manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Lennox
  6. •
  7. Heat Pump
  8. •
  9. Lennox XC14 Installation and operation manual

Lennox XC14 Installation and operation manual

Page 1
©2007 Lennox Industries Inc.
Corp. 0704−L2 XC14
Service Literature Revised 07−2008
XC14 SERIES UNITS
The XC14 is a high efficiency residential split−system con-
densing unit, which features a scroll compressor and
R−410A refrigerant. XC14 units are available in sizes rang-
ing from 1 1/2 through 5 tons. The series is designed for use
with an expansion valve or RFC (approved for use with
R−410A) in the indoor unit. This manual is divided into sec-
tions which discuss the major components, refrigerant sys-
tem, charging procedure, maintenance and operation se-
quence.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are sub-
ject to change.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.
WARNING
Warranty will be voided if covered equipment is re-
moved from original installation site. Warranty will
not cover damage or defect resulting from:
Flood, wind, lightning, or installation and operation
in a corrosive atmosphere (chlorine, fluorine, salt,
recycled waste water, urine, fertilizers, or other dam-
aging chemicals).
DANGER
Shock Hazard
Remove all power at disconnect
before removing access panel.
Single phase XC14 units use single-
pole contactors. Potential
exists for electrical shock resulting
in injury or death.
Line voltage exist at all components
(even when unit is not in operation).
IMPORTANT
Operating pressures of this R−410A unit are higher
than pressures in R−22 units. Always use service
equipment rated for R410A.
TABLE OF CONTENTS
General Page 1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications / Electrical Data Page 2. . . . . . . . .
I Application Page 4. . . . . . . . . . . . . . . . . . . . . . . . .
II Unit Components Page 4. . . . . . . . . . . . . . . . . .
III Refrigeration System Page 8. . . . . . . . . . . . . . .
IV Charging Page 9. . . . . . . . . . . . . . . . . . . . . . . . .
V Service and Recovery Page 21. . . . . . . . . . . . . .
VI Maintenance Page 21. . . . . . . . . . . . . . . . . . . . . .
VII Wiring and Sequence of Operation Page 22. .
Page 2
SPECIFICATIONS −1 units and 030 through 060 −2 units
General
Dt
Model No. XC14−018 XC14−024 XC14−030 XC14−036 XC14−042 XC14−048 XC14−060
Data Nominal Tonnage 1.5 2 2.5 3 3.5 4 5
Connections
(sweat)
Liquid line o.d. − in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
(sweat) Suction line o.d. − in. 3/4 3/4 3/4 7/8 7/8 7/8 1-1/8
1Refrigerant (R-410A) furnished 6 lbs. 12 oz. 7 lbs. 10 oz. 8 lbs. 0 oz. 8 lbs. 9 oz. 8 lbs. 10 oz. 10 lbs. 0 oz. 12 lbs. 0 oz.
Outdoor
Coil
Net face area -
sq ft
Outer coil 13.22 13.22 16.33 16.33 16.33 21.00 22.00
Coil sq. ft. Inner coil 12.60 12.60 15.71 15.71 15.71 20.25 21.33
Tube diameter − in. 5/16 5/16 5/16 5/16 5/16 5/16 5/16
Number of rows 2 2 2 2 2 2 2
Fins per inch 22 22 22 22 22 22 22
Outdoor
Fan
Diameter − in. 18 18 22 22 22 22 26
Fan Number of blades 4 4 4 4 4 4 4
Motor hp 1/5 1/5 1/6 1/6 1/4 1/4 1/3
Cfm 2400 2400 2900 2900 3500 3600 4400
Rpm 1100 1100 825 825 825 825 825
Watts 200 200 220 220 310 310 310
Shipping Data − lbs. 1 package 146 148 169 172 198 221 238
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V
2Maximum overcurrent protection (amps) 20 30 30 30 40 50 60
3Minimum circuit ampacity 12.3 17.9 17.2 18.7 24.1 29.0 34.8
Compressor Rated load amps 9.0 13.4 12.9 14.1 17.9 21.8 26.4
p
Power factor .96 .97 .98 .98 .94 .95 .98
Locked rotor amps 48 58 64 77 112 117 134
Condenser
Fan Motor
Full load amps 1.0 1.0 1.1 1.1 1.7 1.7 1.8
Fan Motor Locked rotor amps 1.9 1.9 2.1 2.1 3.1 3.1 2.9
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Crankcase Heat-
er
93M05    
er 93M06 Factory Factory
Compressor Hard Start Kit 10J42 
88M91      
Compressor Low Ambient Cut−Off 45F08 
Compressor Time−Off Control 47J27 
Freezestat 3/8 in. tubing 93G35 
5/8 in. tubing 50A93       
Indoor Blower Off Delay Relay 58M81 
Loss of Charge Switch Kit 84M23 
Low Ambient Kit 34M72 
Refrigerant
Line Sets
L15−41−20, L15−41−30,
L15−41−40, L15−41−50
  
L15−65−30, L15−65−40,
L15−65−50
  
Field Fabricate 
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
1Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2HACR type circuit breaker or fuse.
3Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 3
SPECIFICATIONS 018, 024 −2 units & 030 through 060 −3 units
General
Dt
Model No. XC14−018 XC14−024 XC14−030 XC14−036 XC14−042 XC14−048 XC14−060
Data Nominal Tonnage 1.5 2 2.5 3 3.5 4 5
Connections
(sweat)
Liquid line o.d. − in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
(sweat) Suction line o.d. − in. 3/4 3/4 3/4 7/8 7/8 7/8 1-1/8
1Refrigerant (R-410A) furnished 5 lbs. 11 oz. 6 lbs. 8 oz. 6 lbs. 11 oz. 6 lbs. 11 oz. 8 lbs. 10 oz. 10 lbs. 0 oz. 12 lbs. 0 oz.
Outdoor
Coil
Net face area -
sq ft
Outer coil 13.22 18.67 21.00 21.00 16.33 21.00 22.00
Coil sq. ft. Inner coil − − − − − − − − − − − − 15.71 20.25 21.33
Tube diameter − in. 5/16 5/16 5/16 5/16 5/16 5/16 5/16
Number of rows 1 1 1 1 2 2 2
Fins per inch 26 26 26 26 22 22 22
Outdoor
Fan
Diameter − in. 18 22 22 22 22 22 26
Fan Number of blades 3 3 3 3 4 4 4
Motor hp 1/10 1/6 1/6 1/6 1/4 1/4 1/3
Cfm 2270 3160 3160 3160 3500 3600 4400
Rpm 1050 850 850 850 825 825 825
Watts 165 215 215 215 310 310 310
Shipping Data − lbs. 1 package 163 203 215 217 243 272 290
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V
2Maximum overcurrent protection (amps) 25 30 30 30 40 50 60
3Minimum circuit ampacity 15.7 17.9 17.2 18.7 24.1 29.0 34.8
Compressor Rated load amps 9.0 13.4 12.9 14.1 17.9 21.8 26.4
p
Power factor .93 .97 .98 .98 .94 .95 .98
Locked rotor amps 48 58 64 77 112 117 134
Condenser
Fan Motor
Full load amps 0.7 1.1 1.1 1.1 1.7 1.7 1.8
Fan Motor Locked rotor amps 1.4 2.1 2.1 2.1 3.1 3.1 2.9
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Crankcase Heat-
er
93M04    
er 93M06 Factory Factory
Compressor Hard Start Kit 10J42 
88M91      
Compressor Low Ambient Cut−Off 45F08 
Compressor Time−Off Control 47J27 
Freezestat 3/8 in. tubing 93G35 
5/8 in. tubing 50A93       
Indoor Blower Off Delay Relay 58M81 
Loss of Charge Switch Kit 84M23 
Low Ambient Kit 34M72 
Refrigerant
Line Sets
L15−41−20, L15−41−30,
L15−41−40, L15−41−50
  
L15−65−30, L15−65−40,
L15−65−50
  
Field Fabricate 
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
1Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2HACR type circuit breaker or fuse.
3Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 4
I − APPLICATION
XC14 condensing units are available in 1 1/2, 2, 2 -1/2, 3,
3 -1/2, 4 and 5 ton capacities. All major components (indoor
blower and coil) must be matched according to Lennox rec-
ommendations for the compressor to be covered under war-
ranty. Refer to the Engineering Handbook for approved sys-
tem matchups.
II − UNIT COMPONENTS
Unit components are illustrated in figure 1.
XC14 PARTS ARRANGEMENT
FIGURE 1
HR1
Crankcaseheater
(−048 & −060) S4 High
Presure
Switch
Vapor Line
Service Valve
Liquid Line
Service Valve
Muffler
Drier
S40
Crankcaseheater
Thermostat
(−048 & −060)
S5
Discharge
Line
Thermostat
CAUTION
To prevent personal injury, or damage to panels, unit
or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow
all removed panels out of the way, so that the panels
will not cause injury to personnel, nor cause damage
to objects or structures nearby, nor will the panels be
subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any
weather conditions, especially windy conditions, that
may cause panels to be blown around and battered.
Detail
A
Detail C
Detail
B
FIGURE 2
Removing/Installing Louvered Panels
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT
AS POSSIBLE) WHILE INSTALLING PANEL.
PREFERRED ANGLE
FOR INSTALLATION
Detail D
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE PANEL
SCREW
HOLES
ANGLE MAY BE TOO
EXTREME
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
LIP
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab
is for alignment and not designed to support weight of panel.
Panel shown slightly rotated to allow top tab to exit (or enter) top
slot for removing (or installing) panel.
Remove the louvered panels as follows:
1.Remove 2 screws, allowing the panel to swing open slight-
ly (see figure 2).
2.Hold the panel firmly throughout this procedure. Ro-
tate bottom corner of panel away from hinge corner post
until lower 3 tabs clear the slots (see figure 2, Detail B).
Page 5
3.Move panel down until lip of upper tab clears the top slot
in corner post (see figure 2, Detail A).
Position and Install PanelPosition the panel almost par-
allel with the unit (figure 2, Detail D) with the screw side" as
close to the unit as possible. Then, in a continuous motion:
Slightly rotate and guide the lip of top tab inward (figure 2,
Details A and C); then upward into the top slot of the
hinge corner post.
Rotate panel to vertical to fully engage all tabs.
Holding the panel’s hinged side firmly in place, close the
right−hand side of the panel, aligning the screw holes.
When panel is correctly positioned and aligned, insert the
screws and tighten.
A − Control Box (Figure 3)
XC14 units are not equipped with a 24V transformer. All 24
VAC controls are powered by the indoor unit. Refer to wir-
ing diagram.
Electrical openings are provided under the control box cov-
er. Field thermostat wiring is made to color-coded pigtail
connections.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic com-
ponents. Take precautions during unit installation
and service to protect the unit’s electronic controls.
Precautions will help to avoid control exposure to
electrostatic discharge by putting the unit, the con-
trol and the technician at the same electrostatic po-
tential. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface be-
fore performing any service procedure.
FIGURE 3
DUAL CAPACITOR
(C12)
COMPRESSOR
CONTACTOR
(K1)
CONTROL BOX
GROUNDING
LUG
1 − Compressor Contactor (K1)
The compressor is energized by a single−pole contactor lo-
cated in the control box. See figure 3. K1 is energized by the
indoor thermostat terminal Y1 (24V) when thermostat de-
mand is present.
2 − Dual Capacitor (C12)
The compressor and fan in XC14 series units use perma-
nent split capacitor motors. The capacitor is located in-
side the unit control box (see figure 3). A single dual" ca-
pacitor (C12) is used for both the fan motor and the com-
pressor (see unit wiring diagram). The fan side and the
compressor side of the capacitor have different MFD rat-
ings. See side of capacitor for ratings.
3 − Timed Off Control TOC (option) (A4)
The time delay is electrically connected between thermostat
terminal Y and the compressor contactor. Between cycles,
the compressor contactor is delayed for 5 minutes ±2 min-
utes but may last as long as 8 minutes. At the end of the
delay, the compressor is allowed to energize. When thermo-
stat demand is satisfied, the time delay opens the circuit to
the compressor contactor coil and the compressor is de−en-
ergized.
4 − Start Kit (option)
The start kit consist of a potential relay K31 and start capaci-
tor C7. The potential relay controls the operation of the start-
ing circuit. The relay is normally closed when contactor K1 is
de−energized. When K1 is energized, the compressor im-
mediately begins start up. K31 remains closed during com-
pressor start up and capacitor C7 remains in the circuit.
When compressor reaches approximately 75% of its speed,
K31 is energized. When K31 energizes, the contacts open
and start capacitor C7 is taken out of the circuit.
Page 6
B − Compressor (B1)
The scroll compressor used in all XC14 model units, is de-
signed for use with R410A refrigerant and operation at high
pressures. Compressors are shipped from the factory
charged with 3MA (32MMMA) P.O.E. oil. All XC14 compres-
sors are equipped with a factory installed sound cover made
of polyethylene containing a 2 inch thick batt of fiberglass in-
sulation. See figure 5.
See ELECTRICAL DATA table at the front of this manual or
compressor nameplate for compressor specifications.
The scroll compressor design is simple, efficient and requires
few moving parts. A cutaway diagram of the scroll compressor
is shown in figure 4. The scrolls are located in the top of the
compressor can and the motor is located just below. The oil lev-
el is immediately below the motor.
FIGURE 4
SCROLL COMPRESSOR
DISCHARGE
SUCTION
The scroll is a simple compression concept centered around
the unique spiral shape of the scroll and its inherent properties.
Figure 6 shows the basic scroll form. Two identical scrolls are
mated together forming concentric spiral shapes (figure 7). One
scroll remains stationary, while the other is allowed to "orbit" (fig-
ure 8). Note that the orbiting scroll does not rotate or turn but
merely orbits the stationary scroll.
NOTE − During operation, the head of a scroll compressor may
be hot since it is in constant contact with discharge gas.
FIGURE 5
SOUND COVER
COMPRESSOR
SOUND PAD
FIGURE 6
SCROLL FORM
FIGURE 7
STATIONARY SCROLL
ORBITING SCROLL
DISCHARGE
SUCTION
CROSS−SECTION OF SCROLLS
TIPS SEALED BY
DISCHARGE PRESSURE
DISCHARGE
PRESSURE
Page 7
12
34
SUCTION
POCKET
SUCTION
ORBITING SCROLL
STATIONARY SCROLL
SUCTION SUCTION
DISCHARGE
POCKET
SUCTION INTERMEDIATE PRESSURE
GAS
CRESCENT
SHAPED
GAS POCKET
HIGH PRESSURE GAS
FLANKS SEALED
BY CENTRIFUGAL
FORCE
MOVEMENT OF ORBIT
FIGURE 8
The counterclockwise orbiting scroll draws gas into the outer
crescent shaped gas pocket created by the two scrolls (figure 8
− 1). The centrifugal action of the orbiting scroll seals off the
flanks of the scrolls (figure 8 − 2). As the orbiting motion contin-
ues, the gas is forced toward the center of the scroll and the gas
pocket becomes compressed (figure 8 − 3). When the com-
pressed gas reaches the center, it is discharged vertically into a
chamber and discharge port in the top of the compressor (figure
6). The discharge pressure forcing down on the top scroll helps
seal off the upper and lower edges (tips) of the scrolls (figure 6).
During a single orbit, several pockets of gas are compressed
simultaneously providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid return. If
liquid enters the scrolls, the orbiting scroll is allowed to separate
from the stationary scroll. The liquid is worked toward the center
of the scroll and is discharged. If the compressor is replaced,
conventional Lennox cleanup practices must be used.
Due to its efficiency, the scroll compressor is capable of draw-
ing a much deeper vacuum than reciprocating compressors.
Deep vacuum operation can cause internal fusite arcing
resulting in damaged internal parts and will result in com-
pressor failure. Never use a scroll compressor for eva-
cuating or pumping−down" the system. This type of dam-
age can be detected and will result in denial of warranty
claims.
The scroll compressor is quieter than a reciprocating com-
pressor, however, the two compressors have much different
sound characteristics. The sounds made by a scroll compres-
sor do not affect system reliability, performance, or indicate
damage.
C − Drier
A filter drier designed for all XC14 model units must be
installed in the liquid line. The field installed drier is designed
to remove moisture, which can lead to compressor failure.
Any time unit is exposed to open air due to service, drier
must be replaced. All replacement driers must be ap-
proved for R410A refrigerant.
D − Condenser Fan Motor (B4)
Make sure all power is disconnected before
beginning electrical service procedures.
DANGER
All units use single−phase PSC fan motors which require a run
capacitor. In all units, the condenser fan is controlled by
the compressor contactor.
ELECTRICAL DATA tables in this manual show specifi-
cations for condenser fans used in XC14’s.
Access to the condenser fan motor on all units is gained
by removing the four screws securing the fan assembly.
See figure 9. The grill fan assembly can be removed from
the cabinet as one piece. See figure 10. The condenser
fan motor is removed from the fan guard by removing the
four nuts found on top of the grill. See figure 10 if con-
denser fan motor replacement is necessary.
Page 8
FIGURE 9
Remove
screws
Remove
screws
FIGURE 10
E − Discharge Line Thermostat (S5)
The discharge line thermostat is NC, auto re−set and located
on the discharge line of the compressor. The switch opens
when discharge line temperatures exceeds the factory set-
ting of 220° + 5° F and shuts down the compressor.
F − High Pressure Switch (S4)
XC14 units are equipped with a high pressure switch that is
located in the liquid line of the compressor. The switch
(SPST, manual reset, normally closed) removes power from
the compressor contactor control circuit when discharge
pressure rises above factory setting at 590 + 10 psi.
G − Crankcase Heater (HR1) &
Thermostat (S40) 4 and 5 ton only
XC14−048 and −060 units are equipped with a 70 watt belly
band type crankcase heater. HR1 prevents liquid from accu-
mulating in the compressor. HR1 is controlled by a thermo-
stat located on the liquid line. When liquid line temperature
drops below 50° F the thermostat closes energizing HR1.
The thermostat will open, de−energizing HR1 once liquid line
temperature reaches 70° F.
H − Loss of Charge Switch (option) (S24)
The loss of charge switch is NC, auto re−set and located on
the suction line of the compressor.The switch opens when
suction line pressure drops to 25psi + 5 (shutting down the
compressor) and will close when suction line pressure rises
to 55psi + 5.
III − REFRIGERANT SYSTEM
A − Plumbing
Field refrigerant piping consists of liquid and suction lines
from the condensing unit (sweat connections) to the indoor
evaporator coil (sweat connections). Use Lennox L15
(sweat) series line sets as shown in table 1.
TABLE 1
Unit Liquid
Line
Suction
Line
L15 Line
Sets
018, −024,
−030,
3/8 in.
(10 mm)
3/4 in.
(19 mm)
L15−41
20 ft. − 50 ft.
(6 m − 15 m)
−036, −042,
−048
3/8 in.
(10 mm)
7/8 in.
(22 mm)
L15−65
30 ft. − 50 ft.
(9 m − 15 m)
−060 3/8 in.
(10 mm)
1−1/8 in.
(29 mm)
Field
Fabricated
The liquid line and vapor line service valves (figures 11 and
12) and gauge ports are accessible from the outside of the
unit. Use the service ports for leak testing, evacuating,
charging and checking charge.
Each valve is equipped with a service port which has a facto-
ry−installed Schrader valve. A service port cap protects the
Schrader valve from contamination and serves as the pri-
mary leak seal. Service valves are not rebuildable. If a valve
has failed, you must replace it.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench.
2 − Connect gauge to the service port.
3 − When testing is complete, replace service port cap. Tight-
en finger tight, then an additional 1/6 turn.
To Open Service Valve:
1 − Remove the stem cap with an adjustable wrench.
2 − Using the adjustable wrench to keep the valve station-
ary, use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for 3/8" line
sizes or a 5/16" extension for large line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Page 9
To Close Service Valve:
1 − Remove the stem cap with an adjustable wrench.
2 − Using the adjustable wrench to keep the valve station-
ary, use a service wrench with a hex−head extension to
turn the stem clockwise to seat the valve. Tighten the
stem firmly.
NOTE − Use a 3/16" hex head extension for 3/8" line
sizes or a 5/16" extension for large line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
NOTE − Stem cap must be replaced to help prevent
valve leakage.
Service Valve
(Valve Closed)
Schrader valve open
to line set when valve is
closed (front seated)
service
port
service
port cap
stem cap
insert hex
wrench here
(valve front seated)
to outdoor coil
to indoor coil
Service Valve
(Valve Open)
Schrader
valve
service
port
service port
cap
insert hex
wrench here
to indoor coil
to outdoor coil
stem cap
FIGURE 11
Vapor Line Ball Valve – 5 Ton Units Only
Vapor line service valves function the same way as the other
valves, the difference is in the construction. A ball valve is
illustrated in figure 12.
The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−free
seal.
Ball Valve (Valve Open)
FIGURE 12
Schrader valve
service port
service port
cap
stem cap
stem
Use Adjustable Wrench
To open: rotate Stem Clockwise 90°.
To close: rotate Stem Counter-clockwise 90°.
ball
(shown open)
to outdoor coil
to indoor coil
IV − CHARGING
WARNING
R−410A refrigerant can be harmful if it is inhaled.
R−410A refrigerant must be used and recovered re-
sponsibly.
Failure to follow this warning may result in personal
injury or death.
A − Leak Testing
After the line set has been connected to the indoor and out-
door units, check the line set connections and indoor unit
for leaks.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting
of (CFC’s and HFC’s) as of July 1, 1992. Approved
methods of recovery, recycling or reclaiming must be
followed. Fines and/or incarceration my be levied for
noncompliance.
Page 10
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could re-
sult in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open flame,
can cause damage by fire and/or an ex-
plosion, that could result in personal
injury or death.
WARNING
Danger of explosion!
When using a high pressure gas such
as dry nitrogen to pressurize a refriger-
ant or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
Using an Electronic Leak Detector
1 − Connect a cylinder of R−410A to the center port of the
manifold gauge set. Connect manifold gauge to service
valve port.
2 − With both manifold valves closed, open the valve on the
R−410A cylinder.
3 − Open the high pressure side of the manifold to allow the
R−410A into the line set and indoor unit. Weigh in a trace
amount of R−410A. [A trace amount is a maximum of 2
ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the
valve on the R−410A cylinder and the valve on the high
pressure side of the manifold gauge set. Disconnect the
R−410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R−410A
mixture. Correct any leaks and recheck.
B − Evacuating
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.
NOTE − This evacuation process is adequate for a new
installation with clean and dry lines. If excessive mois-
ture is present, the evacuation process may be required
more than once.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.
1 − Connect manifold gauge set to the service valve ports :
 low pressure gauge to vapor line service valve
 high pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercury).
During the early stages of evacuation, it is desirable to
close the manifold gauge valve at least once to deter-
mine if there is a rapid rise in absolute pressure. A rap-
id rise in pressure indicates a relatively large leak. If this
occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total
actual pressure within a given volume or system, above
the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacu-
um pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the air from the hose with nitrogen. Open the
manifold gauge valves to break the vacuum in the line
set and indoor unit. Close the manifold gauge valves.
Page 11
CAUTION
Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing and
compressor failure.
Damage caused by deep vacuum operation will void
warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge
valves to release the nitrogen from the line set and in-
door unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not rise
above 500 microns (29.9 inches of mercury) within a
20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R−410A
refrigerant. Open the manifold gauge valves to break the
vacuum from 1 to 2 psig positive pressure in the line set
and indoor unit. Close manifold gauge valves and shut
off the R−410A cylinder and remove the manifold gauge
set.
C − Charging −1 units and 030 through 060 −2
Polyol Ester Oil
IMPORTANT
Mineral oils are not compatible with R−410A. If oil
must be added, it must be a polyol ester oil.
The compressor is charged with sufficient polyol es-
ter oil. If oil must be added to the compressor in the
field, Copeland has approved Mobil EALtArctic
22CC and ICI EMKARATEtRL32CF.
This system uses R−410A refrigerant which operates at
much higher pressures than HCFC−22. The provided liquid
line filter drier is approved for use with R−410A. Do not re-
place it with components designed for use with HCFC−22.
This unit is NOT approved for use with coils which use capil-
lary tubes as a refrigerant metering device.
Factory Charge
Units are factory-charged with the amount of R−410A refrig-
erant indicated on the unit rating plate. This charge is based
on a matching indoor coil and outdoor coil with 15 ft. (4.6 m)
line set. For varying lengths of line set, refer to table 2 for re-
frigerant charge adjustment.
TABLE 2
Liquid Line Set
Diameter
Ounces per 5 feet (g per 1.5 m) adjust
from 15 feet (4.6 m) line set*
3/8 in. (9.5 mm) 3 ounce per 5 ft. (85 g per 1.5 m)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.
Page 12
Units Delivered Void of Charge
If the system is void of refrigerant, clean the system using
the procedure described below.
1.Use nitrogen to pressurize the system and check for
leaks. Repair leaks, if possible.
2.Evacuate the system to remove as much of the moisture
as possible.
3.Use nitrogen to break the vacuum and install the provided
filter drier in the system.
4.Evacuate the system again. Then, weigh the appropriate
amount of R−410A refrigerant (listed on unit nameplate)
into the system.
5.Monitor the system to determine the amount of moisture
remaining in the oil. Use test kit 10N46 to verify that the
moisture content is within the kit’s dry color range. It
may be necessary to replace the filter drier several
times to achieve the required dryness level. If system
dryness is not verified, the compressor will fail in
the future.
Pre−charge Airflow Check of Temperature Drop
across Evaporator Coil (Delta−T)
NOTE − Be sure that filters and indoor and outdoor coils are
clean before testing
Measure the entering air dry bulb (DB) and wet bulb (WB)
temperatures at the indoor coil. Find Delta−T in table 3. Mea-
sure evaporator coil’s leaving air DB and subtract that value
from the entering air DB. The measured difference should
be within +3ºF (+1.8ºC) of table value. If Delta−T is too low,
decrease the indoor fan speed (refer to indoor unit for infor-
mation). If the Delta−T is high, increase the indoor fan speed.
Repeat charging procedure and Delta−T (air flow adjust-
ment) procedure until both are correct.
Example:
Assume entering air DB − 72, WB − 64, leaving DB − 53.
Delta−T should be 15 (per table); delta across coil is 19 (72
minus 53) which is 4ºF higher than table value; therefore, in-
crease fan speed.
TABLE 3
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
Dry bulb
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
Dry
bulb
temperature 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
temperature
of air entering
indoor coil
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
indoor coil 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Wet bulb temperature of air entering indoor coil
Page 13
WHEN TO CHARGE?
Warm weather best
Can charge in colder weather
CHARGE METHOD? Determine by:
Metering device type
Outdoor ambient temperature
REQUIREMENTS:
Sufficient heat load in structure
Indoor temperature between 70-80ºF (21−26ºC)
Manifold gauge set connected to unit
Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure vapor line temperature
TXV RFC
APPROACH OR
SUBCOOLING
WEIGH-IN SUPERHEAT
Which
metering
device?
Below 65ºF
(18ºC)?
Above 40ºF
(4ºC)?
Above 65ºF
(18ºC)?
START: Determine how refrigerant is metered
FIGURE 13 When to charge, method to use, conditions & equipment required
IMPORTANT
Before attempting to charge any system, confirm proper airflow across the in-
door coil. Airflow over the indoor coil can be determined by measuring the stat-
ic pressure drop across the coil and comparing it with the factory table pro-
vided in the indoor coil installation instructions.
If value is greater than
shown, add refrigerant;
if less than shown,
remove refrigerant.
ABOVE
Outdoor
ambient 40ºF
(4ºC)?
START: Measure outdoor ambient temperature
BELOW
Check Liquid and Vapor line pressures
Compare unit pressures with Normal
Operating Pressures table 4, page 15.
(Table 4 is a general guide. Expect minor pressures
variations. Significant differences may mean improp-
er charge or other system problem.)
Use SUPERHEAT to correctly charge unit
or to verify the charge is correct.
NOTE − Do not at-
tempt to charge sys-
tem where a dash ap-
pears, system could
be overcharged. Su-
perheat is taken at va-
por line service port.
Vapor line superheat
must never be less
than 5ºF at the vapor
line service port.
USE WEIGH-IN METHOD
Weigh-in or remove refriger-
ant based upon line length
SHº (Superheat) Values (+/−5ºF)
Wet Bulb (air entering indoor coil)
ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76
40 15 18 20 23 26 29 32 34 38 41 43 46 48 51
45 13 16 18 21 24 27 30 33 36 39 41 44 46 49
50 11 14 16 19 22 25 28 31 34 37 39 42 44 47
55 9 12141720232730333638404244
60 7 10121518212427303335384043
65 - 6 10 13 16 19 21 24 27 30 33 36 38 41
70 - - 7 1013161921242730333639
75 - - - 6 9 121518212428313437
80 - - - - 5 8 12 15 18 21 25 28 31 35
85 - - - - - - 8 11151922263033
90 - - - - - - 5 9 13 16 20 24 27 31
95 - - - - - - - 6 10 14 18 22 25 29
100 --------81216212428
105 - - - - - - - - 5 9 13 17 22 26
110 ---------611152025
115 ----------8141824
* Dry−bulb temperature (ºF) of entering outdoor ambient air.
If refrigerant added or
removed, retest to
confirm that unit is
properly charged
SUPERHEAT METHOD
Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
Connect gauge set
When heat demand is satisfied, set
thermostat to call for cooling
Allow temperatures and pressures to
stabilize
Record vapor line pressure; use value to
determine saturation temperature
(table 5 on page 15) SATº =
Record vapor line
temperature VAPº =
Subtract to determine superheat (SHº):
VAPº − SATº = SHº
Record the wet bulb temperature (air
entering indoor coil) WB =
Record outdoor ambient temperature
Compare results with table
FIGURE 14 Charging RFC units with Superheat Method
Page 14
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060
65 (18) 3 (1.7) 5 (2.8) 4 (2.2) 5 (2.8) 6 (3.3) 7 (3.9) 8 (4.4)
75 (24) 5 (2.8) 6 (3.3) 5 (2.8) 5 (2.8) 8 (4.4) 8 (4.4) 9 (5.0)
85 (29) 6 (3.3) 6 (3.3) 6 (3.3) 6 (3.3) 8 (4.4) 8 (4.4) 9 (5.0)
95 (35) 6 (3.3) 7 (3.9) 6 (3.3) 6 (3.3) 8 (4.4) 8 (4.4) 9 (5.0)
105 (41) 6 (3.3) 6 (3.3) 6 (3.3) 5 (2.8) 8 (4.4) 8 (4.4) 9 (5.0)
115 (45) 6 (3.3) 6 (3.3) 6 (3.3) 6 (3.3) 8 (4.4) 9 (5.0) 9 (5.0)
*Temperature of air entering outdoor coil
APPROACH METHOD
Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
Connect gauge set
When heat demand is satisfied, set
thermostat to call for cooling
Allow temperatures and pressures to
stabilize
Record outdoor ambient
temperature AMBº =
Record line temp. LIQº =
Subtract to determine approach (APPº):
LIQº − AMBº = APPº
Compare results with table
DO NOT CHARGE UNIT
(Results of charging at low
temperatures not reliable)
ABOVE
START: Measure outdoor ambient temperature
BELOW
Check Liquid and Vapor line pressures
Compare unit pressures with Normal
Operating Pressures table 4, page 15.
(Table 4 is a general guide. Expect minor pressures
variations. Significant differences may mean improp-
er charge or other system problem.)
Use APPROACH to correctly charge unit or
to verify the charge is correct.
USE WEIGH-IN METHOD
Weigh-in or remove refriger-
ant based upon line length
APPº (Approach) Values(F:+/−1.0°; [C: +/−0.5°])
Above or
below 65ºF
(18ºC)?
If refrigerant added or
removed, retest to
confirm that unit is
properly charged
If value is greater than shown (high
approach), add refrigerant; if less
than shown (liquid temp too close to
ambient temp, low approach), remove
refrigerant.
FIGURE 15 Charging TXV units with Approach Method
DO NOT CHARGE UNIT
(Results of charging at low
temperatures not reliable)
ABOVE
START: Measure outdoor ambient temperature
BELOW
Check Liquid and Vapor line pressures
Compare unit pressures with Normal
Operating Pressures table 4, page 15.
(Table 4 is a general guide. Expect minor pressures
variations. Significant differences may mean improp-
er charge or other system problem.)
Use SUBCOOLING to correctly charge unit
or to verify the charge is correct.
USE WEIGH-IN METHOD
Weigh-in or remove refriger-
ant based upon line length
SUBCOOLING METHOD
Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
Connect gauge set
Measure outdoor ambient temperature
When heat demand is satisfied, set
thermostat to call for cooling
Allow temperatures and pressures to
stabilize [NOTE − IF NECESSARY, block
outdoor coil to maintain 325 − 375 psig]
Record line temp. LIQº =
Record liquid line pressure; use value to
determine saturation temperature
(table 5 on page 15) SATº =
Subtract to determine subcooling (SCº):
SATº − LIQº = SCº
Compare results with table
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060
65 (18) 10 (5.6) 10 (5.6) 10 (5.6) 11 (6.1) 10 (5.6) 8 (4.4) 8 (4.4)
75 (24) 6 (3.3) 8 (4.4) 8 (4.4) 11 (6.1) 7 (3.9) 8 (4.4) 7 (3.9)
85 (29) 6 (3.3) 8 (4.4) 7 (3.9) 11 (6.1) 7 (3.9) 8 (4.4) 8 (4.4)
95 (35) 6 (3.3) 8 (4.4) 7 (3.9) 10 (5.6) 7 (3.9) 8 (4.4) 7 (3.9)
105 (41) 6 (3.3) 8 (4.4) 7 (3.9) 10 (5.6) 7 (3.9) 8 (4.4) 7 (3.9)
115 (45) 6 (3.3) 8 (4.4) 6 (3.3) 9 (5.0) 7 (3.9) 7 (3.9) 6 (3.3)
*Temperature of air entering outdoor coil
SCº (Subcooling) Values (F:+/−1.0°; [C: +/−0.5°])
Above or
below 65ºF
(18ºC)?
If refrigerant added or
removed, verify
charge using the
approach method
BLOCK OUTDOOR COIL
[sometimes necessary with lower temperatures]
Use cardboard or plastic sheet to restrict the
airflow through the outdoor coil to achieve pres-
sures from 325−375 psig (2240−2585 kPa).
Higher pressures are needed to check charge.
Block equal sections of air intake panels and
move coverings sideways until the liquid pres-
sure is in the above noted ranges.
If value is greater than
shown, remove
refrigerant; if less than
shown, add refrigerant
FIGURE 16 Charging TXV units with Subcooling Method
Page 15
TABLE 4 Normal Operating Pressures
IMPORTANT
Use this table to perform maintenance checks; it is not a procedure for charging
the system. Minor variations in these pressures may be due to differences in
installations. Significant deviations could mean that the system is not properly
charged or that a problem exists with some component in the system.
Model −018 −024 −030 −036 −042 −048 −060
**
Temp.
*Liquid Line Pressure / Vapor Line Pressure
**Temp
.
5F (5C) Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
Expansion Valve (TXV)
65 (18) 222 / 140 233 / 138 230 / 136 240 / 137 236 / 138 238 / 136 239 / 133
70 (21) 241 / 141 250 / 138 247 / 137 259 / 138 253 / 140 256 / 138 258 / 135
75 (24) 259 / 143 271 / 140 265 / 139 278 / 139 273 / 141 277 / 139 278 / 136
80 (27) 279 / 144 291 / 141 287 / 140 299 / 139 296 / 142 299 / 140 300 / 137
85 (29) 301 / 145 313 / 143 308 / 141 321 / 140 318 / 143 320 / 139 323 / 138
90 (32) 319 / 145 335 / 143 331 / 142 344 / 141 341 / 144 343 / 140 346 / 139
95 (35) 346 / 146 361 / 145 355 / 144 368 / 142 366 / 146 369 / 141 370 / 140
100 (38) 370 / 147 384 / 146 380 / 145 393 / 143 392 / 147 395 / 142 396 / 142
105 (41) 396 / 148 412 / 147 405 / 146 419 / 144 417 / 148 422 / 144 415 / 143
110 (43) 422 / 150 436 / 148 432 / 147 446 / 145 445 / 149 450 / 146 449 / 145
115 (45) 451 / 151 468 / 149 461 / 148 477 / 146 475 / 151 481 / 148 476 / 147
Fixed Orifice (RFC)
65 (18) 223 / 123 230 / 121 231 / 123 234 / 130 248 / 135 240 / 126 244 / 125
70 (21) 239 / 127 251 / 128 249 / 127 247 / 134 266 / 138 260 / 129 263 / 128
75 (24) 253 / 131 272 / 133 270 / 132 270 / 136 285 / 141 281 / 133 281 / 131
80 (27) 278 / 136 289 / 135 291 / 136 290 / 138 305 / 143 301 / 135 303 / 134
85 (29) 299 / 139 312 / 140 314 / 140 313 / 141 327 / 145 324 / 138 324 / 136
90 (32) 320 / 142 335 / 142 337 / 142 336 / 143 349 / 147 346 / 140 347 / 139
95 (35) 343 / 145 361 / 144 359 / 144 358 / 145 372 / 149 371 / 142 370 / 141
100 (38) 367 / 147 383 / 147 383 / 146 361 / 148 396 / 150 395 / 144 394 / 143
105 (41) 392 / 149 409 / 149 408 / 147 409 / 150 421 / 152 420 / 146 418 / 145
110 (43) 417 / 152 441 / 151 433 / 149 430 / 151 447 / 153 447 / 148 444 / 146
115 (46) 445 / 154 467 / 152 467 / 151 463 / 152 476 / 154 473 / 150 471 / 147
*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary.
**Temperature of the air entering the outside coil.
TABLE 5 HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0 125 445.9 141 545.6
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
Page 16
D − Charging 018, 024 −2 units & 030 through 060 −3 units
TO SUCTION
SERVICE VALVE
TO LIQUID
LINE SERVICE
VALVE
TEMPERATURE
SENSOR
QC RESTRICTOR
FITTING
REFRIGERANT
TANK
TEMPERATURE SENSOR
(LIQUID LINE)
MANIFOLD
GAUGE SET
AClose manifold gauge set valves and connect the center hose to an upright cylinder of R−410A.
BConnect the manifold gauge set’s low pressure side to the suction line service port.
CConnect the manifold gauge set’s high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port.
OUTDOOR UNIT
CHARGING SYSTEM
A
B
C
D
FIGURE 17
1. Determine the desired DTMeasure entering air temperature
using dry bulb (A) and wet bulb (B). DTis the intersecting value of A
and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb
entering and leaving air temperatures (Aand C). Temperature Drop
Formula: (TDrop) = Aminus C.
3. Determine if fan needs adjustmentIf the difference between
the measured TDrop and the desired DT(TDrop–DT) is within +3º, no
adjustment is needed. See examples: Assume DT= 15 and Atemp.
= 72º, these C temperatures would necessitate stated actions:
Cº TDrop –DT=ºF ACTION
53º 19 – 15 =4Increase the airflow
58º 14 – 15 =−1 (within +3º range) no change
62º 10 – 15 =−5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to
increase/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3º.
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Temp.
of air
entering
indoor
coil ºF
INDOOR
COIL
DRY BULBDRY
BULB
WET
BULB
B
TDrop
19º
A
Dry−bulb
Wet−bulb ºF
A
72º
B
64º
C
53º
air flowair flow
All temperatures are
expressed in ºF
INDOOR COIL AIRFLOW CHECK
Check indoor coil airflow using the Delta−T (DT) process as illustrated.
FIGURE 18
Page 17
WHEN TO CHARGE?
Warm weather best
Can charge in colder weather
CHARGE METHOD? Determine by:
Metering device type
Outdoor ambient temperature
REQUIREMENTS:
Sufficient heat load in structure
Indoor temperature between 70-80ºF
(21−26ºC)
Manifold gauge set connected to unit
Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure suction line temperature
TXV FIXED
ORIFICE
APPROACH OR
SUBCOOLING
WEIGH-IN
SUPERHEAT
65ºF
(18.3ºC) and
Above
START: Determine how refrigerant is metered
39ºF
(3.8ºC) and
Below
Which indoor
metering
device?
WEIGH-IN
64ºF
(17.7ºC) and
Below
40ºF
(4.4ºC) and
Above
DETERMINING CHARGE METHOD
ABCDE
FIGURE 19
START: Measure outdoor ambient temperature 1.. Connect gauge set as illustrated in figure
17.
2.. Check Liquid and suction line pressures
3.. Compare unit pressures with table 6,
Normal Operating Pressures.
4.. Weigh in the unit nameplate charge plus
any charge required for line set
differences over feet.
Liquid Line
Set Diameter
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3/8" (9.5 mm) 3 ounce per 5’ (85 g per 1.5 m)
NOTE − *If line length is greater than 15
ft. (4.6 m), add this amount. If line length
is less than 15 ft. (4.6 m), subtract this
amount.
Refrigerant
Charge per Line
Set Length
USE EITHER APPROACH
OR SUBCOOLING
METHOD
This nameplate is for illustration
purposes only. Go to actual
nameplate on outdoor unit for
charge information.
64ºF and
BELOW
65ºF
and
ABOVE
ABOVE or BE-
LOW
FIGURE 20
A
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
WEIGH IN TXV
Page 18
DO NOT CHARGE UNIT
(Results of charging at low
temperatures not reliable)
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant
based upon line length
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])
1.. Connect gauge set as illustrated in figure 17.
2.. Confirm proper airflow across coil using figure 18.
3.. Compare unit pressures with table 6, Normal
Operating Pressures.
4.. Set thermostat to call for heat (must have a cooling
load between 70-80ºF (21−26ºC).
5.. When heat demand is satisfied, set thermostat to call
for cooling.
6.. Allow temperatures and pressures to stabilize.
7.. Record outdoor ambient temperature:
AMBº =_________
8.. Record liquid line temperature:
LIQº = __________
9.. Subtract to determine approach (APPº):
LIQº_____ − AMBº _____ = APPº_____
10.. Compare results with table below.
FIGURE 21
64ºF and
BELOW
65ºF
and
ABOVE
ABOVE or BE-
LOW
If value is MORE
than shown, remove
refrigerant.
If value is LESS
than shown, add
refrigerant.
If refrigerant is added
or removed, verify
charge using the
Subcooling Method.
MORE or
LESS
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060
65 (18) 4 (2.2) 2 (1.1) 2 (1.1) 2 (1.1 6 (3.3) 7 (3.9) 8 (4.4)
75 (24) 5 (2.8) 4 (2.2) 4 (2.2) 5 (2.8) 8 (4.4) 8 (4.4) 9 (5.0)
85 (29) 6 (3.3) 4 (2.2) 6 (3.3) 8 (4.4) 8 (4.4) 8 (4.4) 9 (5.0)
95 (35) 5 (2.8) 4 (2.2) 5 (2.8) 7 (3.9) 8 (4.4) 8 (4.4) 9 (5.0)
105 (41) 3 (1.7) 4 (2.2) 5 (2.8) 6 (3.3) 8 (4.4) 8 (4.4) 9 (5.0)
115 (45) 3 (1.7) 3 (1.7) 4 (2.2) 6 (3.3) 8 (4.4) 9 (5.0) 9 (5.0)
*Temperature of air entering outdoor coil
B
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
APPROACH TXV
DO NOT CHARGE UNIT
(Results of charging at low
temperatures not reliable)
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant
based upon line length
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])
BLOCK OUTDOOR COIL: [sometimes necessary with lower
temperatures] Use cardboard or plastic sheet to restrict the airflow
through the outdoor coil to achieve pressures from 325−375 psig
(2240−2585 kPa). Higher pressures are needed to check charge.
Block equal sections of air intake panels and move coverings
sideways until the liquid pressure is in the above noted ranges.
If value is MORE
than shown, remove
refrigerant.
1.. Connect gauge set as illustrated in figure 17.
2.. Confirm proper airflow across coil using figure 18.
3.. Compare unit pressures with table 6, Normal
Operating Pressures.
4.. Set thermostat to call for heat (must have a cooling
load between 70-80ºF (21−26ºC)
5.. Measure outdoor ambient temperature
6.. When heat demand is satisfied, set thermostat to
call for cooling
7.. Allow temperatures and pressures to stabilize.
NOTE − If necessary, block outdoor coil to maintain
325 − 375 psig.
8.. Record liquid line temperature:
LIQº = ______
9.. Measure liquid line pressure and use the value to
determine saturation temperature (see table 5):
SATº = ______
10.. Subtract to determine subcooling (SCº):
SATº_____ − LIQº _____ = SCº _____
11.. Compare results with table below.
FIGURE 22
MORE or
LESS
If refrigerant is added or
removed, verify charge
using the Approach
Method.
64ºF and
BELOW
65ºF
and
ABOVE
ABOVE or BE-
LOW
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060
65 (18) 10 (5.6) 10 (5.6) 11 (6.1) 13 (7.2) 10 (5.6) 8 (4.4) 8 (4.4)
75 (24) 6 (3.3) 7 (3.9) 8 (4.4) 9 (5.0) 7 (3.9) 8 (4.4) 7 (3.9)
85 (29) 6 (3.3) 8 (4.4) 6 (3.3) 7 (3.9) 7 (3.9) 8 (4.4) 8 (4.4)
95 (35) 6 (3.3) 9 (5.0) 6 (3.3) 8 (4.4) 7 (3.9) 8 (4.4) 7 (3.9)
105 (41) 10 (5.6) 9 (5.0) 7 (3.9) 9 (5.0) 7 (3.9) 8 (4.4) 6 (3.3)
115 (45) 10 (5.6) 10 (5.6) 8 (4.4) 10 (5.6) 7 (3.9) 7 (3.9) 6 (3.3)
*Temperature of air entering outdoor coil
C
If value is LESS
than shown, add
refrigerant.
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
CARDBOARD OR
PLASTIC SHEETS
SUBCOOLING TXV
Page 19
START: Measure outdoor ambient temperature 1.. Connect gauge set as illustrated in figure
17.
2.. Check Liquid and suction line pressures
3.. Compare unit pressures with table 6,
Normal Operating Pressures.
4.. Weigh in the unit nameplate charge plus
any charge required for line set
differences over feet.
Liquid Line
Set Diameter
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3/8" (9.5 mm) 3 ounce per 5’ (85 g per 1.5 m)
NOTE − *If line length is greater than
15 ft. (4.6 m), add this amount. If line
length is less than 15 ft. (4.6 m),
subtract this amount.
Refrigerant Charge per Line Set Length
USE SUPERHEAT
This nameplate is for
illustration purposes only.
Go to actual nameplate on
outdoor unit for charge
information.
ABOVE or BE-
LOW
39ºF and
BELOW
40ºF
and
ABOVE
D
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
WEIGH IN FIXED ORIFICE
FIGURE 23
START: Measure outdoor ambient temperature
NOTE − Do not attempt to charge system where a
dash appears, system could be overcharged.
Superheat is taken at suction line service port.
Suction line superheat must never be less than 5ºF
at the suction line service port.
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant
based upon line length
SHº (Superheat) Values (+/−5ºF)
Wet Bulb (air entering indoor coil)
ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76
40 15 18 20 23 26 29 32 34 38 41 43 46 48 51
45 13 16 18 21 24 27 30 33 36 39 41 44 46 49
50 11 14 16 19 22 25 28 31 34 37 39 42 44 47
55 9 12141720232730333638404244
60 7 10121518212427303335384043
65 - 6 10 13 16 19 21 24 27 30 33 36 38 41
70 - - 7 1013161921242730333639
75 - - - 6 9 121518212428313437
80 - - - - 5 8 12 15 18 21 25 28 31 35
85 - - - - - - 8 11151922263033
90 - - - - - - 5 9 13 16 20 24 27 31
95 - - - - - - - 6 10 14 18 22 25 29
100 --------81216212428
105 - - - - - - - - 5 9 13 17 22 26
110 ---------611152025
115 ----------8141824
* Dry−bulb temperature (ºF) of entering outdoor ambient air.
1.. Connect gauge set as illustrated in figure 17.
2.. Confirm proper airflow across coil using figure
18.
3.. Compare unit pressures with table 6, Normal
Operating Pressures.
4.. Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
5.. When heat demand is satisfied, set thermostat to
call for cooling.
6.. Allow temperatures and pressures to stabilize.
7.. Measure the suction line pressure and use the
use value to determine saturation temperature
(table 5):
SATº =_________
8.. Record suction line temperature:
VAPº =_________
9.. Subtract to determine superheat (SHº):
VAPº − _____ SATº ______ = SHº______
10.. Record the wet bulb temperature (air entering
indoor coil):
WB =_______
11.. Record outdoor ambient temperature.
12.. Compare results with table to the left.
If value is MORE
than shown, remove
refrigerant.
If value is LESS
than shown, add
refrigerant.
If refrigerant is
added, retest to
confirm that unit is
properly charged.
MORE or
LESS
If refrigerant is
removed, retest to
confirm that unit is
properly charged.
ABOVE or BE-
LOW
39ºF and
BELOW
40ºF
and
ABOVE
E
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
Once refrigerant
charge is correct,
disconnect gauge
set and replace
service port caps.
SUPERHEAT FIXED ORIFICE
FIGURE 24
Page 20
TABLE 6
Normal Operating Pressures (Liquid +10 and Suction +5 psig)
IMPORTANT
Use this table to perform maintenance checks; it is not a procedure for charging
the system. Minor variations in these pressures may be due to differences in
installations. Significant deviations could mean that the system is not properly
charged or that a problem exists with some component in the system.
Model −018 −024 −030 −036 −042 −048 −060
**Temp.
5F (5C) Liquid / Vapor Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Vapor Liquid / Vapor Liquid / Vapor
Expansion Valve (TXV)
65 (18) 230 / 138 225 / 135 226 / 129 238 / 132 236 / 138 238 / 136 239 / 133
70 (21) 244 / 139 242 / 137 241 / 131 254 / 135 253 / 140 256 / 138 258 / 135
75 (24) 265 / 140 260 / 138 259 / 134 273 / 138 273 / 141 277 / 139 278 / 136
80 (27) 286 / 140 282 / 140 281 / 138 293 / 140 296 / 142 299 / 140 300 / 137
85 (29) 307 / 142 304 / 141 301 / 140 316 / 142 318 / 143 320 / 139 323 / 138
90 (32) 330 / 143 326 / 142 324 / 141 340 / 143 341 / 144 343 / 140 346 / 139
95 (35) 351 / 144 351 / 142 348 / 142 366 / 144 366 / 146 369 / 141 370 / 140
100 (38) 380 / 144 376 / 144 372 / 143 392 / 145 392 / 147 395 / 142 396 / 142
105 (41) 407 / 145 403 / 145 399 / 144 420 / 147 417 / 148 422 / 144 415 / 143
110 (43) 436 / 146 433 / 145 428 / 145 449 / 148 445 / 149 450 / 146 449 / 145
115 (45) 466 / 147 463 / 147 456 / 146 480 / 149 475 / 151 481 / 148 476 / 147
Fixed Orifice (RFC)
65 (18) 232 / 124 228 / 125 229 / 128 241 / 131 248 / 135 240 / 126 244 / 125
70 (21) 248 / 127 244 / 127 243 / 129 258 / 134 266 / 138 260 / 129 263 / 128
75 (24) 267 / 131 261 / 131 261 / 132 277 / 136 285 / 141 281 / 133 281 / 131
80 (27) 286 / 135 284 / 134 284 / 135 298 / 139 305 / 143 301 / 135 303 / 134
85 (29) 307 / 138 303 / 137 305 / 138 321 / 141 327 / 145 324 / 138 324 / 136
90 (32) 328 / 141 325 / 140 327 / 140 342 / 143 349 / 147 346 / 140 347 / 139
95 (35) 351 / 143 347 / 142 349 / 142 366 / 145 372 / 149 371 / 142 370 / 141
100 (38) 375 / 146 370 / 144 372 / 144 392 / 147 396 / 150 395 / 144 394 / 143
105 (41) 400 / 148 394 / 146 396 / 146 416 / 149 421 / 152 420 / 146 418 / 145
110 (43) 426 / 150 420 / 148 422 / 148 446 / 151 447 / 153 447 / 148 444 / 146
115 (46) 457 / 153 447 / 150 449 / 150 480 / 152 476 / 154 473 / 150 471 / 147
*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary.
**Temperature of the air entering the outside coil.
TABLE 7
HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0 125 445.9 141 545.6
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0

Other manuals for XC14

3

This manual suits for next models

7

Other Lennox Heat Pump manuals

Lennox LHT156 User manual

Lennox

Lennox LHT156 User manual

Lennox 14HPX Installation and operation manual

Lennox

Lennox 14HPX Installation and operation manual

Lennox INNOV DM R Series User guide

Lennox

Lennox INNOV DM R Series User guide

Lennox 4HP18LT User manual

Lennox

Lennox 4HP18LT User manual

Lennox Merit 14ACX-018-230 User manual

Lennox

Lennox Merit 14ACX-018-230 User manual

Lennox XP14 User manual

Lennox

Lennox XP14 User manual

Lennox Elite XP13024 User manual

Lennox

Lennox Elite XP13024 User manual

Lennox ASC Series User manual

Lennox

Lennox ASC Series User manual

Lennox KHA180 User manual

Lennox

Lennox KHA180 User manual

Lennox KGB Series Installation and operation manual

Lennox

Lennox KGB Series Installation and operation manual

Lennox Allied Air Enterprises BHP16L User manual

Lennox

Lennox Allied Air Enterprises BHP16L User manual

Lennox XP14 User manual

Lennox

Lennox XP14 User manual

Lennox HPXA12 SERIES Planning guide

Lennox

Lennox HPXA12 SERIES Planning guide

Lennox HS20-211 Setup guide

Lennox

Lennox HS20-211 Setup guide

Lennox Elite 13 User manual

Lennox

Lennox Elite 13 User manual

Lennox R22 User guide

Lennox

Lennox R22 User guide

Lennox Magic-Pak PWC182 User manual

Lennox

Lennox Magic-Pak PWC182 User manual

Lennox Signature XP19-024 User manual

Lennox

Lennox Signature XP19-024 User manual

Lennox Elite Series HP13 User manual

Lennox

Lennox Elite Series HP13 User manual

Lennox LHT180 User manual

Lennox

Lennox LHT180 User manual

Lennox XP15 User manual

Lennox

Lennox XP15 User manual

Lennox 13HPX Installation and operation manual

Lennox

Lennox 13HPX Installation and operation manual

Lennox HP29-090 User manual

Lennox

Lennox HP29-090 User manual

Lennox HPXA16 series User manual

Lennox

Lennox HPXA16 series User manual

Popular Heat Pump manuals by other brands

AQUARK BLACK SILENCE user manual

AQUARK

AQUARK BLACK SILENCE user manual

Carrier 50ZH Series Guide to operating and maintaining

Carrier

Carrier 50ZH Series Guide to operating and maintaining

M&C CSS Series instruction manual

M&C

M&C CSS Series instruction manual

EAS Electric E301WHF instruction manual

EAS Electric

EAS Electric E301WHF instruction manual

American Water Heater HPE6280H045DV Specification sheet

American Water Heater

American Water Heater HPE6280H045DV Specification sheet

Qlima SPHP 130 operating manual

Qlima

Qlima SPHP 130 operating manual

Atlantic alfea extensa + Installation and operating manual

Atlantic

Atlantic alfea extensa + Installation and operating manual

Carrier 38AB Installation, Start-Up and Service Instructions

Carrier

Carrier 38AB Installation, Start-Up and Service Instructions

Macon MWCRW045Z Installation instructions manual

Macon

Macon MWCRW045Z Installation instructions manual

Bosch Climate 6100i Operation manual

Bosch

Bosch Climate 6100i Operation manual

Bryant 569J 08G Series Installation, Start-Up and Service Instructions

Bryant

Bryant 569J 08G Series Installation, Start-Up and Service Instructions

CTC Union EcoAir 500M Installation and maintenance manual

CTC Union

CTC Union EcoAir 500M Installation and maintenance manual

Valeo REVO-E Workshop manual

Valeo

Valeo REVO-E Workshop manual

Carrier 48VR Owner's information manual

Carrier

Carrier 48VR Owner's information manual

Maritime Geothermal ATF Series Installation and service manual

Maritime Geothermal

Maritime Geothermal ATF Series Installation and service manual

Salda SIG 6-17 Installation and maintenance manual

Salda

Salda SIG 6-17 Installation and maintenance manual

Nordic PASRW150S-BP-PS-D Installation and instruction manual

Nordic

Nordic PASRW150S-BP-PS-D Installation and instruction manual

Viessmann VITOCAL 222-G Installation and service instructions

Viessmann

Viessmann VITOCAL 222-G Installation and service instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.