
18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS® DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
Figure 32 - Typical Horizontal Vent Installation
Vertical
Rise
SV4.5E90
Elbow
Horizontal / Inclined Run SV4.5HT-2
Termination
Firestop/Spacer
SV4.5L6/12/24/36/48
Vent Sections
Support bracket spacing
every 5 ft (1.52 m)
See Figure 24 on Page 15 for
vertical vent section support.
SV4.5HT-2
Termination
Support
Brackets
Building
Support
Framing
Ceiling
Fireplace
Exterior
Wall
Exterior
Wall
TYPICAL HORIZONTAL VENT INSTALLATION
HORIZONTAL(OUTSIDEWALL)TERMINATION
SYSTEM
Figure 32, and Figures 35 to 41 on Pages
21 to 23 and their associated Horizontal
Vent Table illustrate the various horizontal
venting configurations that are possible for
use with these appliances. Secure Vent®pipe
applicationsare shownin these figures;Secure
Flex®pipe may also be used. A Horizontal Vent
Tablesummarizeseachsystem’sminimumand
maximum vertical and horizontal length values
that can be used to design and install the vent
componentsin avariety ofapplications. Bothof
thesehorizontalventsystemsterminatethrough
an outside wall. Building Codes limit or prohibit
terminating in specific areas. Refer to Figure 7
on Page 7 for location guidelines.
Secure Vent SV4.5 direct vent system compon-
ents are unitized concentric pipe components
featuring positive twist lock connection, (refer
to Figure 21 on Page 15). All of the appliances
covered in this document are fitted with collars
having locking inclined channels. The dimpled
end ofthe vent componentsfit over theappliance
collarto createthe positivetwist lockconnection.
A. Plan the vent run - Analyze the vent routing
and determinethe typesandquantities ofsections
required 4-1/2" (114 mm), 10-1/2" (267 mm),
22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2".
(1181 mm) net section lengths are available. It is
recommended that you plan the venting so that a
jointdoesnotoccurintheceilingorroofjoists.Allow
for elbows as indicated in Figure 23 on Page 16.
Maintain a minimum 1" (25 mm) clearance to
combustiblesontheverticalsections.Clearances
for the horizontal runs are; 3" (76 mm) on top, 1"
(25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening - Locate the
center of the vent outlet on the exterior wall
according to the dimensions shown in Figure
12 on Page 11. Cut and/or frame an opening,
10-1/2" x 12-1/8" (267 mm x 308 mm) inside
dimensions, about this center.
C. Frame ceiling opening - If the vertical route
isto penetratea ceiling,use plumbline tolocate
thecenterabovetheappliance.Cutand/orframe
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm)insidedimensions,aboutthiscenter(refer
to Figure 20 on Page 15).
D. Attach vent components to appliance - To
attach a vent component to the appliance collar,
alignthedimpledendoverthecollar,adjustingthe
radialalignmentuntilthe fourlockingdimplesare
aligned with the inlets of the four incline channels
on the collar (refer to Figure 21 on Page 15).
Push the vent component against the collar
until it fully engages, then twist the component
clockwise, running the dimples down and along
the incline channels until they seat at the end of
the channels. The unitized design of the Secure
Vent components will engage and seal both the
inner and outer pipe elements with the same
procedure. Sealant and securing screws are
not required.
NOTE: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
E. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vent tables. To add
another vent component to a length of vent run,
align the dimpled end of thecomponent over the
inclined channel end of the previously installed
section, adjusting the radial alignment until the
fourlockingdimplesarealignedwiththeinletsof
thefourincline channelsoftheprevioussection.
Push the vent component against the previous
section until it fully engages, then twist the
componentclockwiserunningthedimplesdown
and along the incline channels until they seat at
the end of the channels.This seating position
is indicated by the alignment of the arrow and
dimple as shown in Figure 21 on Page 15.
F. Install firestop/spacer at ceiling - When
usingSecureVent,useSV4.5VFfirestop/spacer
at ceiling joists; when using Secure Flex®, use
SF4.5VF firestop/spacer. If there is living space
abovetheceilinglevel,thefirestop/spacermust
be installed on the bottom side of the ceiling.
If attic space is above the ceiling, the firestop/
spacer must be installed on the top side of
the joist. Route the vent sections through the
framed opening and secure the firestop/spacer
with 8d nails or other appropriate fasteners at
each corner.
Remember to maintain 1" (25 mm) clearance
to combustibles, framing members, and attic
or ceiling insulation when running vertical
chimney sections.
G. Support the vertical run sections - On the
vertical run, support the venting system every
8 feet (2.4m) above the fireplace vent outlet
with field provided support straps (Plumber's
tape). Attach the straps to the vent pipe and
secure to the framing members with nails or
screws. See Figure 22 on Page 15.
H.Changeventdirection- At transitionfromor
toahorizontal/inclinedrun,installtheSV4.5E45
and SV4.5E90 elbows in the same manner as
thestraight ventsections. The elbowsfeature a
twist section to allow them to be routed about
the center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the
possiblity of unlocking any of the previously
connected vent sections. See Figure 23 on
Page 16.
I.Continue installationofhorizontal/inclined
sections - Continue with the installation of the
straightventsectionsin horizontal/inclinedrun
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber’s tape.
See Figure 32,It is very important that the
horizontal/inclined run be maintained in a
straight (no dips), slightly elevated plane.
The recommended incline is approximately
1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The
rise per foot run ratios that are smaller are
acceptable all the way down to at or near level.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
It is important to maintain the required
clearances to combustibles: 1" (25 mm) at all
sides for all vertical runs; and 3" (76 mm) at
the top, 1" (25 mm) at sides, and 1" (25 mm)
at the bottom for all horizontal/inclined runs.