Littelfuse Startco EL3100 User manual

EL3100 MANUAL
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
REVISION 2-B-022216
Copyright © 2016 by Littelfuse Startco
All rights reserved.
Document Number: PM-1065-EN
Printed in Canada
3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols

Page i
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
This page intentionally left blank.

Page ii
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
TABLE OF CONTENTS
SECTION PAGE
1 Description........................................................... 1
2 Features................................................................ 1
3 Remote Indication............................................... 1
4 Output Contact.................................................... 1
5 Installation........................................................... 1
6 Technical Specifications...................................... 5
6.1 EL3100 ....................................................................... 5
6.2 Remote LED’s (RK-310X-0X) ................................. 5
7 Ordering Information......................................... 6
8 Warranty ............................................................. 6
Appendix A EL3100 Revision History.......................... 7
LIST OF FIGURES
FIGURE PAGE
1 EL3100 Series Outline and Mounting Details ...... 2
2 Connection Diagram ............................................. 3
3 Remote 16-mm IP67 LED Lamp Outline and
Mounting Details................................................... 3
4 Remote LED Labels.............................................. 4
DISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a
result of a malfunction, incorrect application, or incorrect
adjustment.

Page iii
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
This page intentionally left blank.

Page 1
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
1. DESCRIPTION
The EL3100 is a self-powered ground-fault and phase-
voltage indication system for three-phase systems. The
EL3100 meets the National Electrical Code requirements
for ground detectors for ungrounded alternating-current
systems as defined in NEC 250.21. It also meets the
Canadian Electrical Code requirements for ungrounded
alternating-current systems in accordance with
CEC 10-106(2).
Voltage connections are provided on the EL3100 for
208-, 240-, 480-, and 600-V systems. Three green LED’s
on the EL3100 indicate the presence of phase-to-ground
voltage and one red LED indicates a ground fault. The
phase LED intensity is a function of line-to-ground voltage
providing visual indication of phase balance.
There are cases when one of the three phase indicators
is off but no ground fault is indicated. This occurs on an
ungrounded system when there is a phase loss. Ground-
fault indication is still enabled and will be activated when
either of the energized phases develops a ground fault.
The EL3100 can operate stand-alone or with up to five
remote LED indicators. High-intensity 16-mm IP67 LED
lamps are available in red and green colors. LED indicators
and wiring operate in low-voltage mode.
A solid-state relay output provides indication of a
ground fault. The output relay is closed when the three-
phase neutral voltage shifts as the result of ground leakage.
2. FEATURES
Direct connection to EL3100 for voltages up to
600 Vac line-to-line
Provides faulted-phase indication for resistance-
grounded and ungrounded systems
Provides phase-voltage indication for resistance-
grounded and ungrounded systems
The EL3100 can be used stand-alone or with low-
voltage remote LED’s
oSolid-state (100 mA, 120 Vac/Vdc) output relay
oThree green phase-voltage LED’s
oOne red ground-fault LED
oUp to five remote LED’s can be connected
3. REMOTE INDICATION
Terminals 10 through 15 are used for remote LED
indication. High-intensity LED’s with no internal resistors
are required. See Section 7 for ordering information. Fig.
2 illustrates a remote LED application where all LED’s are
used.
There are five remote LED outputs for phase-voltage
indication, no-ground-fault indication, and ground-fault
indication. Connect optional remote LED’s to terminals
DA, DB, and DC (12, 11, and 10) for phase-voltage
indication. The intensity of these LED’s is proportional to
phase-to-ground voltage. A ground fault or phase loss is
indicated when one LED is off while the other two are on.
A remote LED connected to terminal DG (13) provides no-
ground-fault indication. This LED is on when there is no
ground fault and is off when the three-phase-neutral
voltage shifts from ground potential as the result of a
ground fault (or if the system is de-energized). A remote
LED connected to terminal DR (14) is on when a ground
fault is present and off when no ground fault is present (or
the system is de-energized). Terminal DN (15) is the LED
common terminal.
NOTE: Unused LED outputs must be left unconnected.
4. OUTPUT CONTACT
A solid-state normally open ground-fault-indication
relay output is at terminals 16 and 17. The output relay is
closed when the three-phase neutral shifts more than
20 Vac with respect to ground for the “L” voltage inputs
and 40 Vac with respect to ground for the “H” voltage
inputs.
NOTE: The relay output has a rating of 100 mA at
120 Vac/Vdc and has a 35-Ωclosed resistance.
5. INSTALLATION
Outline and mounting details of the EL3100 are shown
in Fig. 1. For 208- or 240-Vac systems use terminals
AL (7), BL (8), and CL (9). For systems above 240 Vac
and up to 600 Vac, use terminals AH (1), BH (3), and
CH (5). Connect bonding terminal (G) to ground. See Fig.
2. Terminals 2, 4, and 6 are not used.
NOTE: Bonding terminal (G) must be connected to ground
for correct fault indication and to ensure that fault potential
is not transferred to the display.
Outline and mounting details for the remote LED’s are
shown in Fig. 3. Cable length should be limited to
10 m (33 ft). The recommended cable is 22 - 18 AWG (0.33
to 0.82 mm2) wire. Use shielded cable for cable lengths
exceeding 2 m (6 ft). When shielded cable is used, connect
cable shield to terminal SH (18) at the EL3100 only.

Page 2
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
FIGURE 1. EL3100 Series Outline and Mounting Details.
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-32.
3. OVERALL HEIGHT WHEN MOUNTED
ON DIN EN50022 35-mm x 7.5-mm
TOP-HAT RAIL.
DISPLAY
208/240
EL3100 SERIES
A
FAULT
SH
480/600
AH BH CH AL BL CL
DN DR DG DA DB DC
19 1718 16 15 1314 12 11 10
126
45
39
8
7
C
B
G
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
87.0
(3.43)
112.5
(4.43)
52.5
(2.07)
56.0
(2.20)
NOTE 3
TOP SIDE
CABLE-TIE EYELET
4 PLACES
BOTTOM
12.5
(0.50)
60.0
(2.36)
14.5
(0.57)
6.8
(0.27)
6.8
(0.27)
100.0
(3.94)
MOUNTING DETAIL
M4 OR 8-32TAP
2 LOCATIONS
NOTE 2

Page 3
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
FIGURE 2. Connection Diagram.
FIGURE 3. Remote 16-mm IP67 LED Lamp Outline and Mounting Details.
SERVICE
ENCLOSURE
ALAH BLBH CLCH
NOTE 1
NOTES
:
1. USE LTERMINALS FOR
SYSTEMS UPTO 240 VAC. USE
H TERMINALS FOR SYSTEMS
ABOVE 240 VAC UPTO
600 VAC.
2. USE SHIELDED 22 AWGTO
18 AWG (0.33TO 0.82 mm2)
CABLE FOR DISTANCES
LONGERTHAN 2 M (6 FT).
USE BELDEN 3002A OR
EQUIVALENT.
3. NOTE LED POLARITY.
SEE FIG. 3.
A
B
C
1 7 3 8 5 9
19
17
16
A
B
C
13
12
11
10
GROUND
NOTE 2
FAULT
G
G
G
R
18
15
14
REMOTE INDICATION
NOTE 3
DN
DR
DG
DA
DB
DC
SH
+
+
+
+
+
FAULT
NO FAULT
PHASE A
PHASE B
PHASE C
G
4.8
(0.19)
13.5
(0.53)
33.8
(1.33)
18.3
(0.72)
Ø 16.0 ±0.1
SIDE VIEW PANEL CUTOUT
NOTES:
1. DIMENSIONS IN
MILLIMETRES (INCHES).
+
GOLD TERMINAL
-
SILVER TERMINAL
2.8 x 0.8 TYP
10.0
(0.39)
9.35
(0.37)
(0.11 x 0.03)
(0.63 ±0.004)

Page 4
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
FIGURE 4. Remote LED Labels.
RK-310R-01 RK-310G-01
RK-311X-01
30.0
(1.18)
15.0
(0.59)
20.0
(0.79)
50.0
(1.97)
Ø20.0 (0.79)
OUTLINE DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. DIMENSIONS ARE IDENTICAL FOR ALL LABELS.
3. RK-311X-01 (PHASE B VOLTAGE) SHOWN.
NOTE 3

Page 5
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
6. TECHNICAL SPECIFICATIONS
6.1 EL3100
Phase Voltage:
Input L ................................ 240 Vac line-to-line
Input H................................ 600 Vac line-to-line
Input L, maximums............. 240 Vac to ground,
0.8 mA input current
Input H, maximums ............ 600 Vac to ground,
2.0 mA input current
Internal Fuses (6) ................ 500 mA, 600 Vac,
not field serviceable
Frequency Response (3 dB) .....0 to 300 Hz
Trip Threshold:
Input L(1) ............................. 20 Vac
Input H(1) ............................. 40 Vac
Fault Current(2).................... 350 µA
Solid-State Relay Output:
Configuration...................... N.O. (Form A)
Operating Mode .................. Non-Fail-Safe
Rating .................................100 mA, 120 V,
12 W (ac or dc)
Protection............................ 130 V MOV
Closed Resistance ............... 35 Ωmaximum
Dielectric Strength.............. 1,500 Vac
Terminal Block Wire Sizes:
Voltage Inputs(3).................. 20 to 12 AWG
(0.5 to 2.5 mm2)
Bonding(3) ........................... 20 to 12 AWG
(0.5 to 2.5 mm2)
Relay(3)................................ 20 to 12 AWG
(0.5 to 2.5 mm2)
Display LED’s .................... 24 to 12 AWG
(0.2 to 2.5 mm2)
Dielectric Strength:
Input L(5) ............................. 1800 Vac, 1 s,
12 mA per phase
Input H(5) ............................. 2650 Vac, 1 s,
9 mA per phase
Shipping Weight....................... 0.4 kg (0.9 lb)
EL3100 Dimensions:
Height ................................. 87 mm (3.4”)
Width .................................. 113 mm (4.4”)
Depth .................................. 56 mm (2.2”)
Mounting Configurations ......... DIN Rail and Surface
Environment:
Operating Temperature....... -40 to 60°C (-40 to 140°F)
Storage Temperature .......... -55 to 80°C (-67 to 176°F)
Humidity............................. 85% Non-Condensing
PWB Conformal Coating ......... MIL-1-46058 qualified
UL QMJU2 recognized
Certification.................................CSA, Canada and USA
ULListed
Australia
CAN/CSA C22.2 No. 144-M91 – Ground Fault Circuit
Interrupters
ANSI/UL Std 1053, 6TH Ed. – Standard for Ground Fault
Sensing and Relaying Equipment
CAN/CSA C22.2 No. 14-10 – Industrial Control
Equipment
UL Std 508, 17TH Ed. – Industrial Control Equipment
Australia, Regulatory Compliance Mark (RCM)
6.2 REMOTE LED’S (RK-31XX-0X)
Current ..................................... 0.4 to 2.0 mA
Terminals(4) .............................. 2.8 mm (0.11”) x
0.8 mm (0.03”)
Configuration ........................... 16 mm (0.6”), panel
mount, IP67
Certification.................................UL Recognized E317459
NOTES:
(1) Three-phase neutral-to-ground shift between terminal
G (19) and source supply.
(2) Current flowing in terminal G (19) (ground
connection).
(3) Accepts No. 8 (M4) ring terminals.
(4) Supplied with Faston terminals for 22 – 18 AWG
(0.33 to 0.82 mm2)wire.
(5) With terminal G (19) connected to ground. Do not
remove ground connection to terminal G (19) during
dielectric testing to avoid test potential transfer to the
remote display.
LR 53428
USC
R

Page 6
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
7. ORDERING INFORMATION
8. WARRANTY
The EL3100 Ground-Fault & Phase-Voltage Indicator is
warranted to be free from defects in material and
workmanship for a period of five years from the date of
purchase.
Littelfuse Startco will (at Littelfuse Startco’s option)
repair, replace, or refund the original purchase price of an
EL3100 that is determined by Littelfuse Startco to be
defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care. Littelfuse Startco does not warrant products repaired
or modified by non-Littelfuse Startco personnel.
RK-31
R= Red
G= Green
Remote LED Part Numbers
(see Fig. 4 for label details):
-0
0= No Label
1= GF Status Label
(Single LED Kit Only),
Phase Labels
(Triple LED Kit Only)
EL3100-00
0= Single LED Kit
1= Triple LED Kit

Page 7
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
APPENDIX A
EL3100 REVISION HISTORY
MANUAL
RELEASE DATE MANUAL
REVISION PRODUCT REVISION
(REVISION NUMBER ON PRODUCT LABEL)
February 22, 2016 2-B-022216 02
January 27, 2014 2-A-012714
November 27, 2012 1 01
October 29, 2012 0 00
MANUAL REVISION HISTORY
REVISION 2-B-022216
SECTION 6
RCM certification added.
Frequency response specification added.
REVISION 2-A-012714
S
ECTION 5
Remote LED labels (Fig. 4) added.
S
ECTION 6
Dielectric strength specification added.
S
ECTION 7
Ordering information updated.
A
PPENDIX A
Revision history added.
REVISION 1
S
ECTION 6
Updated solid-state relay protection information.
REVISION 0
Initial release.
PRODUCT REVISION HISTORY
PRODUCT REVISION 02
Added filter capacitor.
P
RODUCT REVISION 01
Solid-state relay protection changed to 130 V.
P
RODUCT REVISION 00
Initial release.

Page 8
EL3100 Ground-Fault & Phase-Voltage Indicator Rev. 2-B-022216
This page intentionally left blank.

Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Littelfuse:
RK-310G-01 RK-310G-00 RK-310R-00 RK-310R-01
Table of contents