Lightronics AC1109 User manual

www.lightronics.com
Lightronics Inc. 509 Central Drive Virginia Beach, Va 234354 757 486 3588
AC1109
Architectural Remote Station
Version 0.2
Date 12/11/2020

Page 2 of 4
AC1109 ARCHITECTURAL REMOTE STATION
Version 0.2 OWNERS MANUAL 12/11/2020
www.lightronics.com
Lightronics Inc. 509 Central Drive, Virginia Beach, VA 23454 757 486 3588
DESCRIPTION OF UNIT
The AC1109 is a wall mounted, eight scene, remote
station for use with the Lightronics LitNet
architectural control system. The LitNet host units
consist of the AR and AB series of architectural
dimmers, the RA rack mount dimmers and the SR &
SC architectural controllers. User operation is as
simple as it can get (eight numbered scene buttons
and an "OFF" control). LED scene indicators
always display the active scene number.
The unit fits into a standard single gang wall switch
box. The unit communicates on LitNet via a four
wire bus which will accommodate several remotes
and other controls. All LitNet wiring is low voltage.
The unit basically operates in an exclusive mode
where one scene may be activated at a time. When a
scene is selected, the lighting circuits fade at a user
controlled rate to that scene. A blackout button is
also provided to shut all scenes.
Scenes activated by the AC1109 are actually set up
and stored in the LitNet host. The AC1109 only
tells the host which scene to activate. The host can
be programmed to respond to the AC1109 in various
ways to create zone controls.
The AC1109 is normally factory set to operate with
scenes 1 - 8 (block 1) of the dimmer. It can be
factory set to operate with other blocks of 8 scenes
as follows.
Multiple AC1109 units using different scene blocks
can be used together to create zone control.
INSTALLATION
The AC1109 connects to the LitNet system via a
shielded 4 conductor cable arranged as 2 twisted
pairs. One pair connects to the DATA - and DATA
+ signals. The other pair carries the common and
power. Refer to the diagram AC1109
CONNECTIONS in this manual for additional
wiring information.
SINGLE UNIT: Connect the 4 cable wires to the
screw down terminals on the back of the unit.
Connect the cable shield to the REMOTE
COMMON pin. The other end of the cable connects
to the host by different methods. Refer to the host
product Owners Manual for additional wiring
details.
MULTIPLE UNITS: Follow the instructions for a
single unit for the first AC1109. Connect pin 1 of
the second unit to pin 1 of the first unit. Continue for
the remaining wires and shield. Repeat the
procedure for additional AC1109 units.
OPERATION
No setup or turn on procedure is needed. When the
LitNet host is powered on, the AC1109(s) will also
be powered. If communication with the LitNet host
cannot be established, an AC1109 will appear to be
repeatedly scanning through all scenes.
Scenes to be activated by an AC1109 must have
already been created and stored in the LitNet host.
See the host product Owners Manual for instruction
on programming scenes.
If a scene is activated from an "OFF" condition but
has no channels assigned to it which are on or
partially on then the scene LED indicator will light
and the "OFF" indicator will remain lighted.
If a scene with no channels on or partially on is
activated while another scene which does have on or
partially on channels is active then the LED
indicator for the scene will light and the previous
scene indicator will remain lighted
Block 1
Scenes 1 - 8
Block 4
Scenes 25 - 32
Block 2
Scenes 9 - 16
Block 5
Scenes 33 - 40
Block 3
Scenes 17- 24
Block 6
Scenes 41 - 48

Page 3 of 4
AC1109 ARCHITECTURAL REMOTE STATION
Version 0.2 OWNERS MANUAL 12/11/2020
www.lightronics.com
Lightronics Inc. 509 Central Drive, Virginia Beach, VA 23454 757 486 3588
MAINTENANCE AND REPAIR
TROUBLESHOOTING
1. Check the cable and its connections
2. If the unit is being used with a multiple LitNet
hosts - ensure that one (and only one) of the hosts in
the system is set to UNIT ID 00
OWNER MAINTENANCE
There are no user serviceable parts in the unit.
Service by other than Lightronics authorized agents
will void your warranty.
OPERATING AND MAINTENANCE ASSISTANCE
Dealer and Lightronics Factory personnel can help
you with operation or maintenance problems. Please
read the applicable parts of this manual before calling
for assistance. If service is required - contact the
dealer from whom you purchased the unit or contact
Lightronics, Service Dept..
AC1109 CONNECTIONS
4
3
2
1
AC110
Rear
REMOTE VOLTAGE +
REMOTE COMMON
REMOTE DATA -
REMOTE DATA +
SHIELD
To
LitNet
Host
To Other
LitNet Remotes
If Used

All Lightronics products are warranted for a period of TWO/FIVE YEARS from the date of
purchase against defects in materials and workmanship.
This warranty is subject to the following restrictions and conditions:
A) If service is required, you may be asked to provide proof of purchase from an authorized
Lightronics dealer.
B) The FIVE YEAR WARRANTY is only valid if the warranty card is returned to Lightronics
accompanied with a copy of the original receipt of purchase within 30 DAYS of the
purchase date, if not then the TWO YEAR WARRANTY applies. Warranty is valid only for
the original purchaser of the unit.
C) This warranty does not apply to damage resulting from abuse, misuse, accidents, shipping,
and repairs or modifications by anyone other than an authorized Lightronics service
representative.
D) This warranty is void if the serial number is removed, altered or defaced.
E) This warranty does not cover loss or damage, direct or indirect arising from the use or
inability to use this product.
F) Lightronics reserves the right to make any changes, modifications, or updates as deemed
appropriate by Lightronics to products returned for service. Such changes may be made
without prior notification to the user and without incurring any responsibility or liability for
modifications or changes to equipment previously supplied. Lightronics is not responsible
for supplying new equipment in accordance with any earlier specifications.
G) This warranty is the only warranty either expressed, implied, or statutory, upon which the
equipment is purchased. No representatives, dealers or any of their agents are authorized
to make any warranties, guarantees, or representations other than expressly stated herein.
H) This warranty does not cover the cost of shipping products to or from Lightronics for
service.
I) Lightronics Inc. reserves the right to make changes as deemed necessary to this warranty
without prior notification.
WARRANTY
Lightronics Inc. 509 Central Drive Virginia Beach, VA 23454 20050125
Other Lightronics Remote Control manuals