree with the values given in table 6. I not, add re rigerant
to lower the approach temperature or recover re rigerant
rom the system to increase the approach temperature.
TABLE 6
APPROACH METHOD
Model
No.
Liquid Temp. Minu
Ambient Temp. °F (°C)
HP29-090 9.2 + 1 (5.0 + .5)
HP29-120 11.3 + 1 (6.0 + .5)
Note - For best res lts, the same thermometer sho ld be sed to
check both o tdoor ambient and liq id temperat res.
Sy tem Operation
Heat pump and indoor blower cycle on demand rom room
thermostat. When thermostat blower switch is moved to
ON position, indoor blower operates continuously.
HP29 units are equipped with external, bellyĆband crankĆ
case heaters. The crankcase heater should be energized
24 hours be ore unit start-up to prevent compressor damĆ
age as a result o slugging.
The scroll compressor manu acturer stipulates that all heat
pumps are to be equipped with an SPST high temperature
discharge line thermostat. I the discharge line ever reachĆ
es or exceeds 275±5°F, the thermostat will open the comĆ
pressor circuit. The switch automatically resets as the line
temperature decreases to 225±5°F.
HP29 units are equipped with a high pressure switch that is
located in the discharge line o the compressor. The switch
(SPST, manual reset, normally closed) removes power
rom the compressor when discharge pressure rises above
actory setting at 410 + 10 psi.
HP29 units are equipped with a loss o charge switch that is
located in the liquid line immediately a ter the condenser
coil. The switch (SPST, auto-reset, normally closed) reĆ
moves power rom the compressor when the liquid line
pressure drops below the 25+5 psig setting. The switch auĆ
tomatically resets once the pressure reaches 55+5 psig.
Each outdoor unit is equipped with a bypass relay which
switches control o the outdoor an(s) to the low ambient
pressure switch (and low ambient thermostat on
HP29-120) during low ambient operation. The bypass
relay is wired parallel to the compressor reversing valve
and is only energized during the cooling cycle.
Each HP29 heat pump is equipped with a low ambient
pressure switch which cycles the outdoor an during low
ambient operation. The normally closed switch opens
when liquid line pressure drops to 150 + 10 psig. The switch
automatically resets when the liquid line pressure rises to
275 + 10 psig.
HP29-120 units are equipped with a sur aceĆmounted low
ambient thermostat (normally closed) which cycles one
outdoor an during low ambient cooling operation. The
switch opens on temperature all at 55 + 5°F and automatiĆ
cally resets when temperature rises to 65 + 5°F.
The defro t thermo tat, defro t pre ure witch and
the defro t control work together to ensure that the heat
pump outdoor coil does not ice excessively during the heatĆ
ing mode.
The defro t thermo tat is located on the liquid line beĆ
tween the check/expansion valve and the distributor. When
the liquid line temperature drops below 35°F, the switch
closes and signals the defro t control that a de rost cycle
is needed. I the de rost thermostat is still closed a ter the
ield-selected compressor run time (30, 60 or 90 minutes)
has been completed, a de rost cycle begins. The de rost
cycle is limited to a maximum o 14 minutes. The defrost
cycle is terminated by the defrost press re switch. The deĆ
fro t pre ure witch is located on the heating cycle vaĆ
por line (cooling/de rost cycle discharge line). The normally
closed switch opens on a pressure rise at 275 + 10 psi to
terminate a de rost cycle. The pressure switch automatiĆ
cally resets.
The de rost control includes a pressure switch sa ety circuit
that allows or the application o an additional pressure
switch. The de rost control will lock out unit operation on the
third instance (during one demand cycle) that any auto-reĆ
set switch opens this circuit. The diagnostic LEDs will indiĆ
cate a pressure switch lockout. Re er to typical unit diaĆ
gram or application o an optional loss o charge switch.
The de rost control also provides terminal connections or
an ambient thermistor and a service light. Re er to igure 18
or de rost control parts arrangement and compressor run
timing pin adjustment. Table 7 details de rost control diagĆ
nostic LED codes.
TABLE 7
DEFROST CONTROL BOARD DIAGNOSTIC CODES
Mode LED #1 LED #2
Normal Operation/
Power to board
Simultaneous
Flash
Simultaneous
Flash
Time Delay to
Protect Compressor
Alternating
Flash
Alternating
Flash
Pressure Switch Open O On
Pressure Switch
Lockout On O
Board Mal unction On On