LogikaControl LOGIK 26-S User manual

Revision 1 –04.12.2015 1/28
Instructions and Advices
to use the electronic controller
Logik 26-S
ORIGINAL INSTRUCTIONS
(INDUSTRIAL CONTROL EQUIPMENT)
39UG
FILE: E316817

Revision 1 –04.12.2015 2/28
INDEX
CAUTION ..........................................................................................................................................3
TECHNICAL FEATURES......................................................................................................................4
MOUNTING .......................................................................................................................................5
WARNING TO THE WIRING OF THE CONTROLLER.............................................................................5
LEGEND ..............................................................................................................................................................7
CONNECTION SERIAL NET RS485 .....................................................................................................9
MAIN VISUALIZATION ...................................................................................................................10
QUICK SETTING START/STOP PRESSURES (ENABLED WITH PASSWORD LEVEL3) .........................12
GENERAL NOTES TO THE PROGRAMMING.......................................................................................12
M1 MAIN MENU..........................................................................................................................12
M2 ENTER PASSWORD ...............................................................................................................13
M1-1 INFO .................................................................................................................................13
M1-2 PASSWORD.......................................................................................................................13
M1-3 VISUALIZATIONS SETUP...................................................................................................13
M1-4 COMPRESSOR SETUP ........................................................................................................14
M1-5 PRESSURES.......................................................................................................................16
M1-6 TEMPERATURES ................................................................................................................16
M1-7 TIMER...............................................................................................................................16
M1-8 INVERTER RS485 (DANFOSS) ...........................................................................................17
M1-9 ANALOG OUTPUT ..............................................................................................................18
M1-10 HOURS FILTERS/OIL ........................................................................................................19
M1-11 MAINTENANCE LIST..........................................................................................................19
M1-12 ALARMS LIST ....................................................................................................................19
M1-13 TIMER START/STOP..........................................................................................................20
M1-14 RESET ...............................................................................................................................20
ALARMS..........................................................................................................................................21
ALARMS WITH IMMEDIATE COMPRESSOR SHUT-OFF ..............................................................................................21
ALARMS WITH COMPRESSOR SHUT-OFF AFTER 30 SECONDS UNLOAD RUNNING.......................................................21
WARNINGS (VISUAL ALARMS) .............................................................................................................................22
MESSAGES VISUALIZED INTO ALARM LIST ONLY ...................................................................................................22
MAINTENANCE MESSAGES ..................................................................................................................................22
HOW LOGIK 26-S CONTROLS THE COMPRESSOR ............................................................................23
INVERTER OPERATION...................................................................................................................25
INVERTER CONTROLLED VIA ANALOG OUTPUT 4/20mA ..........................................................................................25
INVERTER CONTROLLED VIA RS485 .....................................................................................................................25
MASTER/SLAVE OPERATION ..........................................................................................................26
MASTER/SLAVE INVERTER (ONLY FOR LOGIK26S, LOGIK33S) .................................................................................26
MULTIUNIT OPERATION.................................................................................................................26
WARRANTY TERMS .........................................................................................................................27

Revision 1 –04.12.2015 3/28
CAUTION
THE LOGIK 26-S IS AN INDUSTRIAL CONTROL EQUIPMENT (NOT A SAFETY ISTRUMENT) FOR THE OPERATION
OF A SCREW COMPRESSOR WITH SOFTWARE CLASS A (see EN 60730-1 and EN 60335-1).
THE INSTALLATION MUST BE MADE IN ACCORDANCE TO THE LOCAL AND INTERNATIONAL STANDARDS AND
REGULATIONS WHERE THE COMPRESSOR IS MANUFACTURED.
THE INSTALLATION AND START UP OF THE CONTROLLER MUST BE CARRIED OUT BY TRAINED PERSONNEL
WELL KNOW IN THIS MANUAL.
THE CONTROLLER HAS TO BE USED IN STANDARD INDUSTRIAL ENVIRONMENT AND IT CAN NOT BE USED IN
EXPLOSION RISK ENVIRONMENT, MARITIME AND MILITARY PURPOSE.
THIS MANUAL COULD BE SUBJET TO CHANGES; PLEASE CONTACT LOGIKA CONTROL TECHNICAL OFFICE IN
CASE OF DOUBT ON THE LAST VERSION.
ATTENTION
LA LOGIK 26-S EST UN CONTROLE EQUIPMENT INDUSTRIEL (PAS UN INSTRUMENT DE SECURITE) POUR LE
FONCTIONNEMENT D’UN COMPRESSEUR A VIS AVEC SOFTWARE DE CLASS A (voir EN 60730-1 et EN 60335-1).
L'INSTALLATION DOIT ETRE EFFECTUEE CONFORMEMENT AUX NORMES ET AUX REGLEMENTATIONS LOCALES
ET INTERNATIONALES OU LE COMPRESSEUR EST FABRIQUE.
L'INSTALLATION ET MISE EN MARCHE DE LA COMMANDE DOIVENT ETRE EFFECTUEES PAR DU PERSONNEL
QUALIFIÉ BIEN SAVOIR DANS CE MANUEL.
LE CONTROLEUR DOIT ETRE UTILISE DANS LA NORME ENVIRONNEMENT INDUSTRIEL ET IL NE PEUT PAS ETRE
UTILISE DANS UN ENVIRONNEMENT DE RISQUE D'EXPLOSION ET MARITIME FINS MILITAIRES.
CE MANUEL POURRAIT ETRE SOUS RESERVE DE MODIFICATION; S'IL VOUS PLAIT CONTACTER LOGIKA
CONTROL TECHNIQUE BUREAU EN CAS DE DOUTE SUR LA DERNIERE VERSION.

Revision 1 –04.12.2015 4/28
TECHNICAL FEATURES
-Industrial control equipment for the operation and management of screw compressors only, pollution degree 2.
-In accordance to EC Directives:
-Directive:
-LVD : 2014/35/UE
-EMC: 2014/30/UE
-RHOS: 2011/65/EU
-based on the following harmonized standards applied:
-SAF-EMC: EN 60730-1
-RHOS: EN 50581
-In accordance to UL 508 (FILE #: E316817).
-Black auto-extinguishing box in ABS:
-a) according EC: IP64 for the front panel and IP20 for the other parts;
-b) according UL: type 1 and Type 12 for front panel mounting , installation in pollution degree 2 for the other parts
-Inputs and outputs via terminal-block board to wires (250V, 10A, 12-24AWG) tightening torque 8 Nm.
-Working temperature: 0°C (32°F) ÷ 50°C (122°F) 90% RH (non condensing)
-Storage temperature: -20 (-4°F) ÷ +70 °C (158°F)
-Power supply: 12Vac ± 10% 50 ÷ 60 Hz. (power of the transformer’s secondary: ~ 9 VA) from safety transformer
-Max. current absorbed = ~ 350 mA
- Visualization through back light alphanumerical LCD 20 digits x 2 rows and nr. 1 led for alarm status
- Messages selectable in 8 languages: Italian –English –French –German –Spanish –Portuguese –
Turkish –Russian
-nr. 6 key buttons: increase, decrease, enter, reset, start, stop
-nr. 1 input for temperature probe KTY13.5/NTC 10KOhm@25°C, ß(25/85)= 3977
-nr. 1 input for pressure transducer (working pressure P1)
-nr. 1 input for auxiliary pressure transducer (internal pressure P2) or analog information from inverter
-nr. 1 input for PTC or Klicson for motor protection (IN8).
-nr. 7 opto isolated digital inputs from 12/24Vac to detect:
IN 1 = emergency stop button
IN 2 = thermal motor
IN 3 = thermal fan
IN 4 = remote start/stop
IN 5 = air filter pressure switch
IN 6 = separator filter differential pressure switch
IN 7 = settable as: door of the electrical cabinet open –control phase relay –generic alarm
-nr. 3 digital inputs for connection to Logika Control phases unit.
-nr. 7 outputs via relay with contact 1.5A AC1 250Vac –6 A AC1 250Vac total
RL1 = line contactor
RL2 = delta contactor
RL3 = star contactor
RL4 = load solenoid valve
RL5 = fan contactor
RL6 = settable as fan contactor, condensate drain, compressor status
RL7 = settable as: alarm, fan contactor, condensate drain, compressor status
- nr. 1 real time clock with buffer battery, around 10 years electrical life
- nr. 1 24Vdc power supply input for PNP outputs
- nr. 1 24Vdc input from inverter to detect inverter fault
- nr. 2 PNP digital output to control the inverter (run and jog command)
- nr. 1 analog output 4÷20 mA for inverter operation
- nr. 2 serial output RS485 for:
connection to other compressor for Master/Slave and/or Multiunit operation
inverter communication
-Check min. and max. power supply to the controller
-Non volatile memory to store setting data, working hours, compressor status, alarm list
-The controller switches OFF due to micro interruption longer than ~ 300 m.s.
Weight: 470 g
Accessories:
- nr. 1 temperature probe KTY 13.5 for detection of the air end temperature: cable in silicone rubber, length 2.5 m,
working range –10 ÷ 130°C, resolution 1°C.
- nr. 1 pressure transducer 4-20 mA for working pressure control: 2 wires, AISI 316L stainless steel membrane,
working range 0 ÷ 15 bar, resolution 0,1bar, precision ± 0,1bar.
- nr. 1 Logika Control phases unit for power supply 230 ÷ 460V three phase

Revision 1 –04.12.2015 5/28
MOUNTING
Use the drawing below as overall dimensions to mount the controller.
WARNING TO THE WIRING OF THE CONTROLLER
1) Respect the working technical features and instructions on the electrical wiring; in special way both the cables of the
temperatures probes and pressure transducers must be isolated from the power cables and proper RC filters must be
placed on the contactors’ coils
2) On the back side of the controller there must be enough space for wiring and connectors.
3) The rear side of the controller must be protected against condensation, oil and dust.
4) Don’t wash the front panel by water injection; clean the front mylar with a soft cloth using soap water.
5) Low voltage and high voltage cables run on separate trunks.
6) The connection cables of temperature probe and pressure transducer must be placed in a trunk separate from the power
cables.
7) The connections cables of digital inputs must be placed in a trunk separate from the power cables.
8) The power cable of controller must NOT be placed in the same trunk of the power cables
DRILLING TEMPLATE
161 mm
106 mm

Revision 1 –04.12.2015 6/28
ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS

Revision 1 –04.12.2015 7/28
LEGEND
Terminal M1
Pole 1-2 = power supply 12Vac
Terminal M2 –RS485 FOR CONNECTION MASTER/SLAVE –MULTIUNIT
Pole 1 = 0
Pole 2 = D-
Pole 3 = D+
Pole 4 = +15Vdc (As power supply for a Logik option)
Terminal M3
Pole 1-2 = air end temperature probe
Pole 3-4 = pressure transducer (pole 3 = negative –pole 4 = positive)
Terminal M4
Pole 1 = pole 5 of the control phases (GND)
Pole 2 = pole 1 of the control phases (T)
Pole 3 = pole 2 of the control phases (S)
Pole 4 = pole 3 of the control phases (R)
NOTE: THE GND FROM THE CONTROL PHASES UNIT MUST NOT BE CONNECTED TO EARTH.
IT’S THE GROUND OF THE CONTROLLER AND MUST BE CONNECTED TO GROUND OF THE CONTROL PHASES UNIT
Terminal M5
Pole 1 = IN 1 = emergency stop button (L)
Pole 2 = IN 2 = thermal motor (L)
Pole 3 = IN 3 = thermal fan (L)
Pole 4 = IN 4 = remote start/stop (L)
Pole 5 = IN 5 = air filter pressure switch (L)
Pole 6 = IN 6 = separator filter differential pressure switch (L)
Pole 7 = neutral = N
NOTE: the digital inputs you do not use have to be connected directly to 12-24V otherwise they generate the
related alarm, except IN5 that must not be connected in case you do not use it.
Terminal M6
Pole 1 = RL7 = alarm (configurable)
Pole 2 = RL6 = condensate drain solenoid valve (configurable)
Pole 3 = RL5 = fan contactor (configurable)
Pole 4 = RL4 = solenoid valve
Pole 5 = RL3 = star contactor
Pole 6 = RL2 = delta contactor (configurable)
Pole 7 = RL1 = line contactor
Pole 8 = common = 24 ÷ 230Vac
Terminal M7
Pole 1 = IN 7 = settable as door of electrical cabinet open –control phase relay –generic alarm (L)
Pole 2-3 = IN 8 = PTC or Klicson for motor protection
Terminal M8 –RS485 FOR DRIVE CONNECTION
Pole 1 = 0
Pole 2 = D-
Pole 3 = D+
Polo 4 = 2nd 4/20mA analog input configurable as internal pressure transducer or as analog data coming from the drive:
1. internal pressure transducer: connect to the negative pole of the transducer
2. analog data from drive: connect to a 4/20mA analog output on the drive control board (drive must be set correctly
to give the right information on this output)
Pole 5 = +15V power supply for the internal pressure transducer (first of the above cases): connect to positive pole of the
transducer; not to be connected in case of analog data coming from drive
Terminal M9
These terminals to be connected only to the drive controlled by 4/20mA analog output
Pole 1 = Analog and/or digital GND and DGND from drive
Pole 2 = Inverter fault input, 24Vdc signal coming from drive (normally connected to drive alarm relay)
Pole 3 = 4/20mA analog output computed by Logik26S PID (when activated)
Pole 4 = PNP1 digital output from 24Vdc from drive (when analog output is active this is the run command for the drive)
Pole 5 = PNP2 digital output from 24Vdc from drive (when analog output is active this is the jog command for the drive)
Pole 5 = 24Vdc from drive

Revision 1 –04.12.2015 8/28
EXAMPLE OF CONNECTION TO SECURITY PRESSURE SWITCH
Alarm related to security pressure switch A21 is joined to the lacking phase to all the digital inputs.
This is a shut off alarm: below you can find the connection drawing both to contactors 24Vac and/or 230Vac.
Contactors 230Vac
If the operation of the contactors and
solenoid valves comes through 230 Vac, the
digital inputs have to be connected to 12
Vac; next to the contact of the pressure
switch, place and energize an auxiliary
relay and put the contact in serie to
12 Vac (L) (see drawing on the right).
When the pressure switch is closed, the
auxiliary relay with contact closed supply
power to the digital inputs; the power
supply of the controller is connected before
the contact of the relay.
When the pressure switch opens, the
auxiliary relay opens power to the digital
inputs; the controller detects all the digital
inputs open and signal the alarm “SEC.
PRESSURE SWITCH”.
Contactors 24Vac
If the operation of the contactors and
soenoid valves come through 24 Vac, the
digital inputs have to be connected to 24
Vac (see drawing on the right); on this
way when the pressure switch opens due
to high pressure, 24 Vac lacks and
deenergize all the contactors, solenoid
valve and digital: the controller detects
all the digital inputs opened and signal
the alarm “SEC. PRESSURE SWITCH”.
I°
12 –0
II°
Security pressure
switch for high
pressure detection
Power supply to
the controller
Power supply to digital
inputs and uses
24 –0
I°
12 –0
II°
Security pressure
switch for high
pressure detection
Auxiliary relay
Power supply to
the controller
Power supply to
the uses
230 –0
Power supply to digital
inputs

Revision 1 –04.12.2015 9/28
CONNECTION SERIAL NET RS485
To connect a serial net you have to pay carefully attention to some executive aspects:
1) Use flexible cable, shielded, twisted 22 AWG type.
2) Connect D- and D+ to two conductors of same couple and 0 to a third one (if available) or both conductors of a
second couple.
3) Connect the cable’s shield to only one end of 0.
4) DO NOT CONNECT the cable’s shield to the electrical ground of the plant.
5) The net MUST NOT BE LONGER than 400 meters.
6) Max connectable units through serial net RS 485 is 32.
7) In case of connection via serial line RS485 you have to set the parameter C08 into menu 04 Compressor setup:
this is the number you need to combine to the recognition of the controller.
8) The units on serial net RS485 must be connected without any reversal: pole D+ to D+, pole D- to D-, pole 0 to 0.
9) In case of connection with more than 2 units it is necessary to provide only one line without any deriving.
At the terminal both starting and ending the net it is possible to place (in parallel to D- and D+) a termination
resistance 120 Ohm.
In the picture below you can see the connection of 4 units on serial net RS485 by using a shielded cable with two
twisted couples.
NOTES ON THE WIRING: wrong wiring can damage both the controller and other devices connected to the
serial port.
WARNINGS TO THE WIRING RS485
1) The cable must be placed into a TRUNK SEPARATED by power cables and any potentially dangerous cables as
lighting plant and so on.
2) DO NOT PLACE signal cables next to power bar, lighting lamps, antennas, transformers;
3) Keep signal cables FAR 2 METERS MINIMUM from units with heavy inductive (distribution cabinet, motors,
inverter).
4) Don’t pull the cables with a strength over 12 Kg; stronger strength can damage the wires and reduce the signal
transmission on the line.
5) DO NOT: twist, knot, crush or fray the conductors.
6) Do not make any joints between lengths of cable: always use only one cable to connect any single unit to each
others. Strip the end part carefully, do not crush the cable next to core-hitches or safety supports.
7) Always respect the position of the colors at the both sides of the connection.
Once the wiring is complete, visually and physically check the cables are undamaged and properly placed

Revision 1 –04.12.2015 10/28
MAIN VISUALIZATION
Power on and display visualizes the message “Logika Control” “Logik 26-S” for about 3 seconds, then it shift to the main
visualization and the compressor is in OFF status.
The pic. below shows the main visualization
1
.
According the pic. above and related icons, the main visualization can be described as below:
1. General icons, where be present the following:
I01, Condensate drain in operation
I02, Multiunit operation
I03, Master/slave operation
I04, Maintenance messages
2. Alarm or maintenance messages: if an alarm is detected the display visualizes the icon I05, if maintenance timer is
over visualizes icon I04.
3. Start/stop by timer activated.
4. Time (hours and minutes).
5. Icons I12 when fan ON
6. Air end temperature
7. Inverter area: data visualized when output 4/20mA or RS485 inverter are enabled. In case output 4/20mA is
activated the display shows the PID frequency set (F) and eventual data set on the input 4/20mA (parameter
C19). In case of inverter via RS485 all the data from the inverter are visualized: frequency (F), current (I), power
(P) and temperature (T). Data are visualized on the right side (7b) or left side (7a) according the inverter
configuration is on the air end temperature or working pressure.
8. Compressor status: icons from I07 to I13 as below:
Compressor OFF
Witing for safety timer
Pressure set
Remote start/stop open
Compressor ON
Waiting for start/stop by timer (in this case the display visualizes the day of the week and time of the
next ON by timer).
Waiting for internal pressure P2 lower than parameter AP4
9. Pressure area:
Working pressure (BIG) and stop/start pressures.
Aux pressure transducer (if enabled).
Icon I17, motor run
Icon I18, load solenoid valve open
In case of alarm, the below side of the display (7a, 7b and 8) visualizes the alarm message
The controller is provided with 6 key-buttons with following functions: (with reference to the above pic.):
-T1, decrease, select down
-T2, increase, select up
-T3, change or confirm
-T4, reset or back
-T5, stop compressor
-T6, start compressor
1
In a normal operation status, the icons will not be visualized all together: here they are just to show their own position in the display.
1
3
4
7a
2
6
5
9
8
T6
T5
T4
T3
T1
T2
7b

Revision 1 –04.12.2015 11/28
Meaning of icons
Main visualization: icons located on the upper row
I01
Condensate drain activated
I02
Multiunit operation activated
I03
Master/slave operation activated
I04
Maintenance timer over
I05
Alarm
I06
Weekly start/stop timer activated
Main visualization: icons related to compressor status located lower row (centre)
I07
Compressor OFF
I08
Waiting for safety timer
I09
Pressure set, compressor running unload or stand-by
I10
Remote start/stop input open
I11
Compressor running
I12
Stop by timer: the display visualizes day and time of the next start
I13
Internal pressure P2 too high
Main visualization: left square = pressure –right square: temperature
I14
Fan ON
I15
PID and output 4/20mA enabled
I16
Stop pressure
I17
Start pressure
I18
Motor running
I19
Compressor running load (load solenoid valve activated)
Menu setting: date, time, contrast, units of measurement
I20
Unit of measurement activated
I21
Contrast
I22
Language
I23
Date and time

Revision 1 –04.12.2015 12/28
QUICK SETTING START/STOP PRESSURES (ENABLED WITH PASSWORD LEVEL3)
To change the Start pressure push and the data starts blinking; change the value by using and/orand confirm
the new one by : the data stops blinking. By the button R you can abort the modification.
To change the Stop pressure, push and the data starts blinking; change the value by using and/orand confirm
the new one by : the data stops blinking. By the button R you can abort the modification.
GENERAL NOTES TO THE PROGRAMMING
FLOW AND MODIFICATION OF THE PARAMETERS
To select every single label, use the arrow keys and confirm by to enter into related parameters and/or data.
After you select the data and/or parameter to change by the arrow buttons, push to edit, set the new value till by arrow
buttons and confirm it .
After the last label or by pushing the button R, you can shift back to the main visualization.
ESC FUNCTION
In any part of the menu you can shift back to the main visualization by pushing for about 5 seconds.
ANTIPANIC FUNCTION
In any label or sub-menu related to the setting and/or visualizations, after 180 seconds from the last pushing of a button,
the controller shift back to the main visualization without saving any change you have not confirmed.
LCD ENERGY SAVING
After 1 minute from the last pushing of any button, the back-light of the display switches off; it will be on again by pushing
any button on the controller.
M1 MAIN MENU
To enter the setting, push and the display visualizes the flow menu including the following labels related to other sub-
menu reported in the table below.
In case you push for 3 seconds the display visualize the label related to the password allowing to select the levels to
access the different parameters (1-service 1, 2-service 2, 3-factory).
Id
Submenu
Password level
01
Info
0
02
Password
1
03
Visualizations
0
04
Compressor setup
1
05
Pressures
2
06
Temperatures
2
07
Timer
1
08
Inverter RS485
3
09
Analog output
3
10
Hours filters/oil
0
11
Maintenance list
0
12
Alarms list
0
13
Timer start/stop
1
14
Reset
1

Revision 1 –04.12.2015 13/28
M2 ENTER PASSWORD
Enter to password levels by pushing on the main visualization.
To select the password level, use the arrow buttons and confirm .
Now, enter the code (2,4 or 6 digits according the level).
Use the arrow buttons to change any digit of the code, the button to shift to the digit on
the right and the button R to shift back to the previous one. The digit to enter are indicated
by “-” while the digit already entered by the symbol “*”. Once the password is OK you enter
into the main menu according the level selected. In case you enter a wrong password code,
the display visualizes the message “ERROR”.
PASSWORD FORGOTTEN
In case of password forgotten or missed you have to switch power off to the controller; restore power and keep on pushing
the for more than 5 seconds. During this time the display visualizes the blinking message “Reset Password”;
release the arrows button when the message changes into “Password reset”.
M1-1 INFO
This sub-menu visualizes the following info:
1. Working hours
2. Load hours
3. Load % during last 100 working hours (updated every 5 hours)
4. Frequeny set on output 4/20mA (if enabled)
5. Starts/hour
6. Flow Air Delivered
7. Serial number
8. Software release
M1-2 PASSWORD
In this sub-menu you can change the password codes saved.
Parameters, setting range, default and levels are reported in the table below:
Fuction
Description
Setting range
Default
Password level
PW1
Password service 1
00 ÷ 99
22
1
PW2
Password service 2
0000 ÷ 9999
4444
2
PW3
Password factory
000000 ÷ 999999
666666
3
M1-3 VISUALIZATIONS SETUP
In this sub-menu you can set the parameters related to the visualization of the controller.
By the arrow buttons select the parameter you need and confirm by Enter to enable the change: till by the arrow buttons
change the value and confirm the new one by .
language set to read the message on the display (default TURKISH)
Units of measurement of temperature and pressure
(°C-bar, °C-psi, °F-bar, °F-psi) –(default °C/bar)
LCD contrast
date/time and possible automatic shift between DLS and
Summer time
Password
Service 1
0-
1-2

Revision 1 –04.12.2015 14/28
M1-4 COMPRESSOR SETUP
In this menu you can change the general setting of the compressor.
Parameters, setting range, default and password level are reported in the table below:
Code
Description
Value
Meaning
Default
Level
C01
Restart
MAN-AUT
Restart after power off: MAN (manual) –AUT (automatic)
MAN
2
C02
Starts/hour
0 ÷ 60
Starts/hour of the motor allowed
6
2
C03
Timer Wt4
SI-NO
Wt4 operation: YES = fixed –NO = variable
YES
2
C04
Control phases
YES-NO
Logika control phases uni:
YES = enabled - NO = disabled
YES
2
C05
Safety
YES-NO
Safety operation:
YES = enabled - NO = disabled
NO
3
C06
Low voltage
YES-NO
Alarm low voltage :
SI = enabled - NO = disabled
YES
3
C07
Multiunit
operation
0/1/2/3
Multiunit options:
0 = stand alone –1 = Master/Slave
2 = Master/Slave new –3= Multiunit Slave
0
2
C07.1
Timer Master/Slave
00÷200 h
Balancing working hours:
in case of setting “00”the balancing is not allowed; Master
is the compressor with address 1
100 h.
2
C07.2
Timer slave
1 ÷ 99 min.
Slave support:
After power on if Master unit has not reached stop set until
the time set in this parameter, the slave starts to support
5 min.
2
C07.3
Maintenance mode
YES/NO
In case of Multiunit Slave, the compressor works on
standing alone and Multiunit Master is informed this
compressori s out of order
NO
2
C07.4
Inverter twin
YES/NO
Both inverter modulating in Master/slave operation new
SI = noth inverter modulating
NO = master max speed if both units are running
0
2
C08
Compressor Nr
1 ÷ 32
Enter MODBUS address of the compressor
1
1
C09
Serial number
15
alphanumerical
characters
Serial number of the compressor
3
C10
Flow Air Delivered
100 / 99990
Capacity: nominal air flow of the compressor (liters/min.)
1000L/min
3
C11
Input PTC
YES/NO
Input PTC configuration:
NO = disabled –SI = enabled
0
2
C12
Input IN 7
0/1/2/3
Input IN7 configuration:
0 = disabled –1 = door open
2 = control phases relay –4= high temperature bearings
0
3
C13
Output RL2
0÷6
Relay RL2 setting:
0=default (star contactor)
1=fan - 2 = condensate drain - 3=compressor status
4=alarm - 5 = motor activated - 6 = load valve on –
7 = lubricating - 8 = off - 9 = activation on power on for
the time Wt5
10 = activation on power on for the time Wt5 and
activation in case of alarm
0
3
C14
Output RL5
0/6
See C13
0
3
C15
Output RL6
0/6
See C13
0
3
C16
Output RL7
0/6
See C13
0
3
C17
Shut-off C—h
NO/YES
Compressor stop once the timer “Check compressor” is
over:
NO = disabled –SI = shut-off alarm
NO
3
C18
Output 4/20mA
0/1/2
Operation output 4/20mA and PID:
0= disabled
1 = enabled on working pressure control
2 = enabled on air end temperature control
0
3
C19
Aux input 4/20mA
0÷4
Configuration auxiliary input 4/20mA:
0=disabled –1= relative pressure (delta in relation to the
working pressure) –2=power inverter –3=current inverter
4=inverter temperature
0
3
C19.1
Timer separator filter
1 ÷ 600 sec.
Delay timer separator filter alarm
30s
3

Revision 1 –04.12.2015 15/28
C19.2
Top range AI
10 ÷ 999
Enabled if C19 is set from 2 to 4. This is the top range
related to the current 20mA used to read on the main
visualization the data from the inverter
100
3
C20
Temperature probe
0/1
0=All the alarms related to the temperature are disabled.
Ventilation is operated by ON/OFF fixed cycles managed by
the next parameters C20.1 and C20.2
1=KTY
2=NTC
1
3
C20.1
Time Fan ON
10÷9999s
Time ON fan in case of temperature probe disabled
500
3
C20.2
Time fan OFF
10÷9999s
Time OFF fan in case of temperature probe disabled
500
3
C21
Input Fault Inverter
0/1/2
0=Disabled
1=Input enabled, managed normally open
2=Input enabled, managed normally closed
0
3
C22
Lubricating time
1 ÷ 999s
Activation time of lubricating relay
2
3
C23
Interval lubricating
0 ÷99990m
Time to lubricate
11000
3
NOTES:
C01–RESTART: in case of power off, by selecting “Man”, the compressor doesn’t start automatically and the display
visualizes "POWER OFF"; by selecting “Aut.”, the compressor restart automatically according a delay time set Wt5: during
this time the display visualizes the “WAIT”.
If you change the default setting, it is recorder into the alarm buffer and you can cancel it by general reset only.
C05–SAFETY: if you set “YES”, once the timer “CAF” will be over, the display visualizes the message “Shut-off for safety”;
you can erase it into this parameter only and set it as “Safety = NO”; in this case the alarm code change into “Change air
filter”.
C07–MULTIUNIT OPERATION: set “0”, the compressor works by standing alone.
Set “1”, the compressor communicates with a second unit via serial RS232 as Master/Slave (see related working program)
and the controller visualizes the parameters 07.1 e 07.2.
C07.1–TIMER MASTER / SLAVE: time to switch Master into Slave; if the difference of working hours between the two
compressors is bigger than the setting of this parameter, the unit with more hours will not be Master as long as the other
will reach the same.
C07.2–TIMER SLAVE: after power ON, if the Master unit has not reached the stop pressure until the time setting in this
parameter, the Slave will start to support.
C08–COMPRESSOR Nr.: in case of Master/Slave enabled, the compressor set as 1 will be the Master unit.
C09–SERIAL NUMBER: LCD visualizes the serial number on the third lower right side row from the bottom.
Push to edit.
You can select the characters by the arrows buttons; by shift forward to the next character or enter a new one, by ESC
shift back to the previous one; you can delete the editing by pushing ESC when the cursor in on the first character.
You can save the data by enter two SPACE in a row or by reaching the max. number of characters (15).
C17–Shut-off for C—h: alarm related to the maintenance timer C—h (check compressor); if you set “YES”, 100 hours
before the timer is over, the compressor stops showing alarm STOP FOR AL32 –CHECK COMPRESSOR.
You can reset the alarm and restart the compressor for the next 100 hours and every 50 working minutes the display
remind to maintenance C—h.
Once the residual 100 working hours are over, the compressor will stop again; you can reset such alarm by resetting the
maintenance timer only.
C18–Output 4/20mA: allow to upload factory default parameters in menu M1-9. Two different default set are provided
according regulation is related to the working pressure or air end temperature.
C22-C23: These parameters are enabled if one of the relay is configured as per setting value 7 (lubricating). In this case
the relay allows automatic lubricating according the setting on C22 and C23. The time to lubricate is calculated on BL timer
that is not visible for the reason used on this function.

Revision 1 –04.12.2015 16/28
M1-5 PRESSURES
In this menu you can change the setting related to the working pressure.
Parameters, setting range, default and password level are reported in the table below:
Function
Description
Setting range
Default
Password level
WP1
Top range transducer
15 ÷60
15
3
WP2
High pressure alarm
(WP3+0,2) ÷ (WP1-0,5 )
11,0 bar
3
WP3
Stop pressure
(WP4+0,2) ÷ (WP2-0,2)
8,8 bar
1
WP4
Start pressure
3 ÷ (WP3-0,2)
7,3 bar
1
WP5
Slave start pressure
2,0 ÷ (WP4-0.2)
6,5 bar
1
WP6
Offset
-2,0 ÷ +2,0
0 bar
2
AP1
Separator filter alarm
(AP2+0,2) ÷ (WP1-0,5)
1,7 bar
3
AP2
Separator filter warning
0,1 ÷ (AP1-0,2)
1,2 bar
3
AP3
Offset
-2,0 ÷ +2,0
0 bar
3
AP4
Max. aux. pressure on start
(WP1-0,5) ÷ 1,0
2,0 bar
3
NOTE: WP5 is visualized just in case the compressor has been set to Master/Slave operation (see menu 4 Compressor
SETUP).
Parameters AP1..AP4 are visualized if the security transducer has been configured in COMPRESSOR SETUP and if the
parameter C19 set 1 or 2, only.
AP4 is the max. internal pressure allowing to run the motor (see icon I13, page 11).
M1-6 TEMPERATURES
In this menu you can change the setting related to the temperature.
Parameters, setting range, default and password level are reported in the table below:
Function
Description
Setting range
Default
Password level
WT1
High T. alarm
(WT2+2°C) ÷ 125°C
105 °C
3
WT2
High T. warning
(WT3+2°C) ÷ (WT1-2°C)
100 °C
2
WT3
Start fan
30°C ÷ (WT2-2°C)
85 °C
2
WT4
ΔT fan stop
5°C ÷ 15°C
10 °C
2
WT5
Low T. alarm
-10°C ÷ +15°C
0 °C
2
WT6
Offset
-10°C ÷ +10°C
0 °C
3
WT7
PID Enable temp.
-10°C ÷ 100°C
0 °C
3
M1-7 TIMER
In this menu you can change the setting related to the temperature.
Parameters, setting range, default and password level are reported in the table below:
Function
Description
Setting range
Default
Password level
Wt1
Star
2 ÷ 20 sec
5 sec.
3
Wt2
Star/Delta
10 ÷ 50 m.s.
35 m.s.
3
Wt3
Delta
1 ÷ 900 sec.
2 sec.
3
Wt4
Unload
0÷ 30 min
3 min.
2
Wt5
Safety
0 ÷ 240 sec.
30 sec.
2
Wt6
RL6 On
1 ÷ 10 sec
2 sec
1
Wt7
RL6 Off
1 ÷ 10 min
3 min.
1
NOTE: changing the set value, the new one is loaded once the counting in progress is over.
NOTE Wt4: non stop motor mode when Wt4 set to max.

Revision 1 –04.12.2015 17/28
M1-8 INVERTER RS485 (DANFOSS)
This menu allows to visualize/set the parameters related to the inverter in case of connection via RS485 (Danfoss available
only).
The parameters you can set, related setting range, default and password level necessary to the visualization and
modification are described in the table below:
Function
Description
Setting
Default
Password level
DR0
Drive Model
0/1
0
3
DR1
Min frequency
0Hz÷(DR2-5Hz)
30Hz
3
DR2
Max frequency
(DR1+5Hz)÷300Hz
85Hz
3
DR3
Accel. time
0.0s÷300.0s
40.0s
3
DR4
Decel. time
0.0s÷300.0s
4.0s
3
DR5
PID prop. gain
0.00÷99.99
4.40
3
DR6
PID int. time
0.00s÷99.99s
2.00s
3
DA0
Motor Power
0.00KW÷400.'KW
57.6KW
3
DA1
Motor Voltage
0V÷2000V
415V
3
DA2
Motor Frequency
8Hz÷200Hz
87Hz
3
DA3
Motor Current
0.1A÷999.9A
106.0A
3
DA4
Motor Speed
0RPM÷9999RPM
2575RPM
3
DA5
Current Limit
0.0%÷200.0%
100.0%
3
DA6
PID Diff.Time
0.00s÷99.99s
0.00s
3
DA7
Reset Energy Meter
0÷1
0
3
DA8
Jog Ramp Time
0.0s÷300.0s
20.0s
3
DA9
PID int. mult.
0.10÷4.00
1.00
3
Setup Drive
NOTE:
If you set the parameter a value different from 0 on the parameter DR0, you enable the inverter operation via RS485 and
related alarms 60, 61,62.
After the last parameter DA9 comes “Setup Drive” that allows to start the setting of the inverter; it means to send the
parameters from DR1 to DA9 to the inverter. Moreover all the required settings to make the system Logik26S+Drive
working, such as drive PID enable, drive PID setpoint and feedback source and so on, are programmed to the drive also.
Confirming “Setup Drive” the LCD visualizes the following screen:
In the middle of the LCD is visualized the drive status.
When the download is in progress, above the drive status comes the progress status (in percentage) of the setup.
Pressing the setup start. Setup required approximately 5minutes.
Pressing R the setup abort and it is possible to go back to menu M1-8.
While setting up the inverter, the main contactor is activated.
Setup Drive
Drive ready

Revision 1 –04.12.2015 18/28
M1-9 ANALOG OUTPUT
This menu is visualized only if the safety pressure transducer has been configured in the menu Compressor setup
(parameter C18 different from 0).
The analog output is determined by a PID calculation.
The analog output can be eventually connected to the electrical motor inverter or fan motor inverter. Parameter C18 must
be set 1 for electric motor or 2 for fan motor.
In case of electric motor the regulation is made by the pressure. The setpoint of the PID calculation is placed in the middle
of the interval between start pressure WP3 stop pressure WP4. Example: WP3=7bar and WP4=8bar, setpoint will be 7.5bar
and PID will try to keep the working pressure around such reference value by increasing the inverter output (frequency as
well) in case the pressure is lower than the set and decreasing in case the pressure is higher.
In case of the fan motor the regulation is made by the temperature. The sepoint of the PID calculation is the value set on
WT3 (fan start). PID will try to keep the air end temperature around such reference value by increasing the inverter output
(frequency as well) in case the temperature is higher than the set value and decreasing in case the temperature is lower.
Menu M1-9 allows to visualize/set the parameters related to the PID regulator.
The pic. below shows the PID calculation.
C18
WT3
100°C +
-1,0
PI7
SUM SUM
MUL
PI4
MUL
PI5
+
+
-
PI6
SUM
PID
1,0
-0,1
MUL
PI1
MUL
MUL ∑
MUL
PI3
∆
1,0=20mA
0,0=4mA OUT
ScrewTemp
100°C
WorkPress
WP1
WP3+WP4
2 x WP1
MUL
-1
1
1
PI2(xPM1)
SETPOINT
FEEDBACK
Parameters, setting range, default and password level are reported in the table below:
Function
Description
Setting range
Default
Press/Temp
Password
level
PI1
PID prop. gain
-99.99s÷ 99.99s
2.50/5.00
3
PI2
PID int. time
-99.99s÷ 99.99s
10.00s/15.00s
3
PI3
PID der. time
-99.99s÷ 99.99s
0.00s/0.01s
3
PI4
PID out scaling
-99.99s÷ 99.99s
1.00/4.00
3
PI5
Adder multipl.
-99.99s÷ 99.99s
0.00/1.60
3
PI6
Adder offset
-2.00÷2.00
0.00/0.76
3
PI7
PID low limit
-2.00÷1.00
0.00/-100
3
FR1
Min. Freq.
0Hz÷(FR2 – 5Hz)
25Hz/25Hz
3
FR2
Max. Freq.
(FR1 + 5Hz) ÷ 500Hz
50Hz/50Hz
3
PT1
Ramp up time
0,1s ÷99,9s
5,0s
3
PT2
Ramp down time
0,1s ÷99,9s
5,0s
3
PT3
Jog Ramp time
0,1s ÷99,9s
5,0s
3
PM1
PID I gain multiplier
0,01 ÷9,99
1,00
3
NOTE:
For all the above parameters two default set are provided according the way of control (set on parameter C18).
PID output (limited to the interval 0..1) is transposed to output current: frequency FR1 (PID output=0) correspond 4mA,
frequency FR2 (PID output=1) correspond 20mA.
You have to set the frequency reference on the inverter so that 4mA/20mA input correspond the frequency ranged you
need. You have to set such range both on parameters FR1 and FR2.
PT3 is the duration of the acceleration/deceleration time in case the compressor has to reach the download status; in this
case inverter reaches the minimum frequency FR1 according ramp PT3.
In case of compressor loading the ramps are PT1, while the speed goes up and PT2 while speed goes down.
In case of pressure regulation, PM1 alters the integrating effect of the error on the setpoint; specially integral time PI2 is
multiplied for PM1 when the pressure is over setopint.
Set PI2 or PI3 zero, the related integration or derivative action is disabled.

Revision 1 –04.12.2015 19/28
M1-10HOURS FILTERS/OIL
In this menu you can visualize the maintenance timer; if you enter by a password level over 1, you can enter into the sub-
menu to change and/or reset.
Function
Description
Setting range
Counter
Reset
Default
Password
level
CAF
Change air filter
100 ÷ 3.000 h.
xxxxxx h.
NO
2.000
2
COF
Change oil filter
100 ÷ 10.000 h
xxxxxx h.
NO
2.000
2
CSF
Change separator filter
100 ÷ 10.000 h
xxxxxx h.
NO
4.000
2
C--
Change oil
100 ÷ 10.000 h
xxxxxx h.
NO
8.000
2
C--h
Check compressor
100 ÷ 10.000 h
xxxxxx h.
NO
500
2
C-BL
Bearings lubrication
100 ÷ 29.999 h
xxxxxx h.
NO
29.999
2
The counting is related to the ON time of the line contactor (RL1) and goes on backward: when the counting reaches 0, the
display shows the related message and goes on as negative counting.
The storage of the hours comes every 15 minutes; if the power goes off during the counting such 15 minutes are missed.
If parameter C--his set 10.000, the alarm “CHECK COMP.” is not enabled.
If parameter C-BL is set 29.999, the alarm “BEARING. LUB.” is not enabled (bearing lubricating).
By changing the set value than the count in progress is re-calculated.
Example: CAF, set 2000h, the counter is 1600, it means 400h has passed from reset. If yu change the set, for example
3000, the counter will change into 2600.
M1-11MAINTENANCE LIST
Memory related to reset of the maintenance timer with related date.
In case of empty memory the display visualizes the message “Memory empty”.
The memory keeps till 20 data, the twenty-first erases the first one and so on.
Once the maintenance requested has been carried out, you have to reset the related counter; if you don’t reset the timer
every 50 working minutes or every power on of the compressor the display visualized the related maintenance message.
M1-12ALARMS LIST
List of the alarm detected with related progressive number, date, time and cause.
For maintenance alarm the display shows the icon I04 , while the icon I05 for shut-off alarm.
Memory capacity of 20 alarms: the twenty-first erases the first one and so on; if the memory is empty the display visualizes
the message “Memory empty”.

Revision 1 –04.12.2015 20/28
M1-13TIMER START/STOP
This menu allows to manage start and stop of the compressor by weekly timer.
Editing the timer, the display visualizes the parameters T01 “Enable timer”. If you set
YES, the display shows the link to sub-menu to enter start/stop program and T02
“Weekly timer”.
Enter into this sub-menu to set/change three working bands for every day of the week.
Initially the day of the week is selected.
By the arrow buttons you can select a different day. By selecting a day next to the last
one (Sunday) the display shift back to the previous menu.
By pushing Enter you shift to the start time of the first interval T1.
By the arrow buttons you can change the time and confirm it by Enter or shift back to
select the previous data.
Next pushing of the Enter button allows to select hours and minutes of all start/stop
event visualized.
When the stop minutes of the last interval of the day are selected, by pushing Enter
you enter into the setting of the next day.
In any time by pushing R button for longer time you can shift back to the previous
menu ending the visualization/setting of the weekly timer.
M1-14RESET
Description
Password level
Working hours
3
Alarmsi
3
Maintenance
3
Weekly timer
2
General
3
Select the message you need and push Enter button: the display visualizes a confirmation message
To start reset select YES.
Now the display visualizes the blinking message “RESETTING” for about few seconds
NOTE:
GENERAL reset is allowed when the compressor is “OFF” only; the controller will load all factory default values.
Timer start/stop
T01 Enable timer SI
T02 Weekly program
1-13
Weekly timer
Mon Start Stop
T1 00:00 00:00
T2 00:00 00:00
T3 00:00 00:00
1-13-1
Table of contents