Lucy Electric Aegis 36 Guide

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 2
1 Document Symbols .................. 4
2 Validation ................................... 5
2.1 Validity ..........................................................5
2.2 Safety ............................................................5
3 General Product Information ... 6
3.1 Test facilities ................................................7
3.2 Padlocks .......................................................7
3.3 Pressure Indicators ......................................8
3.4 Extensible Type ............................................8
4 Front Panel Layout ................... 9
5 Technical Data ........................ 10
6 Line Diagrams ......................... 12
6.1 Non-Extensible Functions. ........................12
6.1.1 Single Function L: Load Break Switch
630A ..........................................................12
6.1.2 V: Circuit Breaker 630A ...........................12
6.1.3 2-Way (LV) ................................................12
6.1.4 3-Way (LVV) ..............................................12
6.1.5 4-Way (LVVV) ............................................12
6.2 Extensible Functions. ................................13
6.2.1 Single Function L: Load Break Switch
630A ..........................................................13
6.2.2 V: Circuit Breaker 630A ...........................13
6.2.3 2-Way (LV) ................................................13
6.2.4 3-Way (LVV) ..............................................13
6.2.5 4-Way (LVVV) ............................................13
7 Dimensional Drawings ........... 14
7.1 Unit Range - Dimensions and Weights ....14
7.1.1 Non Extensible Height .............................14
7.1.2 Extensible Height .....................................14
7.1.3 1 - Way Outdoor .......................................15
7.1.4 1 - Way Indoor ..........................................15
7.1.5 2 - Way Outdoor .......................................15
7.1.6 2 - Way Indoor ..........................................15
7.1.7 3 - Way Outdoor .......................................16
7.1.8 3 - Way Indoor ..........................................16
7.1.9 4 - Way Outdoor .......................................16
7.1.10 4 - Way Indoor ..........................................16
7.1.11 Weights .....................................................16
8 Rating Plates ........................... 17
8.1 Unit Rating Plate Details ............................17
8.2 Standards ....................................................17
9 Handling .................................. 18
9.1 Acceptance of unit .....................................18
9.2 By receiving inspection .............................18
9.2.1 Unit RAL colour information ...................18
9.3 Symbol guidance .......................................18
9.4 Packaging Dimensions ..............................19
9.5 Forklift Truck ..............................................20
9.6 Transportation ‘centre of gravity .............20
9.7 Removing unit from pallet ........................21
9.8 Lifting Options ...........................................23
9.8.1 Lifting Label Location ..............................23
9.8.2 Lifting Hooks- Indoor Unit .......................23
9.8.3 Lifting Lugs - Outdoor Unit .....................24
10 Storage .....................................25
10.1 Storage Guide ............................................25
11 Substation Installation
(Resistance to Internal Arcing) 26
11.1 Trench Details ............................................26
11.2 Substation Position Clearance For Unit Type
(AF) ..............................................................27
11.3 Internal arc gas evacuation via the back of the
unit (AF/AFLR) ...........................................28
11.3.1 AFLR Trench Details - Outdoor ..............29
11.3.2 AFLR Trench Details - Indoor .................29
11.3.3 Tread plates ..............................................30
12 Installation Recommendations31
13 Unit Installation .......................32
13.1 Acceptance of unit .....................................32
13.2 By receiving inspection .............................32
13.3 Check SF6 gas ...........................................32
13.4 Aegis Unit Floor Mounting Details ...........32
13.4.1 Floor fixing ...............................................32
13.4.2 1-Way Units ..............................................33
13.4.3 2-Way Units ..............................................33
13.4.4 3-Way Units ..............................................34
13.4.5 4-Way Units ..............................................34
13.5 LV Panels.....................................................35
13.6 LV Connections - Indoor ...........................35
13.6.1 Cable Channel Removal ..........................36
13.6.2 LV Cable installation ................................36
13.7 LV Connections - Outdoor ........................37
14 Commissioning Tests .............38
14.1 Operation Tests .........................................38
14.2 Main Circuit Resistance Tests ..................38
14.3 Secondary Wiring Insulation Resistance
Testing ........................................................39
14.3.1 1 kV test. ...................................................39
14.3.2 Removal of the Earth link ........................39
14.4 HV Tests Before Cabling or Connection To
Transformer ................................................40
14.4.1 HV Insulation Resistance Testing ..........40
14.4.2 Power Frequency Testing .......................40
14.4.3 Test Schedules .........................................41
14.5 Relay Type Protection Tests .....................42
14.5.1 Relay Primary Injection Test - Overcurrent
Test ............................................................42
14.6 Relay Primary Injection Test - Earth Fault
Test .............................................................43
TABLE OF CONTENTS

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 3
14.6.1 Relay Secondary Injection Tests -
Overcurrent and Earth Fault Test ...........43
14.7 Current Transformer Tests ........................44
14.7.1 Polarity Test .............................................44
14.7.2 Ratio Test (Relay Units) ...........................44
14.8 Electrical Tests After Cabling or Connection
To Transformer ...........................................45
14.9 VPIS & NEON Indication (if fitted) .............45
14.9.1 Pickup voltage ..........................................46
14.9.2 Crossover voltage ....................................46
14.9.3 Phase comparator ....................................46
14.9.4 Shunt Trip (if fitted) ..................................46
14.10Auxiliary Wiring Switch testing ................46
15 Gland Plates ............................ 47
15.1 Removing Cable Box Front Panels ..........47
15.2 3 Single Core Cable, Clamps and Glands
Plates ...........................................................48
15.2.1 Cable Clamp and Gland Removal - Circuit
Breaker Function. ....................................48
15.3 Single 3 Core Cable, Clamps and Glands
Plates ...........................................................50
15.3.1 Cable Clamp and Gland Removal - Switch
Function. ...................................................50
16 Cable Connecting
Recommendations ................. 52
16.1 Cable Terminations ....................................52
16.2 Cable Area Dimensions .............................53
16.3 Cable Connecting Recommendations .....53
16.4 Cable Installation - Single 3-core ..............55
16.4.1 3 Single Core Cable Installation .............57
17 Cable Mounted CT Assembly 60
17.1 Cable Mounted Short Type CT Assembly
Fitting ..........................................................60
17.2 Cable Mounted Long Type CT Assembly
Fitting ..........................................................61
18 END-OF-SERVICE-LIFE .......... 63
18.1 SF6 ...............................................................63
18.2 Switchgear Unit Recycling ........................63
18.3 End-Of-Life Services ..................................63

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 4
1. DOCUMENT SYMBOLS
The symbols shown below are found throughout this document, indicating awareness and hazard levels depending
on the situation.
All symbols below are to ISO 3864-2.
INFORMATION: please pay special attention to this
instruction.
CAUTION: Failure to follow this instruction may result
in injury or damage to plant.
WARNING: Failure to follow this instruction may result
in death or serious injury or damage to plant.
DANGER: Failure to follow this instruction will result in
death or serious injury or damage to plant.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 5
2. VALIDATION
2.1 Validity
This is not a commercial document, it is strictly a technical document provided by Lucy Electric Technical
Department.
The objective of this publication is to provide directives for correct installation, test and commissioning
procedures for the Aegis 36 range. Produced in March 2022, this manual applies to the Aegis 36 range
only.
Due to Lucy Electrics policy of continuous research and development, Lucy Electric reserves the right to
change the design and specification of products without prior notice.
2.2 Safety
Operators of this equipment must have experience and
expertise with switchgear.
To prevent personal injury or equipment damage, this
manual must be read carefully.
This manual MUST be readily available wheneverthe unit is
handled or installed .
If this equipment suffers from any fault or damage, contact
the manufacturer and/or supplier immediately.
• Before commencing any work, ensure that the necessary safety precautions, risk assessments, and
safety documents are in place.
• Installation must be carried out observing the Operational Safety Rules.
• Check substation earth is intact - if missing, seek advice.
• In all instances, risk assessments should be undertaken prior to undertaking any new activity where
potential hazards are concerned. This is particularly important in order to identify the necessity for
specific Personal Protective Equipment, that may be required and that cannot be avoided even with
safe systems of work in place.
• It is strongly recommended when undertaking any form of switching operation that the appropriate
PPE is worn. Many PPE suppliers provide Flash resistant or Arc Flash clothing for this purpose.
This equipment contains the fluorinated greenhouse gas
sulphur hexafluoride (SF6) covered by the Kyoto Protocol
withaglobalwarmingpotential.SF6shallberecoveredand
not released into the atmosphere.
For further information on use and handling of SF6, See IEC 62271-4:2013 High-voltage switchgear and
control-gear – Part 4: Handling procedures for sulphur hexafluoride (SF6).

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 6
3. GENERAL PRODUCT INFORMATION
Aegis 36 is a compact SF6insulated ring main unit, which is specially designed for secondary distribution
networks, wind farms and photovoltaic power stations with ratings of up to 36kV.
Modularity –The flexibility of function
combinations allows for Load Break Switch and
Circuit Breaker modules to be placed in any
position in the unit, according to the customer
specification.
Load Break Switch –The switches are of the
single break, fault-make/load-break 3 position
types ’ON’, ‘OFF’ and ‘EARTH-ON’.
Stainless steel gas enclosure –The gas
enclosureis manufacturedfrom stainless steel and
fabricated utilising automatic ‘robot welding’
techniques to produce consistent leak-free
equipment.
Operation – All operating positions and directional
indicators are on the main front fascia of the unit.
Operation is by means of manually independent
mechanisms, which are mounted externally to the
gas enclosure.
Housing – The housing of the Aegis 36 is fully
treatedusingzinccoatedsteelandelectrostatically
applied oven cured paint to resist weather and
aggressive atmospheric environments.
Test facilities – Fully integrated and interlocked
earth and test facilities in accordance with ENATS
41-36 requirements. Access to the test terminals is
achieved by opening the cover located on the front
fascia.
CircuitBreaker–Comprisedofthreesinglephase
vacuum interrupters (which have fault make break
rating) and in series with 3 position disconnector
incorporating ON, OFF and EARTH-ON position.
The opening of the circuit breaker occurs
automatically when a fault is detected, or manually
when the push-to-trip button is actuated.
Interlocks – Positive operation safety interlocks
are incorporated on all switch and circuit breaker
positions.
Padlocks – All switch and selector positions can
be padlocked. The padlock has an 8.5 mm
diameter hole size.
Pressure Gauges – Aegis 36 has three types of
pressure gauges available, see “section 3.3
Pressure Indicators” on page 8

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 7
3.1 Test facilities
The Aegis 36 has optional fully interlocked integrated Earth and Test facilities. Access to the Earth and Test
terminals are achieved by opening the Earth and Test door located on the front fascia.
See LIOM16-015 Operating & Maintenance Manual, section: “Earth & Test Access”.
3.2 Padlocks
All switch and selector positions can be padlocked. The padlock has an 8.5mm diameter hole size.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 8
3.3 Pressure Indicators
The Aegis unit has three options of gas density/pressure indicators available, see below for further
information.
Normal Pressure Gauge
Non temperature compensated Gas Density Indicator
Non temperature compensated Gas density monitor with alarm
contact
Temperature compensated
Pressure IndicatorsTechnical Data
Accuracy ± 1% at 20 deg.
Scale Range (Relative) -1...0.8 Bar
Appearance -1...0.2 Bar Red Zone
0.2 - 0.8 Bar Green Zone
Signalling Contact (Only in GDM) 1 x N/O
Threshold Pressure 0.2 Bar
Connection to the Tank Solid
3.4 Extensible Type
For top extensible installation instruction, see the LIOM16-043 Coupling Manual.
Example Aegis 36 Top extensible unit shown below is an 1 + 3 way outdoor coupled unit.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 9
4. FRONT PANEL LAYOUT
Legend:
1 : Gas Pressure Indication
2 : Earth Fault Indicator
3 : Rating Plate
4 : Load Switch Operation Collar
5 : Earth & Test Access Cover
6 : Load Switch Selector Indication Window
7 : Load Switch Position Indication Window
8 : LV Panels
9 : Load Switch Selector
10 : Load Switch Cable Test & Cable Box Interlock
11 : Voltage Detection System
12 : Protection Relay
13 : Circuit Breaker Operation Collar
14 : Circuit Breaker Disconnector Collar
15 : Circuit Breaker Cable Test & Cable Box Interlock
16 : Circuit Breaker Disconnector Selector
17 : Disconnector Position Indication Window
18 : Circuit Breaker Position Indication Window
19 : Operation Handle
20 : Document Holder
21 : Cable Compartment
22 : Push-to-trip Button

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 10
5. TECHNICAL DATA
General
Rated voltage 36kV
Rated frequency 50/60Hz
Busbar Rated normal current 630A
Busbar Rated short time withstand current 21kA (1 s & 3 s), 25 kA (1 s & 3 s)
Busbar Rated peak withstand current 52.5kA, 62.5/65kA
Rated lightning impulse withstand voltage
Phase-to-earth 170kVp
Across isolating gap 195/220kVp
Rated power frequency withstand voltage
Phase-to-earth 70kV for 1 min
Across isolating gap 80kV for 1 min
Degree of Protection
Indoor IP41
Outdoor IP54
Tank with HV parts IP67
Mechanical impact protection IK07 indoor / IK10 outdoor
Internal arc rating
AF/AFLR 16kA 1 sec, 20kA 1 sec, 25kA 1 sec
SF6 gas
Annual leakage rate <0.1%
Filled pressure (at 20ºC) 0.4 Bar (G)
Minimum operating pressure 0.2 Bar (G)
Installation conditions
Ambient air temperature -25 to +55°C
Maximum altitude 1000m
Relative humidity (max) – over period of 24hrs
(IEC 62271-1, sub-clause 2.1) 95%
Salt deposit 40 mg/100 cm2mg/cm2
Continuity of Service LSC2 Class
Partition Class PM Class

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 11
Load Break Switch: L Function (Non-auto reclose)
Rated normal current 630A
Rated circuit breaking current 630A
Rated cable charging breaking current 35A
Rated cable & Line charging breaking current under earth fault 35A
Rated cable and line charging current 60A
Rated earth fault breaking current 105A
Main electrical circuit
Rated short time withstand current 21kA (1 s & 3 s), 25 kA (1 s & 3 s)
Rated peak withstand current 52.5A, 62.5/65.0A
Earthing circuit
Rated short time withstand current 21kA (1 s & 3 s), 25 kA (1 s & 3 s)
Rated peak withstand current 52.5A, 62.5/65.0A
Mechanical endurance class
Load break switch / Circuit Breaker Class M1 (2000 operations)
Earth switch Class M0 (1000 operations)
Electrical endurance class
Load break switch Class E3 (100 load breaks and 5 fault
makes Operations)
Earth switch Class E2 (5 fault makes Operations)
Operating mechanism
Operating sequence for mechanism -
Local: Close – Open Hand Lever Close–Open
Remote: Close – Open Motor Close–Open
Circuit Breaker Switch: V Function (Non-auto reclose)
Rated normal current 630A
Rated short circuit breaking current 25kA
Rated cable charging breaking current 100A
Rated line charging breaking current 10A
Rated cable and line charging current -
Rated earth fault breaking current -
Main electrical circuit
Rated short time withstand current 21kA (1 s & 3 s), 25 kA (1 s & 3 s)
Rated peak withstand current 52.5, 62.5/65.0
Earthing circuit
Rated short time withstand current 21kA (1 s & 3 s), 25 kA (1 s & 3 s)
Rated peak withstand current 52.5, 62.5/65.0
Mechanical endurance class
Load break switch / Circuit Breaker M1 (2000 operations)
Earth switch M0 (1000 operations)
Electrical endurance class
Circuit Breaker Class E2 (5 fault makes Operations)
Earth switch Class E2 (5 fault makes Operations)
Operating mechanism
Operating sequence for mechanism O-3min-CO-3min-CO
Local: Close – Open Lever – Push Button
Remote: Close – Open Motor – Shunt Trip Coil

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 12
6. LINE DIAGRAMS
All line diagrams shown are examples only.
6.1 Non-Extensible Functions.
6.1.1 Single Function L: Load Break Switch 630A 6.1.2 V: Circuit Breaker 630A
Incoming/outgoing unit with load switch disconnector. Transformer protection unit with vacuum circuit breaker.
6.1.3 2-Way (LV) 6.1.4 3-Way (LVV)
Example of a 2-Way configuration. Example of 3-Way configurations.
6.1.5 4-Way (LVVV)
Example of a 4-Way configuration.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 13
6.2 Extensible Functions.
6.2.1 Single Function L: Load Break Switch 630A 6.2.2 V: Circuit Breaker 630A
Incoming/outgoing unit with load switch disconnector. Transformer protection unit with vacuum circuit breaker.
6.2.3 2-Way (LV) 6.2.4 3-Way (LVV)
Example of a 2-Way configuration. Example of 3-Way configurations.
6.2.5 4-Way (LVVV)
Example of a 4-Way configuration.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 14
7. DIMENSIONAL DRAWINGS
7.1 Unit Range - Dimensions and Weights
Unit weights stated are for guidance purpose only. Weights will
vary depending on optional facilities added to the unit.
Dim A Cable Termination Height (mm)
Standard Termination Height=653mm
With additional Baseframe of 250mm= 903mm
7.1.1 Non Extensible Height 7.1.2 Extensible Height

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 15
7.1.3 1 - Way Outdoor 7.1.4 1 - Way Indoor
7.1.5 2 - Way Outdoor 7.1.6 2 - Way Indoor

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 16
7.1.7 3 - Way Outdoor 7.1.8 3 - Way Indoor
7.1.9 4 - Way Outdoor 7.1.10 4 - Way Indoor
7.1.11 Weights
No of Ways Indoor/Outdoor - Non Extensible (kg) Indoor/Outdoor - Extensible (kg)
1-Way - 400
2-Way 520 570
3-Way 850 950
4-Way 1000 1100

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 17
8. RATING PLATES
8.1 Unit Rating Plate Details
The rating plates are located as shown:
Pme - SF6gas rated filling pressure (density) for
operation Pre - SF6gas rated filling pressure (density) for
insulation
fr - Rated Frequency Ur - Rated Voltage
Up - Lightning impulse withstand voltage LSC - Loss of service continuity category
Ud - Power frequency withstand voltage IAC - Internal arc classification
Ir - busbar Rated normal current Int arc - Internal arc rating of unit tank
Ik - busbar Short time withstand current (RMS) SF6- Mass of SF6gas
Ip - Short time withstand current (peak) TC - Temperature class
tk - Short time withstand current rated duration of short
circuit Mass - Weight of unit
Pcs - D.C. component of rated short-circuit breaking
current at contact separation corresponding to the d.c.
time constant of the rated shortcircuit breaking current
Class - Electrical/mechanical endurance
Isc - Short Circuit Current
8.2 Standards
Aegis complies with the latest standards:
IEC 62271 - 100 Alternating current circuit breakers.
IEC 62271 - 102 Alternating current disconnectors and earthing switches.
IEC 62271 - 103 Switches for rated voltages between 1kV and 52kV.
IEC 62271 - 200 AC metal enclosed switchgear and control gear.
IEC 62271 - 206 VPIS systems for rated voltages between 1kV and 52kV.
IEC 62271 - 1 HV switchgear and control gear: Common specifications.
IEC 61243 - 5 Voltage detecting systems (VDS).
IEC 60255 Measuring relays and protection equipment.
IEC 60529 Degrees of Protection.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 18
9. HANDLING
9.1 Acceptance of unit
• The original packaging must be in good condition covering the unit on arrival.
• On arrival carry out a visual inspection of the unit and its functional components.
• Verify that the rating plate data matches the original order.
9.2 By receiving inspection
Before the unit is accepted it should be inspected carefully for loss or damage incurred
during transit.
The order must be in good condition at the time of receipt. If any such damage has
occurred, a claim must be submitted to the carrier immediately.
9.2.1 Unit RAL colour information
Below are the standard colours of a Aegis 36 unit.
• Unit Chassis & Panels = RAL 9002 – Grey white
• Fascia=RAL 7046 - Telegrey
• Earth and Test Covers = Pantone 286U - Blue Smooth
Althoughthesearethestandard colours,units are also suppliedin ‘customer specific’ colours - call forfurther details.
9.3 Symbol guidance
Keep dry Handle with care This way up Keep away from direct
sunlight
Storage Temp Do not step on High centre of gravity Do not stack
All symbols are to be taken as strict guidelines and are adhered
too, as a prevention of damage to the unit and injury to user.

LIOM16-014 Issue 6 Aegis 36 - Installation, Test & Commision Manual March 2022 19
9.4 Packaging Dimensions
For unit weights, see “section 7.1.11 Weights” on page 16
Package Dimensions
Fn Dimensions in mm
Height (A) Width (B) Depth (C)
1 150 700 1000
2150 1000 1000
3 150 1600 1050
4150 1900 1050
Fn = Number of functions
Keep all Aegis 36 unit surfaces clear, Do not place/rest objects on
top of the Aegis 36 unit.
Table of contents
Popular Industrial Equipment manuals by other brands

Kobelt
Kobelt 5020-M Series Owner's Operation, Installation & Maintenance Manual

Bredenoord
Bredenoord R0292 Operation manual

Nitta
Nitta FP-200 Operator's manual

Syntron Material Handling
Syntron Material Handling BF-4-ALF Service manual

Epson
Epson GX Series manual

R.V.R. Elettronica
R.V.R. Elettronica TLC300 user manual