Lenze AC Tech SCF Series User manual

-~
ARTISAN
®
~I
TECHNOLOGY
GROUP
Your definitive source
for
quality
pre-owned
equipment.
Artisan Technology
Group
Full-service,
independent
repair
center
with
experienced
engineers
and
technicians
on staff.
We
buy
your
excess,
underutilized,
and
idle
equipment
along
with
credit
for
buybacks
and
trade-ins
.
Custom
engineering
so
your
equipment
works
exactly as
you
specify.
•
Critical
and
expedited
services
•
Leasing
/
Rentals/
Demos
• In
stock/
Ready-to-ship
•
!TAR-certified
secure
asset
solutions
Expert
team
ITrust
guarantee
I
100%
satisfaction
All
tr
ademarks,
br
a
nd
names, a
nd
br
a
nd
s a
pp
earing here
in
are
th
e property of
th
e
ir
r
es
pecti
ve
ow
ner
s.
Find the Lenze / AC Tech SF2200 at our website: Click HERE

SCF Series
Installation and Operation Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

THE SCF SUB-MICRO DRIVE
PROGRAMMING
BUTTONS
ELECTRONIC
PROGRAMMING
MODULE (EPM)
INPUT POWER
TERMINALS
3-DIGIT LED
DISPLAY
CONTROL
TERMINAL
STRIP
DC BUS
TERMINALS
OUTPUT (MOTOR)
TERMINALS
Safety Information
All safety information given in these Operating Instruction have the same layout:
Signal Word! (characterizes the severity of the danger)
Note (describes the danger and informs on how to proceed)
Icon Signal Words
Warning of
hazardous
electrical
voltage
DANGER! Warns of impending danger.
Consequences if disregarded:
Death or severe injuries.
Warning of
a general
danger
WARNING! Warns of potential, very hazardous situations.
Consequences if disregarded:
Death or severe injuries.
Warning of
damage to
equipment
STOP! Warns of potential damage to material and
equipment.
Consequences if disregarded:
Damage to the controller/drive or its environment.
Information Note Designates a general, useful note.
If you observe it, handling the controller/drive
system is made easier.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 1
Table of Contents
1.0 GENERAL ........................................................................................2
2.0 SCF DIMENSIONS ..........................................................................4
3.0 SCF MODEL DESIGNATION CODE ...............................................7
4.0 SCF SPECIFICATIONS ...................................................................8
5.0 SCF RATINGS .................................................................................9
6.0 INSTALLATION ..............................................................................11
7.0 INPUT AC POWER REQUIREMENTS ..........................................12
8.0 POWER WIRING ...........................................................................15
9.0 SCF POWER WIRING DIAGRAM .................................................16
10.0 CONTROL WIRING .......................................................................17
11.0 SCF CONTROL WIRING DIAGRAMS ...........................................20
12.0 INITIAL POWER UP AND MOTOR ROTATION ............................25
13.0 PROGRAMMING THE SCF DRIVE ...............................................26
14.0 PARAMETER MENU .....................................................................30
15.0 DESCRIPTION OF PARAMETERS ...............................................33
16.0 TROUBLESHOOTING ...................................................................48
17.0 SCF DISPLAY MESSAGES ...........................................................50
APPENDIX A - THROUGH-HOLE MOUNT OPTION ....................52
APPENDIX B - PI SETPOINT CONTROL OPTION .......................56
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

2 SF01U
1.0 GENERAL
1.1 PRODUCTS COVERED IN THIS MANUAL
This manual covers the Lenze AC Tech SCF Series Variable Frequency Drive.
1.2 PRODUCT CHANGES
Lenze AC Tech Corporation reserves the right to discontinue or make modifications to the
design of its products without prior notice, and holds no obligation to make modifications to
products sold previously. Lenze AC Tech Corporation also holds no liability for losses of any
kind which may result from this action. Instruction manuals with the most up-to-date information
are available for download from the Lenze AC Tech website (www.lenze-actech.com).
1.3 WARRANTY
Lenze AC Tech Corporation warrants the SCF Series AC motor control to be free of defects
in material and workmanship for a period 24 months from date of shipment from Lenze AC
Tech's factory. If an SCF motor control, under normal use, becomes defective within the
stated warranty time period, contact Lenze AC Tech's Service Department for instructions on
obtaining a warranty replacement unit. Lenze AC Tech Corporation reserves the right to make
the final determination as to the validity of a warranty claim, and sole obligation is to repair
or replace only components which have been rendered defective due to faulty material or
workmanship. No warranty claim will be accepted for components which have been damaged
due to mishandling, improper installation, unauthorized repair and/or alteration of the product,
operation in excess of design specifications or other misuse, or improper maintenance.
Lenze AC Tech Corporation makes no warranty that its products are compatible with any
other equipment, or to any specific application, to which they may be applied and shall not be
held liable for any other consequential damage or injury arising from the use of its products.
This warranty is in lieu of all other warranties, expressed or implied. No other person,
firm or corporation is authorized to assume, for Lenze AC Tech Corporation, any other
liability in connection with the demonstration or sale of its products.
1.4 RECEIVING
Inspect all cartons for damage which may have occurred during shipping. Carefully unpack
equipment and inspect thoroughly for damage or shortage. Report any damage to carrier and/or
shortages to supplier. All major components and connections should be examined for damage
and tightness, with special attention given to PC boards, plugs, knobs and switches.
1.5 SAFETY INFORMATION
GENERAL
Some parts of Lenze AC Tech controllers can be electrically live and some surfaces can be hot.
Non-authorized removal of the required cover, inappropriate use, and incorrect installation or
operation creates the risk of severe injury to personnel or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance
must be carried out by qualified, skilled personnel who are familiar with the installation,
assembly, commissioning, and operation of variable frequency drives and the application for
which it is being used.
INSTALLATION
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components
and do not change any insulation distances during transport, handling, installation or
maintenance.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 3
Do not touch any electronic components or contacts. This drive contains electrostatically
sensitive components, which can easily be damaged by inappropriate handling. Static control
precautions must be adhered to during installation, testing, servicing and repairing of this
drive and associated options. Component damage may result if proper procedures are not
followed.
This drive has been tested by Underwriters Laboratory (UL) and is an approved component
in compliance with UL508 Safety Standard.
Warnings!
• Suitable for use on a circuit as described in Section 7.0 of this manual.
• Use minimum 75 °C copper wire only.
• Shall be installed in a pollution degree 2 macro-environment.
This drive must be installed and configured in accordance with both national and international
standards. Local codes and regulations take precedence over recommendations provided in
this and other Lenze AC Tech documentation.
The SCF drive is considered a component for integration into a machine or process. It is neither
a machine nor a device ready for use in accordance with European directives (reference
machinery directive and electromagnetic compatibility directive). It is the responsibility of the
end user to ensure that the machine meets the applicable standards.
ELECTRICAL CONNECTION
When working on live drive controllers, applicable national safety regulations must be
observed.
The electrical installation must be carried out according to the appropriate regulations (e.g.
cable cross-sections, fuses, protective earth [PE] connection). While this document does make
recommendations in regards to these items, national and local codes must be adhered to.
The documentation contains information about installation in compliance with EMC (shielding,
grounding, filters and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required
limit values demanded by EMC legislation.
APPLICATION
The drive must not be used as a safety device for machines where there is a risk of personal injury
or material damage. Emergency Stops, over-speed protection, acceleration and deceleration
limits, etc must be made by other devices to ensure operation under all conditions.
The drive does feature many protection devices which are aimed at protecting the drive
and the driven equipment by generating a fault and shutting the drive and motor down by
removing power. Mains power variances can also result in shutdown of the drive. When the
fault condition disappears or is cleared, the drive can be configured to automatically restart,
it is the responsibility of the user and/or OEM and/or integrator to ensure that the drive is
configured for safe operation.
1.6 CUSTOMER MODIFICATION
Lenze AC Tech Corporation, its sales representatives and distributors, welcome the opportunity
to assist our customers in applying our products. Many customizing options are available to aid
in this function. Lenze AC Tech Corporation cannot assume responsibility for any modifications
not authorized by its engineering department
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

4 SF01U
2.0 SCF DIMENSIONS
HP kW INPUT
VOLTAGE MODEL H W D P R
0.25 0.18 208 / 240 SF203Y 5.75 (146) 2.88 (73) 3.94 (100) 0.80 (20) 4.37 (111)
0.5 0.37 208 / 240 SF205Y 5.75 (146) 2.88 (73) 3.94 (100) 0.80 (20) 4.37 (111)
400 / 480 SF405 5.75 (146) 2.88 (73) 3.94 (100) 0.80 (20) 4.37 (111)
1 0.75
208 / 240 SF210Y 5.75 (146) 2.88 (73) 4.74 (120) 1.60 (41) 4.37 (111)
208 / 240 SF210 5.75 (146) 2.88 (73) 4.74 (120) 1.60 (41) 4.37 (111)
400 / 480 SF410 5.75 (146) 2.88 (73) 4.74 (120) 1.60 (41) 4.37 (111)
480 / 590 SF510 5.75 (146) 2.88 (73) 4.74 (120) 1.60 (41) 4.37 (111)
1.5 1.1
208 / 240 SF215Y 5.75 (146) 3.76 (96) 5.24 (133) 1.90 (48) 4.37 (111)
208 / 240 SF215 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 4.37 (111)
400 / 480 SF415 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 4.37 (111)
2 1.5
208 / 240 SF220Y 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 4.37 (111)
208 / 240 SF220 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 3.06 (78)
400 / 480 SF420 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 4.37 (111)
480 / 590 SF520 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 4.37 (111)
Mounting Tab Detail
If R < 6.30" (160)
S = 0.19" (5)
T = 0.38" (10)
U = 0.18" (5)
V = 0.66" (17)
If R = 6.30" (160)
S = 0.28" (7)
T = 0.50" (13)
U = 0.24" (6)
V = 0.90" (23)
D
H
W
R
P
T
U
V
S
Dia. Slot
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 5
HP kW INPUT
VOLTAGE MODEL H W D P R
3 2.2
208 / 240 SF230Y 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 3.25 (83)
208 / 240 SF230 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 3.06 (78)
400 / 480 SF430 5.75 (146) 2.88 (73) 5.74 (146) 2.60 (66) 3.06 (78)
480 / 590 SF530 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 4.37 (111)
5 3.7
208 / 240 SF250Y 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
208 / 240 SF250 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 3.25 (83)
400 / 480 SF450 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 3.25 (83)
480 / 590 SF550 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 3.25 (83)
7.5 5.5
208 / 240 SF275 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
400 / 480 SF475 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
480 / 590 SF575 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
10 7.5
208 / 240 SF2100 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
400 / 480 SF4100 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
480 / 590 SF5100 7.75 (197) 5.02 (128) 7.18 (182) 3.40 (86) 4.81 (122)
15 11
208 / 240 SF2150 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
400 / 480 SF4150 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
480 / 590 SF5150 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
20 15
208 / 240 SF2200 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
400 / 480 SF4200 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
480 / 590 SF5200 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
25 18.5 400 / 480 SF4250 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
480 / 590 SF5250 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
30 22 400 / 480 SF4300 9.75 (248) 6.68 (170) 8.00 (203) 3.60 (91) 6.30 (160)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

6 SF01U
2.1 SCF THROUGH-HOLE MOUNT DIMENSIONS
D
H
W
P
HP kW INPUT
VOLTAGE MODEL H W D P
1 0.75
208 / 240 SF210YF 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
208 / 240 SF210F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
400 / 480 SF410F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
480 / 590 SF510F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
1.5 1.1
208 / 240 SF215YF 7.72 (196) 6.80 (173) 4.75 (121) 1.20 (30)
208 / 240 SF215F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
400 / 480 SF415F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
2 1.5
208 / 240 SF220YF 7.72 (196) 6.80 (173) 4.75 (121) 1.20 (30)
208 / 240 SF220F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
400 / 480 SF420F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
480 / 590 SF520F 7.72 (196) 6.80 (173) 4.55 (116) 1.20 (30)
3 2.2
208 / 240 SF230YF 7.72 (196) 8.54 (217) 5.30 (135) 1.75 (44)
208 / 240 SF230F 7.72 (196) 8.54 (217) 5.10 (130) 1.75 (44)
400 / 480 SF430F 7.72 (196) 8.54 (217) 5.10 (130) 1.75 (44)
480 / 590 SF530F 7.72 (196) 8.54 (217) 5.30 (135) 1.75 (44)
5 3.7
208 / 240 SF250YF 9.59 (244) 11.14 (283) 7.65 (194) 3.60 (91)
208 / 240 SF250F 7.72 (196) 8.54 (217) 6.30 (160) 2.75 (70)
400 / 480 SF450F 7.72 (196) 8.54 (217) 6.30 (160) 2.75 (70)
480 / 590 SF550F 7.72 (196) 8.54 (217) 6.30 (160) 2.75 (70)
7.5 5.5
208 / 240 SF275F 11.59 (294) 11.14 (283) 7.65 (194) 3.60 (91)
400 / 480 SF475F 9.59 (244) 11.14 (283) 7.65 (194) 3.60 (91)
480 / 590 SF575F 9.59 (244) 11.14 (283) 7.65 (194) 3.60 (91)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 7
NOTE: Refer to Appendix A for mounting template dimensions for the Through-hole Mount option.
HP kW INPUT
VOLTAGE MODEL H W D P
10 7.5
208 / 240 SF2100F 15.59 (396) 11.14 (283) 7.65 (194) 3.60 (91)
400 / 480 SF4100F 11.59 (294) 11.14 (283) 7.65 (194) 3.60 (91)
480 / 590 SF5100F 11.59 (294) 11.14 (283) 7.65 (194) 3.60 (91)
15 11
208 / 240 SF2150F 18.09 (459) 11.14 (283) 8.29 (211) 3.60 (91)
400 / 480 SF4150F 15.59 (396) 11.14 (283) 8.29 (211) 3.60 (91)
480 / 590 SF5150F 15.59 (396) 11.14 (283) 8.29 (211) 3.60 (91)
20 15 400 / 480 SF4200F 18.09 (459) 11.14 (283) 8.29 (211) 3.60 (91)
480 / 590 SF5200F 18.09 (459) 11.14 (283) 8.29 (211) 3.60 (91)
25 18.5 400 / 480 SF4250F 28.50 (724) 10.34 (263) 8.39 (213) 3.70 (94)
480 / 590 SF5250F 28.50 (724) 10.34 (263) 8.39 (213) 3.70 (94)
3.0 SCF MODEL DESIGNATION CODE
The SCF model number gives a full description of the basic drive unit (see example below).
EXAMPLE: SF210Y (SCF Series, 208/240 Vac, 1 HP, single or three phase input)
SF 2 10 Y
Series:
SF = SCF Series Variable Speed AC Motor Drive
Input Voltage:
2 = 208/240 Vac (For 208, 230, and 240 Vac; 50 or 60 Hz)
4 = 400/480 Vac (For 380, 415, 440, 460 and 480 Vac; 50 or 60 Hz)
5 = 480/590 Vac (For 440, 460, 480, 575 and 600 Vac; 50 or 60 Hz)
Rating:
03 = ¼ HP (0.20 kW) 30 = 3 HP (2.2 kW) 200 = 20 HP (15 kW)
05 = ½ HP (0.37 kW) 50 = 5 HP (4.0 kW) 250 = 25 HP (18.5 kW)
10 = 1 HP (0.75 kW) 75 = 7½ HP (5.5 kW) 300 = 30 HP (22 kW)
15 = 1½ HP (1.1 kW) 100 = 10 HP (7.5 kW)
20 = 2 HP (1.5 kW) 150 = 15 HP (11 kW)
Input Phase:
Y = Single or three phase input.
No character indicates three phase input only
Mounting Style:
F = Through-hole mount with special heatsink
F1 = Through-hole mount without heatsink (customer supplies heatsink)
No character indicates panel or DIN rail mounting
Application Specific Options:
P = PI (setpoint control) software
V = High Frequency Output - up to 1000 Hz
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

8 SF01U
4.0 SCF SPECIFICATIONS
Storage Temperature -20° to 70° C
Ambient Operating Temperature 0° to 50° C (derate 2.5% per °C above 50°)
Ambient Humidity < 95% (non-condensing)
Maximum Altitude 3300 ft (1000 m) above sea level (derate 5% per additional 3300 ft)
Input Line Voltages 208/240 Vac, 400/480 Vac, 480/590 Vac
Input Voltage Tolerance +10%, -15%
Input Frequency Tolerance 48 to 62 Hz
Output Wave Form Sine Coded PWM
Output Frequency 0 - 240 Hz (consult factory for higher output frequencies)
Carrier Frequency 4 kHz to 10 kHz (over 6 kHz requires derating; see parameter P02)
Service Factor 1.00 (up to 6 kHz carrier; derate above 6 kHz; see parameter P02)
Efficiency Up to 98%
Power Factor (displacement) 0.96 or better
Overload Current Capacity 150% for 60 seconds, 180% for 30 seconds
Speed Reference Follower 0-10 VDC, 4-20 mA
Control Voltage 15 VDC
Power Supply for Auxiliary Relays 50 mA at 12 VDC
Analog Output 0 - 10 VDC or 2 - 10 VDC: Proportional to frequency and load
Digital Outputs Open-collector outputs: 50 mA at 30 VDC
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 9
5.0 SCF RATINGS
MODEL
NUMBER
(NOTE 1)
FOR MOTORS
RATED
INPUT (50-60 Hz) OUTPUT HEAT LOSS
(WATTS)
(NOTE 5)
INPUT
PHASE
CURRENT
(AMPS)
POWER
(kVA)
CURRENT
(AMPS)HP kW
SF200Y SERIES (NOTE 2) 208 / 240 Vac 0 - 200 / 230 Vac STD THRU
SF203Y 0.25 0.20 1 3.6 / 3.2 0.76 1.6 / 1.4 19 N/A
SF203Y 0.25 0.20 3 1.9 / 1.7 0.71 1.6 / 1.4 19 N/A
SF205Y 0.5 0.37 1 5.4 / 4.7 1.2 2.5 / 2.2 26 N/A
SF205Y 0.5 0.37 3 3.1 / 2.7 1.1 2.5 / 2.2 26 N/A
SF210Y 1 0.75 1 10.6 / 9.2 2.2 4.8 / 4.2 49 18
SF210Y 1 0.75 3 5.8 / 5.1 2.1 4.8 / 4.2 49 18
SF215Y 1.5 1.1 1 13.9 / 12.0 2.9 6.9 / 6.0 82 23
SF215Y 1.5 1.1 3 8.0 / 6.9 2.9 6.9 / 6.0 82 23
SF220Y 2 1.5 1 14.8 / 12.9 3.1 7.8 / 6.8 86 26
SF220Y 2 1.5 3 9.1 / 7.9 3.2 7.8 / 6.8 86 26
SF230Y 3 2.2 1 19.7 / 17.1 4.1 11.0 / 9.6 130 29
SF230Y 3 2.2 3 12.4 / 10.8 4.4 11.0 / 9.6 130 29
SF250Y 5 3.7 1 29 / 26 6.1 17.5 / 15.2 212 40
SF250Y 5 3.7 3 19.6 / 17.1 7.1 17.5 / 15.2 212 40
SF200 SERIES (NOTE 2) 208 / 240 Vac 0 - 200 / 230 Vac
SF210 1 0.75 3 5.8 / 5.1 2.1 4.8 / 4.2 41 11
SF215 1.5 1.1 3 8.0 / 6.9 2.9 6.9 / 6.0 69 13
SF220 2 1.5 3 9.1 / 7.9 3.3 7.8 / 6.8 78 15
SF230 3 2.2 3 12.4 / 10.8 4.5 11.0 / 9.6 117 20
SF250 5 3.7 3 19.6 / 17.1 7.1 17.5 / 15.2 187 22
SF275 7.5 5.5 3 28 / 25 10.3 25 / 22 286 31
SF2100 10 7.5 3 34 / 32 13.1 30 / 28 379 39
SF2150 15 11 3 54 / 48 20.0 48 / 42 476 51
SF2200 20 15 3 65 / 61 25.4 58 / 54 648 N/A
NOTE 1: See Section 3.0 for model number breakdown.
NOTE 2: The higher current ratings are for 208 Vac input and the lower current ratings are for 240 Vac input.
NOTE 5: STD = standard unit; THRU = through-hole mount unit. Values are worst-case (not typical) for 6kHz carrier
frequency at full speed and full load.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

10 SF01U
MODEL
NUMBER
(NOTE 1)
FOR MOTORS
RATED
INPUT (50-60 Hz) OUTPUT HEAT LOSS
(WATTS)
(NOTE 5)
INPUT
PHASE
CURRENT
(AMPS)
POWER
(kVA)
CURRENT
(AMPS)HP kW
SF400 SERIES (NOTE 3) 400 / 480 Vac 0 - 400 / 460 Vac STD THRU
SF405 0.5 0.37 3 1.6 / 1.4 1.1 1.3 / 1.1 26 N/A
SF410 1 0.75 3 2.9 / 2.5 2.1 2.4 / 2.1 40 12
SF415 1.5 1.1 3 4.0 / 3.6 3.0 3.4 / 3.0 56 13
SF420 2 1.5 3 4.6 / 4.0 3.3 3.9 / 3.4 67 14
SF430 3 2.2 3 6.2 / 5.4 4.5 5.5 / 4.8 100 19
SF450 5 3.7 3 9.8 / 8.6 7.1 8.7 / 7.6 168 22
SF475 7.5 5.5 3 14.2 / 12.4 10.3 12.6 / 11.0 254 29
SF4100 10 7.5 3 18.1 / 15.8 13.1 16.1 / 14.0 310 37
SF4150 15 11 3 27 / 24 20.0 24 / 21 390 42
SF4200 20 15 3 35 / 31 25.8 31 / 27 530 57
SF4250 25 18.5 3 44 / 38 31.6 39 / 34 648 72
SF4300 30 22 3 52 / 45 37.4 46 / 40 770 N/A
SF500 SERIES (NOTE 4) 480 / 590 Vac 0 - 460 / 575 Vac
SF510 1 0.75 3 2.2 / 2.0 1.9 / 2.0 1.9 / 1.7 40 12
SF520 2 1.5 3 4.0 / 3.5 3.3 / 3.6 3.4 / 3.0 67 13
SF530 3 2.2 3 4.7 / 4.7 3.9 / 4.8 4.2 / 4.2 100 14
SF550 5 3.7 3 7.4 / 7.4 6.1 / 7.5 6.6 / 6.6 168 19
SF575 7.5 5.5 3 11.2 / 11.2 9.3 / 11.4 9.9 / 9.9 254 29
SF5100 10 7.5 3 13.7 / 13.7 11.4 / 14.0 12.2 / 12.2 310 37
SF5150 15 11 3 22 / 22 18.3 / 22.5 19.0 / 19.0 390 42
SF5200 20 15 3 27 / 27 22.4 / 27.6 24 / 24 530 57
SF5250 25 18.5 3 31 / 31 25.8 / 31.7 27 / 27 648 72
NOTE 1: See Section 3.0 for model number breakdown.
NOTE 3: The higher current ratings are for 400 Vac input and the lower current ratings are for 480 Vac input.
NOTE 4: The higher current ratings are for 480 Vac input and the lower current ratings are for 590 Vac input.
NOTE 5: STD = standard unit; THRU = through-hole mount unit. Values are worst-case (not typical) for 6kHz carrier
frequency at full speed and full load.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 11
6.0 INSTALLATION
NOTE
SCF Series drives are intended for inclusion within other equipment, by
professional electrical installers according to EN 61000-3-2. They are not
intended for stand-alone operation
WARNING!
Drives must NOT be installed where subjected to adverse environmental
conditions such as: combustible, oily, or hazardous vapors or dust; excessive
moisture or dirt; vibration; excessive ambient temperatures. Consult Lenze
AC Tech for more information on the suitability of a drive to a particular
environment.
SCF models are suitable for UL pollution degree 2 environment only, and MUST be installed in
an electrical enclosure which will provide complete mechanical protection and will maintain the
internal temperature within the drive’s ambient operating temperature rating. All drive models
MUST be mounted in a vertical position for proper heatsink cooling.
Maintain a minimum spacing around the drive of at least 1 inch (25 mm) on each side and
2 inches (50 mm) on the top and bottom for units rated up to 5 HP (3.7 kW). For units rated
7.5 - 30 HP (5.5 - 22 kW), maintain at least 2 inches (50 mm) on each side and 4 inches (100
mm) on the top and bottom. Allow more spacing if the drive is mounted next to other heat-
producing equipment. Do not mount drives above other drives or heat producing equipment.
Fans or blowers should be used to insure proper cooling in tight quarters.
In order to properly size an enclosure, the heat generated by the drive(s) must be known. Refer
to the HEAT LOSS columns in Section 5.0 - SCF RATINGS. The STD column is for standard
units, and the THRU column is for through-hole mount units (drives with the through-hole
mount option still generate some heat inside the enclosure that must be taken into account).
An enclosure manufacturer can then determine the required enclosure size based on the total
heat generated inside the enclosure (from the drive(s) and other heat sources), the maximum
allowable temperature inside the enclosure, the maximum ambient temperature outside the
enclosure, and the enclosure properties.
The SCF Series is UL approved for solid state motor overload protection. Therefore, a separate
thermal overload relay is not required for single motor applications.
6.1 INSTALLATION AFTER A LONG PERIOD OF STORAGE
STOP!
Severe damage to the drive can result if it is operated after a long period of
storage or inactivity without reforming the DC bus capacitors!
If input power has not been applied to the drive for a period of time exceeding three years
(due to storage, etc), the electrolytic DC bus capacitors within the drive can change internally,
resulting in excessive leakage current. This can result in premature failure of the capacitors
if the drive is operated after such a long period of inactivity or storage.
In order to reform the capacitors and prepare the drive for operation after a long period of
inactivity, apply input power to the drive for 8 hours prior to actually operating the motor.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

12 SF01U
6.2 EXPLOSION PROOF APPLICATIONS
Explosion proof motors that are not rated for inverter use lose their certification when used
for variable speed. Due to the many areas of liability that may be encountered when dealing
with these applications, the following statement of policy applies:
“Lenze AC Tech Corporation inverter products are sold with no warranty of fitness for a
particular purpose or warranty of suitability for use with explosion proof motors. Lenze AC Tech
Corporation accepts no responsibility for any direct, incidental or consequential loss, cost, or
damage that may arise through the use of its AC inverter products in these applications. The
purchaser expressly agrees to assume all risk of any loss, cost, or damage that may arise
from such application."
7.0 INPUT AC POWER REQUIREMENTS
DANGER!
Hazard of electrical shock! Capacitors retain charge after power is removed.
Disconnect incoming power and wait until the voltage between terminals B+
and B- is 0 VDC before servicing the drive.
The input voltage must match the nameplate voltage rating of the drive. Voltage fluctuation
must not vary by greater than 10% overvoltage or 15% undervoltage.
NOTE
Drives with dual input voltage ratings must be programmed for the proper
supply voltage (refer to Parameter 01 - LINE VOLTAGE SELECTION in
Section 15.0 - DESCRIPTION OF PARAMETERS).
The drive is suitable for use on a circuit capable of delivering not more than 5,000 RMS
symmetrical amperes at 5 HP (3.7 kW) and below, and 18,000 RMS symmetrical amperes at
7.5 HP (5.5 kW) and above, at the drive’s rated voltage.
If the kVA rating of the AC supply transformer is greater than 10 times the input kVA rating
of the drive(s), an isolation transformer or 2-3% input line reactor must be added to the line
side of the drive(s).
Three phase voltage imbalance must be less than 2.0% phase to phase. Excessive phase to
phase imbalance can cause severe damage to the drive’s power components.
Motor voltage should match line voltage in normal applications. The drive’s maximum output
voltage will equal the input voltage. Use extreme caution when using a motor with a voltage
rating which is different from the input line voltage.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 13
7.1 INPUT VOLTAGE RATINGS
SF200 Series drives are rated for 208/240 Vac, three phase, 50-60 Hz input. The drive will
function with input voltages of 208 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz.
SF200Y Series drives are rated for 208/240 Vac, single or three phase, 50-60 Hz input. The
drive will function with input voltage of 208 to 240 Vac (+10%, -15%), at 48 to 62 Hz.
SF400 Series drives are rated for 400/480 Vac three phase, 50-60 Hz input. The drive will
function with input voltages of 400 to 480 Vac (+ 10%, - 15%), at 48 to 62 Hz.
SF500 Series drives are rated for 480/590 Vac, three phase, 50-60 Hz input, and will function
with input voltages of 480 to 590 Vac (+ 10%, - 15%), at 48 to 62 Hz.
NOTE
Parameter 01 - LINE VOLTAGE SELECTION must be programmed
according to the applied input voltage. See Section 15.0 - DESCRIPTION
OF PARAMETERS.
7.2 INPUT FUSING AND DISCONNECT REQUIREMENTS
A circuit breaker or a disconnect switch with fuses must be provided in accordance with the
National Electric Code (NEC) and all local codes. Refer to the following tables for proper fuse/
circuit breaker ratings and wire sizes.
INPUT FUSE & CIRCUIT BREAKER RATINGS
208/240 Vac, 1 phase 208/240 Vac, 3 phase 400/480 Vac, 3 phase 480/590 Vac, 3 phase
MODEL RATING MODEL RATING MODEL RATING MODEL RATING
SF203Y 10 A SF203Y 10 A
SF205Y 10 A SF205(Y) 10 A SF405 10 A
SF210Y 15 A SF210(Y) 10 A SF410 10 A SF510 10 A
SF215Y 20 A SF215(Y) 12 / 10 A SF415 10 A
SF220Y 25 / 20 A SF220(Y) 15 / 12 A SF420 10 A SF520 10 A
SF230Y 30 / 25 A SF230(Y) 20 / 15 A SF430 10 A SF530 10 A
SF250Y 45 / 40 A SF250(Y) 30 / 25 A SF450 15 A SF550 12 A
SF275 45 / 40 A SF475 20 A SF575 20 A
SF2100 50 / 50 A SF4100 30 / 25 A SF5100 20 A
SF2150 80 / 75 A SF4150 40 / 35 A SF5150 30 A
SF2200 100 / 90 A SF4200 50 / 45 A SF5200 40 A
SF4250 70 / 60 A SF5250 45 A
SF4300 80 / 70 A
NOTE
• Applicable national and local electrical codes take precedence over
recommendations in these tables.
• Use UL Class CC fast-acting, current limiting type fuses. Select fuses with low
I 2 T values, rated at 200,000 AIC. Recommended fuses are Bussman
KTK-R, JJN, and JJS. Similar fuses with equivalent ratings by other
manufacturers may also be acceptable.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

14 SF01U
WARNING!
This product can cause a DC current in the protective conductor. Where a
residual current device (RCD) is used for protection in case of direct or indirect
contact, only an RCD of Type B is allowed on the supply side of this product.
Otherwise, another protective measure shall be applied, such as separation
from the environment by double or reinforced insulation, or isolation from the
supply system by a transformer.
Observe the following when using RCDs:
1. Only install the RCD between the supply mains and drive controller.
2. The RCD can be activated by:
- capacitive leakage currents between the cable screens during operation
(especially with long, screened motor cables)
- connecting several drives to the mains at the same time
- additional RFI filters
7.3 INPUT WIRE SIZE REQUIREMENTS
WIRE SIZE REQUIREMENTS
208/240 Vac, 1 phase 208/240 Vac, 3 phase 400/480 Vac, 3 phase 480/590 Vac, 3 phase
MODEL AWG mm2MODEL AWG mm2MODEL AWG mm2MODEL AWG mm2
SF203Y 14 2.5 SF203Y 14 2.5
SF205Y 14 2.5 SF205Y 14 2.5 SF405 14 2.5
SF210Y 12 4.0 SF210(Y) 14 2.5 SF410 14 2.5 SF510 14 2.5
SF215Y 12 4.0 SF215(Y) 14 2.5 SF415 14 2.5
SF220Y 10 6.0 SF220(Y) 12 4.0 SF420 14 2.5 SF520 14 2.5
SF230Y 10 6.0 SF230(Y) 10 6.0 SF430 14 2.5 SF530 14 2.5
SF250Y 8 6.0 SF250(Y) 10 10 SF450 14 2.5 SF550 14 2.5
SF275 10 10 SF475 12 4.0 SF575 14 2.5
SF2100 8 10 SF4100 10 6.0 SF5100 12 4.0
SF2150 6 16 SF4150 8 10 SF5150 10 6.0
SF2200 4 25 SF4200 8 10 SF5200 8 10
SF4250 6 16 SF5250 8 10
SF4300 6 16
7.4 INSTALLATION ACCORDING TO EMC REQUIREMENTS
The SCF Series can be installed to meet the European standards for Electromagnetic
Compatibility (EMC) requirements. These requirements govern the permissible electromagnetic
emissions and immunity, both radiated and conducted, of a drive system.
The EMC requirements apply to the final installation in its entirety, not to the individual
components used. Because every installation is different, the recommended installation should
follow these guidelines as a minimum. Additional equipment (such as ferrite core absorbers
on power conductors) or alternative wiring practices may be required to meet conformance
in some installations.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 15
Filter: The input to the drive (or group of drives) must include a filter to reduce the electrical
noise reflected back to the AC Line. The SCM can be installed to meet the industrial standards
set by the EU, EN 61800-3 for conducted emissions and EN 55011 for radiated emissions to
class A compliance when installed with an appropriately installed external line filter.
EMC
Compliance with EN 61800-3/A11
Installation: Shielded cable must be used for all control and power cables
and exposed wiring must be kept as short as possible.
A Screen clamps
B Control cable
C Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D Electrically conductive mounting plate
E Filter
8.0 POWER WIRING
DANGER!
Hazard of electrical shock! Capacitors retain charge after power is removed.
Disconnect incoming power and wait until the voltage between terminals B+
and B- is 0 VDC before servicing the drive.
Note drive input and output current ratings and check applicable electrical codes for required
wire type and size, grounding requirements, over-current protection, and incoming power
disconnect, before wiring the drive. Size conservatively to minimize voltage drop.
Refer to Section 9.0 - SCF POWER WIRING DIAGRAM for information on torque and wire
stripping requirements for power wiring.
Input fusing and a power disconnect switch or contactor MUST be wired in series with terminals
L1, L2, and L3 for three phase input models. For 208/240 Vac single phase input models, use
terminals L1 and L2. This disconnect must be used to power down the drive when servicing,
or when the drive is not to be operated for a long period of time, but should not be used to
start and stop the motor.
Repetitive cycling of a disconnect or input contactor (more than once every two minutes)
may cause damage to the drive.
8.1 WIRING FOR SINGLE PHASE OR THREE PHASE INPUT
If the drive is rated for single and three phase input (SF200Y models), wire to terminals L1 and
L2 for single phase input, or wire to terminals L1, L2, and L3 for three phase input.
If the drive is rated for three phase input, wire the input to terminals L1, L2, and L3.All three
power output wires, from terminals T1, T2, and T3 to the motor, must be kept tightly bundled
and run in a separate conduit away from all other power and control wiring.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

16 SF01U
It is not recommended to install contactors or disconnect switches between the drive and motor.
Operating such devices while the drive is running can potentially cause damage to the drive's
power components. If such a device is required, it should only be operated when the drive is
in a STOP state. If there is potential for the device to be opened while the drive is running, the
drive must be programmed for COAST to stop (see Parameter 4 - STOP METHOD), and an
auxiliary contact on the device must be interlocked with the drive's run circuit. This will give
the drive a stop command at the same time the device opens, and will not allow the drive to
start again until the device is closed.
9.0 SCF POWER WIRING DIAGRAM
3 PHASE
AC MOTOR
DC BUS
VOLTAGE
OUTPUT (ALL SERIES)
T1 T2 T3 B- B+
+
SINGLE PHASE INPUT
(SF200Y SERIES)
L1 L2 L3
THREE PHASE INPUT
(SF200, SF200Y, SF400,
AND SF500 SERIES)
L1 L2 L3
4.5 lb-in / 0.5 Nm
0.24 in / 6 mm
10 lb-in / 1.2 Nm
0.35 in / 9 mm
18 lb-in / 2.0 Nm
0.5 in / 13 mm
15 - 30 HP
(11 - 22 kW)
7.5 - 10 HP
(5.5 - 7.5 kW)
0.25 - 5 HP
(0.37 - 3.7 kW)
STOP!
DO NOT connect incoming AC power to output terminals T1, T2, T3, or
terminals B+, B-! Severe damage to the drive will result.
NOTE
• WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL
APPLICABLE LOCAL CODES.
• Motor wires MUST be run in a separate steel conduit away from control
wiring and incoming AC power wiring.
• Do not install contactors between the drive and the motor without consulting
AC Technology for more information. Failure to do so may result in drive
damage.
• Use only UL and CSA listed and approved wire.
• Minimum wire voltage rating is 300 V for 120, 208, and 240 Vac systems,
and 600 V for 400 and 480 Vac systems.
• Wire gauge must be based on a minimum of 125% of the rated input/output
current of the drive, and a minimum 75°C insulation rating. Use copper
wire only.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

SF01U 17
10.0 CONTROL WIRING
10.1 CONTROL WIRING VS. POWER WIRING
External control wiring MUST be run in a separate conduit away from all other input and output
power wiring. If control wiring is not kept separate from power wiring, electrical noise may be
generated on the control wiring that will cause erratic drive behavior. Use twisted wires or
shielded cable grounded at the drive chassis ONLY. Recommended control wire is Belden
8760 (2-wire) or 8770 (3-wire), or equivalent.
NOTE
Control terminals provide basic isolation (insulation per EN 61800-5-1).
Protection against contact can only be assured by additional measures e.g.
supplemental insulation.
Strip off 0.20 to 0.25 inches (5 to 6 mm) of insulation for control wiring, and torque the terminals
to 2 lb-in (0.2 Nm). Be careful not to overtorque the terminals, as this will cause damage to
the terminal strip. This is not covered under warranty and can only be repaired by replacing
the control board.
10.2 TB-2: CIRCUIT COMMON
The TB-2 terminals are used as circuit common for the start/stop, forward/reverse, input
select, local/remote, analog input, and analog output functions. There are three TB-2 terminals
available on the terminal strip, and they are all internally connected to each other on the main
control board. If necessary TB-2 may be connected to chassis ground.
NOTE
TB-2 must be connected to chassis ground when using serial
communications.
10.3 SURGE SUPPRESION ON RELAYS
Current and voltage surges and spikes in the coils of contactors, relays, solenoids, etc, near
or connected to the drive, can cause erratic drive operation. Therefore, a snubber circuit
should be used on coils associated with the drive. For AC coils, snubbers should consist of
a resistor and a capacitor in series across the coil. For DC coils, a free-wheeling or flyback
diode should be placed across the coil. Snubbers are typically available from the manufacturer
of the device.
10.4 START/STOP CONTROL
There are various control schemes that allow for 2-wire and 3-wire Start/Stop circuits. Refer
to the wiring diagrams in Section 11.0 - SCF CONTROL WIRING DIAGRAMS
10.5 SPEED REFERENCE SIGNALS
The drive allows for three analog speed reference inputs:
SPEED POT Connect the wiper of a speed pot to terminal TB-5, and connect the high and
low end leads to terminals TB-6 and TB-2, respectively. The speed pot can
be 2.5kΩ up to 10kΩ.
0-10 VDC Wire the positive to terminal TB-5 and the negative to terminal TB-2. TB-5
input impedance is 120 kilohms.
4-20 mA Wire the positive to terminal TB-25 and the negative to terminal TB-2. TB-25
input impedance is 100 ohms.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
This manual suits for next models
37
Table of contents
Other Lenze AC Tech Controllers manuals
Popular Controllers manuals by other brands

InoTec
InoTec CPS 220 Series Mounting and operating instructions

Siemens
Siemens SIPART PS2 6DR5 series operating instructions

KREPEL
KREPEL TOUCH VIEW Operating and users manual

MR
MR VACUTAP VM Series operating instructions

Omega
Omega PHCN-37 Quick start up guide

Pentair
Pentair COLOR SYNC quick start guide

ZIEHL-ABEGG
ZIEHL-ABEGG R-E-0.5E operating instructions

SEW-Eurodrive
SEW-Eurodrive Movipro MPCI-DCMA-82-MMCX Addendum to the operating instructions

Nevco
Nevco 541 Operator instructions

Parker
Parker A4AT-DN Installation and Service Information

Franklin Fueling Systems
Franklin Fueling Systems TS-SCM installation guide

Omron
Omron NX102 series user manual