Lux Power Technology LXP Series User manual

LXP HYBRID INVERTER
USER MANUAL
Version:EN-UM-2.0-03
LXP 3K/3.6K/4K/4.6K/5K/6K Hybrid
LXP 4K/5K/6K HB
LXP 3K/3.6K/4K/4.6K/5K/6K MG
Monitor APP Download
Android IOS
Standard Model:
Parallel Model:
High Voltage Model:

1
About This Manual
CONTENTS
Safety
Brief Introduction
2
Symbol Explanation
1.1
Safety Instruction
1.2
System Solution
2.1
Installation
3
Packaging List & Storing
3.1
Select Location
3.2
Install the Inverter
3.3
Connection
3.4
Connection Overview
3.4.1
Operation
4
01
01
01
01
03
03
04
04
06
05
07
07
PV Connection3.4.2 08
Battery Connection
3.4.3 09
Grid Connection
3.4.4 11
UPS/Back-up Connection
3.4.5 12
Meter and CT Connection
3.4.6 13
Communication Connection3.4.7 14
DRMs Connection3.4.7.1 14
3.4.7.2 15
3.4.7.3 16
Wireless Communication Module Connection
3.4.7.4 16
Grounding
3.4.8 17
Operation Mode
4.1
LCD operation and settings
4.2
LCD Menu Structure Overview
4.2.1
Status and Parameter show in LCD
4.2.2
LCD Settings
4.2.3
Information Searching
4.2.3.1
4.2.3.2
17
17
18
18
18
21
21
23
Monitor System
4.3
Work with Gen set
4.4
Parallel System Setup Guidance
4.5
31
32
31
34
34
34
Start-up and shut down the inverter
5
5.1
Connect the Meter3.4.6.1 13
3.4.6.2 14
Connect the CT
Safety Standard Configuration - SW2
Balancing Resistor Configuration - SW1
Settings Guidance
34
34
34
34
35
Troubleshooting & Maintenance
Troubleshooting
6.1
Introduction to LED Displays
6.1.1
Maintenance
6.1.2
Troubleshooting Based On LCD Displays
6.1.3
6
Start up the inverter
Shut down the inverter
5.2

01 02
“ ” Danger in dicates a
hazardous sit uation
which, if not avoided,
will result i n death or
ser ious injury.
“Warning” indicates a
hazardous situation
which, if not avoided,
could result in death
or serious injury.
“ ” Caution ind icates a
hazardous sit uation
which, if not avoided,
cou ld r esult in minor
or moder ate injury.
“Notice” provides tips
that are valuable for the
optimal operation of
your products.
Be ware of high PV voltage. Please turn-off the DC switch of PV Panel output before and during
the installation to avoid electric shock.
Be ware of high grid volta ge. Please turn-off the AC switch of grid connection before and during
the installation to avoid electric shock.
Do not operate the inverter when it's working, only the LCD and buttons can be touched in
limite d cases by qualified personnel, other parts of the inverter can be touched when the inverter
is under a safe state(e.g. fully shut-down).
Inspect the connections are good between inverter and PV, battery and grid during installation
to prevent damages or injuries caused by bad connections.
Inspect relevant existed wiring on-site of the installation is under good condition before
installation, operation or maintenance.
Make sure the inverter is well grounding, an operator should make sure itself is good protected by
reasonable and professional insulation measurements (e.g. personal protective equipment (PPE)).
Do not connect or disconnect any connections (PV, battery, grid, communication etc.) of the
inve rter when it's working.
Be ware of large current of the battery output. Please turn-off the battery module before and
during the installation to avoid electric shock.
Do not open the inverter when it's working to avoid electric shock and damages from live voltage
and current from the system.
Be ware of burning hurt, the inverter and some parts of the system could be hot when working,
please do not touch the inverter surface or most of the parts when they are working. During
inverter working states, only the LCD and buttons could be touched.
All connections must be in accordance with local and national regulations and standards.
Only when permitted by utility grid, the inverter and system can interconnected with the utility grid.
All the work of this product (system design, installation, operation, setting and configuration,
maintenance etc. must be carried out by qualified personnel as required.
All the warning table or nameplate on the inverter must be clearly visible and must not be
removed, covered or pasted.
The installation should choose a right position and location as required in this manual with
consider ation to safety of users' in future operation.
Please keep the children away from touching or misoperation the inverter and relevant system.
1. Safety
There might be possible dama ge to health as a result of the effects of radiation, do not stay
closer than 20cm to the inverter for long time.
Only qualified personnel can change the inverter settings.
The qualified personnel should have had training in the installation and commissioning of the
electrical system as well as dealing with hazards, also they should have the knowledge of the
manual and other related documents. As the installer or operator they are required to be familiar
with local regulations and directives.
Please carefully read this manual before any work carried out on this inverter, after the
installation, please keep this manual carefully stored and easy to access at any time.
The inverter has been designed and tested strictly according to international safety regulations. Read all
safety instructions carefully prior to any work and observe them at all times when working on or with the
inverter. The operator must be qualified personnel and the installation must be capable with relevant
national or international standards or regulations.
Incorrect operation or work may cause:
- injury or death to the operator or a third party; or
- damage to the inverter and other properties belonging to the operator or a third party.
There are many safety issues need to be carefully notified before, during and after the installation, and
also in future operation and maintenance, following is important safety notifications to operator, owner
and user of this product in appropriate usage.
The general information and safety instruction is highlighted with following symbols in this manual:
Following list shows the meaning of all the safety symbols on inverter type label:

03 04
2. Brief Introduction 3. Installation
3.1 Packaging List & Storing
This product and relevant system is suitable for following system applications (system diagram):
When the packaging is unpacked, the inner components should be the sam e as described in below
packaging list.
Hybrid I nverte r X1
Wall-m ounte d
Bracket X1 User Ma nual X1
Rj45 Ext ension
Termi nal X4
Commu nicati on
Port Cov er X 1 Wi-Fi M odule X 1 AC Conn ector X2 Meter X1
CT X1 PV Con ne ctor X4 RJ45 Term inal X4 Expans ion Scre w
and Tube X4 Secu rity Screw X 2 O T T ermin al X2
Cross He ad
Screw X13
The inverter must be stored appropriately if not installed immediately, refer to below figure.
CAUTION
a) The inverter and its components must be stored in its original packaging.
b) The storage temperature should be within -25~60 and humidity within 0~85%.
c) The packing should be upright and maximum stacked layers is 6 .
d) Do not exposed the inverter and its packaging to directly sunshine, raindrops and keep away
from corrosion.
Grid
Router Lux Power Viewer
A. Solar and energy storage hybrid system B. Energy storage system without solar
C. On-grid solar system without battery
(hybrid ready)
D. Off-grid and back-up applications
E. Hybrid system with zero export funtion F. Parallel system for MG model
Battery communication
cable which is used for
Pylontech battery, for
other brand battery,
please make the cable
according to PIN definition
Reserved
Battery&UPS
Interfaces

05 06
3.2 Select Location
The LXP hybrid inverters are designed as IP65 devices with a capability to be installed in both outdoor and
indoor conditions. However, selecting an optimal installation location is highly recommended to increase
the safety, performance and lifespan of the inverter.Please note the installation should not be accessible to
children for safety consideration.
Suggestions and Requirements
a) The wall for mounting should be strong enough to bear the weight of inverter .
b) The ambient temperature is required to be within -25°C ~ 60°C.
c) To ensure the heat dispassion efficiency and inverter lifespan, do not install the inverter enclosed.
d) The structure of the wall where inverter mounted should not be flammable, or make sure the inverter is
not surrounded by flammable or corrosion materials and is away from the gas.
e) Never install the inverter exposed to directly sunshine, rain and snow. Please refer to below figure and
select a well shaded place or install a shell to protect the inverter from directly sunshine, rain and snow etc.
3.3 Install the Inverter
The inverter is wall-mounted installed , steps shows below:
Step1. Use the wall-mounting bracket as the template to mark the position of the 4 holes, then drill 8 mm
holes and make sure the depth of the holes is deeper than 50mm.
Step3. Install the inverter on the wall-mounting bracket and lock the inverter using the security screws.
Step2. Install the expansion tubes into the holes and tight them, then use the expansion screws (packaged
together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.
>75 90 >90 90

07 08
3.4 Connection
3.4.1 Connection Overview
The system connection diagram is as below:
Please prepare the breakers before connetion, breakers selection recommendation for both DC and AC
Connection Terminals and Interfaces Overview
Battery
Terminals
PV
Terminals
AC
Terminal
UPS
Terminal
Wi-Fi
Module
DC
Switch
Communication
Interfaces
3.4.2 PV Connection
6-8 mm
- Before connection the PV, please use the multi-meter to measure the PV array voltage to
verify if PV array is working normally, if not, please fix the PV array to normally working
states before connection
C a b l e D i a m e t e rCross-section Minimum Voltage
3 - 6 mm22-2.6mm 600V
The PV connection of LXP hybrid inverter is the same to traditional on-grid solar inverter (string inverter).
Cable Requirement:
Ste p 1:Turn off or disconnect the PV switch (DC switch). Then keep this switch always open during
the connection.
Ste p 2:Assemble the PV connector
a) Strip 6~8mm insulation from the cable end.
- When your PV panel ambient temperature could possibly be lower than 0 , then please
check the PV array voltage up ceiling and if you are not sure please ask your system or
panel provider for further assistance. As when temperature is extremely low the PV panel
voltage will increase by a certain percentage.
℃
b) Assemble the cable ends to crimp contacts.
c) Lead the cable through the cable gland, then insert into the corresponding insulator until it snaps
into place, then tighten the cable gland.
When verified the PV connector is tightly, align the 2 half connector and mate them together by hands
until ‘click’ is felt or heard.
Hybrid
DC Breaker
selection(2 poles)
AC Breaker
selection(2 poles)
UPS Breaker
selection(2 poles)
LXP 6K
(MG)
50A/500V
50A
50A
LXP 3K/3.6K/4K
(MG)
100A/100V
40A
40A
LXP 6K HB
(MG)
LXP 4K HB
(MG)
LXP 4.6K/5K
(MG)
100A/100V
50A
40A
LXP 5K HB
(MG)
50A/500V
50A
50A
50A/500V
50A
50A
50A/500V
50A
50A
UPS Load

09 10
3.4.3 Battery Connection
If the battery type is lithium-ion or ternary battery which need communication between the inverter
and battery management system (B MS), the communication connection must be installed.
RJ45 Terminal Configuration of Battery Communication
Pin
1
Function Description
2
3
4
BAT 485 B
BAT 485 A
BA T CAN L
BAT CAN H
5
6
7
8
NC
BAT NTC
BAT Wake UP
GND-S
Pin 1 2 345678
Make the RJ45 terminal based on above introduction of each Pin definition, you could either make
RS485 connector or CAN connector based on the best support connection way of your battery packs.
For Lead acid battery temperature sensor, please connect signal to Pin6 and Pin8, the other pins are
not connected.(External temperature sensor is needed, the sensor is 15KΩ thermistor for typical, or
consult Luxpowertek)
This part in this manual only describe the battery connection on inverter side, should you need more
detailed information regarding the battery connection on battery side please refer to the manual of
the battery you are using.
Ste p 1: Assemble the terminal.
battery connection
A. Diameter
B. Cross Section
C. Strip Length
10-12mm
20-25mm²
-10mm
Cable
Tighten Waterproof Sl eeve
Terminals On Inverter
① ② ③
①
②
③
Recommendations
Install a DC isolator between battery and inverter
can avoid potential damages caused by electric arc.
Red Cable
Black Cable
+
2*M6 Screws
Warning!
Polarity reverse will damage the inverter!
For the first time power on, please turn on the battery after LCD show "Run without Bat",
otherwise the it may shorten the lifetime of inverter.
For lead acid batteries temperature sensor, please refer to Page29 “Cable Connection” figure.
For Li-ion battery
For Lead-acid battery
1. If work with lithium battery , please make sure it is compatible with the Lux units. Now Lux
Power inverter is compatible with Pylontech, Dyness, Aoboet, Weco, Murata, Merit 48V battery.
2. After battery power cable and communication cable connection, users need to choose battery
brand by LCD
3.The battery communication cable inside the Luxpower carton box is used for Pylontech battery,
if you are using Pylontech battery, you can use the cable directly. Please note there is label ‘BAT’
(ne ed to plug into battery side) attached with the cable, do not plug the battery side terminal to
the inverter side
4.If you install more than 8pcs Pylontech battery, you need a hub for the battery.
5.Please remember to connect Master battery to inverter if you have battery group, and set the
Master battery for the battery group.(Please conta ct battery manufacture for battery group setup)
1. The lea d acid battery temperature sensor cable is optional, if required, please request the
temperature sensor cable from your supplier.
2. There are three stages for lead acid battery charge . For charge part, please set CV voltage and
floating voltage. For discharge part, please set the discharge cut off voltage for on grid and off grid
.
.
.
Connection between inverter and battery

11 12
3.4.4 Grid Connection
a) Lead the AC cable though cable gland, seal ring
and threaded sleeve, and fully insert the conductors
to corresponding terminals on connection terminal
and tighten the screws.
c) Assemble the GRID connector and make sure that
the rib of the terminal block and the groove on the
housing engage perfectly until a ‘click’ is heard or felt.
a) Align the GRID connector and AC terminal and mate them together by hand until a ‘click’ is heard or felt .
c) Connect the PE conductor to grounding electrode, and connect N and L conductors to AC breakers.
d) Connect the AC breakers to the AC grid.
3.4.5 UPS/Back-up Connection
Cross-section Diameter
4 - 6 mm22 mm - 2.6 mm
Cable Requirements:
Step 1: Assemble the AC connector.
AC Connector Structure Overview
b) Refer to below figure and confirm the AC cables
are correctly connected. The difference between the
AC connector and UPS connector is that AC connector
has a “Grid” mark on it and UPS does not
Ste p 2: Install the AC connector
b) An AC breaker (AC switch) should be installed between inverter and the grid, confirm the AC breaker
is working normally before connect the AC cable from inverter to AC breaker. Turn off the AC breaker
and keep it open.
Cable requirements
Step 1: Assemble and install the UPS connector process is the same as AC connectors which show
in Chapter 5.4 Grid Connection (the Step 1 and Step 2). Finish the UPS connector assembling and
installation first of all.
There are 2 different UPS wiring mode in accordance with different local or national rules, standards
or regulations. Please choose the suitable wiring mode according to the local requirements.
Mode A:Neutral line of alternative supply must not be isolated or switched.
The connection diagram of UPS Connection Mode A is shown in below figure.
Backup loads neutral and grid neutral are connected internally inside the
inve rter, so the installer do not need to connect them outside. The power
of backup load should be lower than 5kW.
Mode B:Neutral line of alternative supply can be isolated or switched.
The connection diagram of UPS Connection Mode B is shown in below figure.
Cross-section Diameter
4 - 6 mm22 mm - 2.6 mm
Cross-section Diameter
4 - 6 mm22 mm - 2.6 mm
Cross-section Diameter
4 - 6 mm22 mm - 2.6 mm
UPS Load
UPS Load
e) You must install a separate single-phase circuit-breaker or other load disconnection unit foe each
inverter in order to ensure that the inverter can be safely disconnected under load.
The inverter has the function of detecting residual current and protecting
the inverter against residual current. If your inverter has to equip a AC
breaker which has the function of detecting residual current, you must
choose a AC breaker with the rating residual current more than 300mA.

13 14
3.4.6 Meter and CT Connection
In a completed installed on-grid energy storage system, the CT or Meter should be installed. The CT or Meter
should installed in the right position as below picture
The communication port for communicate with
meter or CT clamp is as below:
Pin Function Description
3.4.6.1 Connect the Meter
Step1. Connect the meter in the LN line as below
Inverter
Side
AC Grid
Side
3.4.6.2 Connect the CT
12
Step2. Connect the communication cable
between inverter and meter, and plug the
RJ45 to communication port
3.4.7 Communication Connection
Interface Overview
3.4.7.1 DRMs Connection
DRMs is short for ‘inverter demand
response modes’, and it is a mandatary
requirements for inverters in Australia
Pin 1 2 3 4 5 6 7 8
RJ45 Terminal Configuration of Meter/CT Communication
The functional interfaces overview of the meter is shown in below figure. Now Luxpower only support
EASTRON SDM120 and SDM630- Modbus Modbus model meter.
Step3. Check the connection. When the meter displays -xxxxW as below figure shows, the hybrid
inverter is feeding power to the grid.and when it displays xxxxW, it means the house load is using
energy from grid.
Battery Communication Interface
Safety Standard Configuration Switch
Balancing Resistor
Configuration Switch
CT and Meter
Communication Interface
Parallel cable
communication Interface
Parallel cable
communication Interface
DRM Interface
DRM Communication Interface Overview
/
For the CT clamp connection, we need to put the CT clamp in the L cable and the arrow printed on the CT
should point to inverter.
Now Luxpower support two ratio and CT clamps . For default, the ratio is , if you install
another CT clamp, please set it in the monitor system or LCD.
For the CT clamp cable, users can use the normal net cable to extend the length if the original length is not
enough. The longest distance can be 100m.
1000:1 3000:1 1000:1
Generator Controller Box Interface
Pin
1 2 3 4 56 7 8
RJ45 Terminal Configuration of DRM
Pin
1
Function Description
2
3
4
DRM15
DRM26
DRM37
DRM48
5
6
7
8
RefGen
DRM0
+12V
GND-S
5/6 Reserved
CTN
CTP
UPS Load UPS Load

15 16
Country
Standard
Country
Standard
By configuring the SW1 balancing resistor configuration
switch, you could configure the balancing resistors of
parallel CAN comm unication. This Function is used for
multiple inverter paralleling operation.
Please turn on the DIP in the first and last inverter in the
inve rter loop. For more info, please check the parallel
connection part.
By configuring the DIP switch the inverter could comply
with different safety requirements of various areas.
Sw2 Safety Standard Configuration Switch Overview
Note: The DIP switch is composed of five-digit binary number
PINs. Each PIN has two status, when set upward to“ON”, its
value turns to“1”, when set downward, its value turns to “0”.
Safety Standard Configuration Guidance
Default
VDE0126
Germany
VDE0126
Australia
AS4777
New Zealand
NZS
En50549
United Kingdom
G59
United Kingdom
G83
Germany
N4105
Europe
EN50438
Italy
CEI0-21
South Africa
NRS 097-2-1
Finland
EN 50438
Thailand
PEA
Thailand
MEA
Ireland
EN 50438
Czech
EN 50438
SW2
Configuration
SW2
Configuration
3.4.7.4 Wireless Communication Module Connection
Pin Function Description
1 & 2
3 & 4
The Wireless C ommunication Interface Details

17
3.4.8 Grounding
A second protective earth (PE) terminal is equipped at the side of the inverter.
Be sure to connect this PE terminal to the PE bar for reliable grounding.
When you fi nish all of above chapters of c onnections,
please don’t forget to install the protective shell back
to the inverter . This step can be carried out either after
finished grounding or commissi oning of the system.
Cable Requirements
3-6mm² copper cable or 10-16mm² aluminum cable.
Install the Protective Shell
17
4. Operation Guide
4.1 Operation Mode
Users can have different settings to satisfy their demands, the working modes is as below:
Operation
mode Related SettingsExplanation Application Notes
Self usage
(Default mode)
The priority of the PV energy will be Load >battery
> grid, which means the energy generated by PV
will be mainly used by local loads, and rest will be
stored in the battery, excessive power will be feed
back into the grid.
Effective when charge
priority and force time
charge/discharge are
disable
Charge priority
Charge Priority and
related time, SOC
Force time
Force charge/discharge
enable and disable, and
related time SOC
This mode suits for situation
where the price difference of
energy is big under Time of
Use (To U)
Micro Grid
mode(Genset)
When used in pure off grid application, users may
connect the Gen set output to grid input , when
battery SOC is low. Inverter will use generator to
take the load and charge the battery.
Micro grid enable
/disable
Area where is no grid and
there is utility
Off grid mode Inverter will switch to off grid mode
automatically when there is no grid. UPS enable Area where is no grid
The priority of the PV energy will be battery >Load >grid,
which means the energy generated by PV will be used to
charge the battery first, and then used by local loads,
excessive power will be feed back into the grid.
User can set the charging and discharging time and
priority of energy use under Force Time Use mode .
This is also used to flexibly make use of your system
by customized settings by the users.
increase the self consumption
rate and reduce the energy bil
significantly
When the load shedding
always happens, users need
to charge battery first
18
4.2 LCD operation and settings
4.2.1 LCD Menu Structure Overview
Display Menu
Fault
Flash
PV Grid On
PV Charge
PV Charge+ Grid On
Battery Grid On
PV+Battery Grid On
AC Charge
PV+AC Charge
Battery Grid Off
PV Battery Grid Off
PV Charge Grid Off
Standby PV Info
Battery Info
Grid Info
UPS Info
PV Charge+ Grid On
Set COM Address
Set Time
Set Language
Set Battery
Set PV Input
Set UPS Mode
Set AC Charge
Model
Ser No.
FW Version
Bulid
Error Record
Energy Record
Alarm Record
History Info Product Info
Status Measured Info Setting
PV Charge+ Grid On
Set Feed-in grid
Set EOD
Set CT or Meter
Set Micro-Grid
Set Parasys Role
Set Parasys Phase
(For MG model)
(For MG model)
4.2.2 Status and Parameter show in LCD
Inverter is waiting for sufficient DC voltage from the PV or battery. It occurs when the sunlight is not
sufficient to make the inverte r working and battery SOC is low.
Fault occurred with the inverter or system. Inverter will stop working unless fault or error is fixed.
Detailed information and troubleshooting please refer to Chapter 8. Troubleshooting & Maintenance.
When upgrading the firmware of inverter, the inverter will working at flash status.
There are 2 ways to upgrade the firmware of inverter:
- Remote upgrading based on remotely connected server through the wireless communication module.
- Locally upgrading through RS485 communication connection.

19 20
Parameters of Power:
Ppv: PV input power Pac: active power of AC output
Sac: apparent power of AC output Po: active power of UPS
So: Apparent power of UPS Pc: Charging power
Pd: discharging power PtoGrid: active power of exporting / feed-in to grid
Parameters of Voltage and Frequency etc.:
Vb: battery voltage Vo: UPS voltage
Vbus: voltage of DC bus Vg: grid voltage
F: frequency SOC: state of charge
Parameters of Energy:
Einvday: energy output via AC output today Einvall: total energy output via AC output
total feed-in energyEtoGall:
Ecday: charged energy today Ecall: total charged energy
Edday: discharged energy today Edall: total discharged energy
Eoday: UPS output energy today Eoall: total UPS output energy
Epv1day: energy generated today of PV array 1 Epv2day: energy generated today of PV array 2
Epv1all: total energy generated of PV array 1 Epv2all: total energy generated of PV array 2
Erecday: AC charge energy of today Erecall: total AC charge energy
EtoUday: energy consumed by loads today EtoUall: total energy consumed by loads
EtoGday: feed-in energy today
f) PV Charge + Grid On
The inverter is working normally on-grid, the power generated by PV is sufficient and within a range which
PV power is used to charge the battery and there are still excessive PV power rested to export or feed-in
via the AC grid connection. Under this inverter working status, your general loads will either consumption
the power from PV or use power from the grid or at them same time from the two sources, the detailed
situation is based on the PV power output range and your general loads power demands differences.
g) Battery Grid On
The inverter is working on-grid with no PV power input, and there are sufficient energy stored in the battery,
the inverter is discharging the battery and export the power via AC grid connection to your system.
h) PV+Battery Grid On
The inverter is working normally on-grid with limited PV power input and the battery energy is
sufficient, at this inverter working status the limited PV power is used together with the battery
discharging power to export or feed-in via the AC grid connection.
I) AC Charge
The inverter is working normally on-grid with no PV input power, and is using the AC power from the
grid to charge the battery as configured previously (the function should be enabled firstly as Chapter
Inverter Settings - h) AC Charge Settings described).
j) PV+AC Charge
The inverter is working normally on-grid with limited PV input power, and the batter SOC is not
sufficient, if at this time the inverter is configured to charge the battery with both PV power and
AC grid power, then inverter will run in this status.
k) Battery Grid Off
The inverter is working normally off-grid with no PV input power, and the battery SOC is sufficient.
When inverter works at this status, the battery is discharging to output power via the UPS connection.
l) PV Battery Grid Off
The inverter is working normally off-grid with limited PV input power, and the battery SOC is sufficient.
When inverter works at this status, the battery is discharging together with the PV power to output via
the UPS connection.
m) PV Charge Grid Off
The inverter is working normally off-grid with sufficient PV input power, and the battery SOC is
insufficient. When inverter works at this status, the inverter is charging the battery using PV power
and there are excessive power rested to output via the UPS connection.
d) PV Grid On
The inverter is working normally on-grid, and the all the power generated by PV will export or feed-in
via the AC grid connection to your general loads and the grid.
e) PV Charge
The inverter is working normally, the power generated by PV is within a range that all the PV power is
used to charge the battery, while there are no excessive power rested to output from neither the AC
Grid connection nor UPS connection.

21 22
In Display Menu interface, select History menu and touch Enter button to enter in t he History menu
interface and use Up and Down button to select relevant display menu and touch Enter button to
view detailed history information.
In Display Menu interface, select Product Info. menu and touch E nter button to enter in the Product
Info. menu interface to view detailed product information.
In Display Menu interface, select Measured Info. menu and touch Enter button to enter in the
Measured Info. menu interface to view detailed running information of the system, such as PV,
battery, grid and UPS data.
History Info
Error Record
Display Menu
Enter
History Info
Energy Record
Alarm Record
History Info
Alarm Record
History Info
xxxxxxxx
DownUP
Daily Record
Energy Record Error Record
Energy Record
xxxxxxxx
Total Record
Down
UP
Down
UP
EnterEnter Enter
DownUP
Energy Record
Hourly Record
DownUP
Energy Record
Monthly Record
DownUP
Energy Record
Yearly Record
Enter
Enter
Enter
Enter
Enter
Daily Record
xxxxxxxx
Total Record
Hourly Record
Monthly Record
Yearly Record
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
Product Info
Buidl: xxxxxxxxxx
Display Menu
Enter
Model:xxxxxxxxxx
Ser No:xxxxxxxxxx
FW Version:xxxxxxxx
Down
UP
4.2.3 LCD Settings
4.2.3.1 Information Searching
Refer to below flow chart which shows the information option interfaces and interconnection.
Operator can search target information by following below directions.
Touch Return button to enter Display Menu interface, search and select corresponding information
options using Up and Down button, relevant information will be immediately displayed on the LCD
screen after touched Enter button to confirm the selection.
Display Menu
Measured Info
Down
UP
Setting
Status
DownUP
Down
UP
Product Info History
Down
UP
Down UP
Display Menu
Display Menu
Display Menu
Display Menu
Enter

23 24
Operating Guidance: by touching Enter button to select the numerical digits of the COM address -
hundreds, tens and units, and use UP and Down button to set the number of selected numerical digits.
XXXXXXXXXX
Notice that the setting range of the RS485 communication address is from 000 to 255, and it’s set to
be 001 by default when manufactured.
Set Language
Enter
Enter
Set Language
Language : English
Enter
Down UP
Set Language
Setup completed
XXXXXXXXXX
Set OK!
Sprache : Deutsh
Down UP
Down
UP
Down
UP
Set Language
Idioma : Espanol
Set Language Set Language
Language : Francais Ligua : Italiano
Set COM Address
COM Address:001
Setting
Enter
Set COM Address
COM Address:001
Set tens:
COM Address:001
Set units:
Down UP
COM Address:001
Set hundreds:
Set tens:
Set hundreds:
COM Address:011
COM Address:101
Down UP
Set hundreds:
COM Address:201
Down UP
Set tens:
COM Address:201
Down UP
Down UP Down UP
Set units:
COM Address:002
Set units:
COM Address:003
Enter Enter
xxxxxxxxxx
Setup Completed
Set OK!
xxxxxxxxxx
Enter
Enter
*Set the hundreds digit *Set the tens digit *Set the units digit
Setting
4.2.3.2 Settings Guidance
Touch Return button to enter into Display Menu interface, search and select the Setting menu using
UP and Down button, and then touch Enter button to confirm and enter into inverter setting interface.
Set AC Charge
Display Menu
Enter
Setting
Set PV Input
Down UP
Setting
Setting
Set UPS Mode
Setting
Set Battery
Down UP
Down
UP
Down
UP
Set Language
Setting Setting Setting
Set Time Set COM Address
Down
UP
Down
UP
Down UP
Setting
In Setting interface, search and select the Set Battery menu and touch Enter button to confirm and
enter into battery setting interface. Set the battery paramete rs and configuration follow the direction
in below flow chart. Notice that the LXP Hybrid series energy storage inverter supports Lithium-ion
and Lead-Acid type batteries.
Operating Guidance: by touching Enter button to select the options and use UP and Down button to
set the parameter or number of selected options.

25 26
Operating Guidance: by touching UP and Down button to select the parame ter of the PV input.
Notice that the PV input parameters must be set in accordance to actually configuration of PV
system. The parameter is set to Two PV separate by default.
UPS Disable
UP EnableS
XXXXXXXXXX
Set UPS Mode
Enter
UPS Disable
Enter
Enter
UPS Mode On/Off Enter
Enter
Enter
Down UP
UPS Mode On/Off
Setup completed Set OK!
XXXXXXXXXX
UPS Voltage Set: Down
UP
Down
UP
Enter
Enter
UPS Voltage :xxxV
UPS Frequency:
XXXXXXXXXX
Setup completed Set OK!
XXXXXXXXXX
UPS Frequency:
UPS Voltage Set:
UPS Voltage :240V
Setting
Set UPS Mode
UPS Fre : 50Hz UPS Fre : 50Hz
In Setting interface, search and select Set Time menu then enter into time setting interface. Follow the
direction in below flow chart to set the time parameters.
Operating Guidance: by touching Enter button to select the numerical digits of the time - year, month,
date, hour and minute, and use UP and Down button to set the number of selected numerical digits.

27 28
Setting
Feed-in Enable
Feed-in Enable
Feed-in Forbid
xxxxxx
Feed-in Forbid Set Feed-in Forbid
Users are able to set end of discharge (stop d ischarging) battery level when there is grid. This setting
is important for some area where always has load sheddings.
Since in some countries, users can not feed energy into grid, so they are able to disable energy export
function in the LCD, or set power percent which can feed into grid.
XXXXXXXXXX XXXXXXXXXX
Enter
Set Feed-in grid
Set Feed-in grid
Enter
Set Feed-in grid Enter
Enter
Set Feed-in grid
Down UP
Set Feed-in grid
Feed-in 0%
Down
UP
Enter
Set Feed-in grid
Feed-in 100%
Down
UP
Set Feed-in grid
Feed-in 5%
Enter
Setup completed
xxxxxx
Set OK!
Setup completed Enter Set OK!
Set EOD
Enter
Set EOD
EOD : 10%
Enter
Set EOD
EOD : 10%
Enter
Down
UP
Setup completed Enter
Down
UP
Set EOD
EOD : 85%
Set EOD
EOD : 90%
Set OK!
Setting
In Setting interface, search and select the Set AC Charge menu and enter into AC charge setting
interface. Follow the directions in below flow charge to enable or disable AC charge function,
if enabled then configure relevant parameters.

29
Settin
g
For parallel system, users need to set one inverter to master and others to slave. If the system is single phase, then
users need to choose 1 phase master, if the system is three phase, then users need to choose 3 phase master.
For parallel system, the inverter is able to detect the phase auto if there is three phase grid input. If the application is
pure off grid three phase application, users need to set the phase output for each inverter. For master, it is considered
as R phase.
30
Set Parasys Role
Enter
Set Parasys Role
Enter
Slave
Setup completed
Slave
Down UP
Set Parasys Role
Enter
Setup completed
Down UP
Enter
Setup completedSet Parasys Role
3 Phase Master
1 Phase Master
3 Phase Master
1 Phase Master
Enter
Setting
Set Parasys Phase
Set Parasys Phase Enter
Setup completed
Set Parasys Phase
Setup completed
Enter
R Phase R Phase
Down UP
Down UP
S Phase S Phase
Setup completed
Set Parasys Phase Enter
T Phase T Phase
Setting
CT o m
r eter?
CT ?
or meter
CT or meter?
Settin
g
Mic Grid?ro-
Mic Grid?ro-
D wn
oUP
Mic Grid?ro-
When connect the generator to inverter AC terminal, users need to enable mirco grid function so the
inve rter will use generator to charge battery and will not export any power by AC terminal.
Since the inverter support the connection of both CT clamp and meter, users can select if the system
is connecting a meter or a CT clamp and then choose the CT clamp ratio when connects a CT clamp.
Enter
Enter
CT
CT or ? meter
CT
Enter
Enter
Down UP
meter
Set CT Ratio
3000:1
1 Phase meter
Meter type
Enter
Enter Meter type
1 Phase meter
3000:1
Set CT Ratio
UP Down
Set CT Ratio
1000:1
Enter
Enter
3000:1
Setup completed
1000:1
Setup completed
Enter
Enter
Setup completed Enter
Enter
Setup completed
Enter
Enter
3 Phase meter
Meter type
Down UP
3 Phase meter 3 Phase meter
Set OK!
1 Phase meter 1 Phase meter
Set OK!
3000:1
Set OK!
1000:1
Set OK!
Set Micro-Grid
Enter
Enter
Enable
Enable
Enter
Enable
Setup completed Enter
Enter
Setup completed
Disable Disable
Enter
Set OK!
Enable
Set OK!
Disable

32
4.5 Parallel system setup guidance
Please note that the parallel model is different from standard model, if users need to connect the UPS
together, they need to buy parallel model from distributors.
For parallel system setup,
Step1. Cable connection :the system connection for single phase paralleling is as below:
the system connection for threephase paralleling is as below:
4.4 Work with Gen set
All lux units can work with generator.
Users can connect the generator output to inverter Grid terminal. If you have both grid and generator as AC input,
we need an external ATS to switch between grid and generator.
Please purchase an external control box to remote turn on/off the generator(which support dry contact function).
The generator will be automatically started when battery voltage is lower than the cut-off value or there is charge
request from BMS. When voltage is higher than AC charge setting value, it will stop the generator
4.3 Monitor System
1.
Quick guidance for setting password for wifi module the paper is also available in the wifi box
2 and
Monitor system registration wifi password setting and wifi local monitor and setting
Introduction of monitor interface
,
.
, ,
.
Wifi Quick Guidance
Monitor system setup for Distributors Monitor system setup for endusers
3 Lux_Monitor_UI_Introduction
4 WebsiteSettingGuidance
.
Introduction of website settings for hybrid inverter
Users can use wifi donlge/WLAN dongle/4G dongle(Avaiblable from 2021 March for some countries) to monitor
the energy storage system, The monitor website is: server.luxpowertek.com
The APP is also available in the google play and apple APP store(Scan two code bar to download the APP).
Please download the introduction of guidance by website: https://www.luxpowertek.com/download/
Document Reference:
You should enable ‘Micro-grid’ function via the APP or Web page while you connect the generator to the
Lux unit. Battery will get charged when the generator is turned on, and the generator is bypassed to take
all loads in AC and UPS terminal.
EPS Bus Bar(L,N)-
PV AC Input
AC Output
CAN 1
CAN 2
BAT
DC
DC
DC
AC
AC
AC
AC
L
N
PE
L
N
PE
L
N
PE
L
N
PE
L
N
PE
L
N
PE
AC
AC
PV
CAN 1
CAN 2
BAT
PV
CAN 1
CAN 2
BAT
AC Input
AC Output
Parallel line 1
Parallel line 2
Grid Bus-Bar(L,N)
Grid Bus-Bar(L,N)
Grid Bus-Bar(L,N)
PE
PE
Grid
EPS LOAD
Inverter 1
AC Input
AC Output
Inverter 2
AC Input
AC Output
Inverter 3
PV AC Input
AC Output
CAN 1
CAN 2
BAT
DC
DC
DC
AC
AC
AC
AC
L
N
PE
L
N
PE
L
N
PE
L
N
PE
L
N
PE
L
N
PE
PV
CAN 1
CAN 2
BAT
PV
CAN 1
CAN 2
BAT
Parallel line 1
Parallel line 2
Grid or Generater
EPS
AC
AC
EPS Bus-Bar(L,N)
Grid or Generater
EPS
Grid or Generater
EPS
Phase L1
Phase L1
Phase L2
Phase L2
Phase L3
Phase L3
AC Input
AC Output
AC Input
AC Output
Inverter 1
Inverter 2
Inverter 3
31

33 34
6.1.2 Maintenance
Every segment of the system need to be check monthly/quarterly/yearly according to the detailed
requirements of each segment.
Inverter Maintenance
a) Check the inverter every 6 months or 1 year to verify if there are damages on cables, accessories,
terminals and the inverter itself.
b) Check the inverter every 6 months to verify if the operating parameter is normal and there is no
abnormal heating or noise from the inverter.
c) Check the inverter every 6 months to confirm there is nothing covers the inverter heat sink, if
there is, shut-down the inverter and clear the heat sink.
Battery Maintenance
As per different types battery, from the original manufacturer’s requirements on maintenance, when you
carried out these works on batteries, please make sure to fully shut-down the inverter for safety consideration.
6. Troubleshooting & Maintenance
6.1 Troubleshooting
When faults and errors occurred, please deal with these problems following below procedures and requirements.
6.1.1 Introduction to LED Displays
Display
LED Description
Green LED
Long light
Suggestion
Flashing
Working normally
Firmware upgrading Wait till upgrading complete
Yellow LED
Red LED
Long light
Long light
Warning, inverter working Need troubleshooting
Fault, inverter stop work Need troubleshooting
Step4. Enable share battery for the system if the system share one battery bank, otherwise disable the
shared battery function
Step5. Set the system as a parallel group in the monitor system
For more detailed guidance for paralleling system, please visit
And download the guidance
https://www.luxpowertek.com/download/
Step3. Setup Master and Slave for Parallel system. There should be only one master in the system. Set one
inverter as master and the others as slave
Please put the CAN communication PIN to on status for the first and the end inverter
Step2. Setup the monitor for the system,add all datalogs in one station. Users can login the visit the monitor system,
Configuration->station->Plant Management->add datalog to add the datalogs.
No.1 No.2 No.n-1 No.n
1
03
1 1
1
03
0 0
1
03
0 0
1
03
1 1
4 4 4 4
Parallel line1 Parallel line2 Parallel line(n-1 to n)
Parallel line(n to 1)
The max parallel quantity is 10, so 2<n<10
5. Start-up and shut down the inverter
5.1 start up the inverter
Step1. Turn on the battery breaker , then turn on "EPS Output" switch and check if the inverter works in
battery back-up mode.
Step2. Make sure the PV voltage of the strings are higher than 120V ,and check if the inverter works in PV
charge or PV back-up mode.
Step3. Make sure step1and 2 above work properly before turning the grid power or generator, and check
if the inverter can go to bypass mode and on-grid mode normally.
5.2 Shut down the inverter
Danger: Do not disconnect the battery , PV and AC input power under load.
If there is emergency issue , and you have to shut down the inverter ,please follow the steps as below,
Step1. Cut off AC input breaker of inverter side
Step2. Cut off the breaker of load side
Step3. Cut off PV breaker and then cut off the battery ,and waiting for the LCD goes off
Step4. Turn off "Power" switch on the inverter if needed.

35 36
E010
E011
E012
E013
E016
E017
E018
E020
E021
E022
E023
W000
W003
E031
E019
E015
E024
E025
E026
E027
UPS short circuit
Relay fault
Internal communication
fault 2
Internal communication
fault 3
Multiple master
Parallel AC inconsistent
UPS power reversed
Parallel phase abnormal
Bus voltage high
UPS connection fault
PV voltage high
Over current
Neutral fault
Both PV short circuit
Temperature over range
Internal fault
Sampling inconsistent
between main and slave CPU
Internal communication
fault 4
Communication failure
with battery
Communication failure
with meter
E010
E011
E012
E013
E016
E017
E018
E020
E021
E022
E023
E031
E019
E015
E024
E025
E026
E027
Bat Com Fault
Meter Com Fault
1.Check if the parallel system
have two masters at less.
2.Only allow one master,
reconfigure the others to slaves.
Check the AC connection
between parallel inverters
1.Check UPS L,N connection
2.Disconnect the UPS connector,
if the error still exist, contact us.
Restart the inverter, if the error
still exist, contact us.
Check the AC connection
between triphase parallel system
Restart the inverter, if the error
still exist, please contact us.
Wait for the inverter automatically
restart complete, if this error repeats
for several times, please contact us
Check UPS and AC connections
Restart inverter, if the error
still exist, please contact us
Check neutral connection
Check NTC Connection
Restart inverter, if the error
still exist, please contact us
Restart inverter, if the error
still exist, please contact us
Restart inverter, if the error
still exist, please contact us
Disconnect both PV connection,
if the error still exist, contact us
Fix communication cable, if the
warning still exist, contact us
Restart inverter, if the error
still exist, please contact us
Restart inverter, if the error
still exist, please contact us
W020
W021
W022
W025
W026
W027
W028
W023
W030
W018
W017
W016
W004
W005
Battery failure
Auto Test failure
No AC connection
AC voltage out of range
PV isolation low
Leakage current high
DC injection hig h
Battery voltage high
Battery voltage low
Battery open circuit
UPS over load
PV short circuit
Meter connection reversed
AC frequency out of range
Battery failure
Auto Test failure
AC F Outrange
AC V Outrange
No AC Connection
PV Isolation low
Leakage I high
DC Injection high
Bat Volt High
Bat Volt Low
Bat open
UPS Over Load
PV short
Meter Reversed
Restart inverter, if the warning
still exist, please contact us
Check AC grid frequency
Check AC grid voltage
Check AC connection
Restart inverter, if the error
still exist, please contact us
Restart inverter, if the error
still exist, please contact us
Restart inverter, if the error
still exist, please contact us
Check and fix battery connection
Check and fix battery connection
Check and fix battery connection
Check and adjust UPS load
Check and fix PV input connection
Check and fix meter connection
Check PV input connection and
If PV voltageis in range
Check if communication cable is
right and have choose the right
battery brand, if the warning still
exist, contact us
Restart battery, if the warning
still exist, please contact us and
battery manufactyre
6.1.3 Troubleshooting Based On LCD Displays
Once there are any warning or fault occurred, the LED and LCD will displays information to remind the
operator, the LCD will display relevant error code and short description.
Description
Code LCD Display Troubleshooting
E000 Internal communication
fault 1 E000 Restart inverter, if the error
still exist, please contact us
E001 Model fault 1 E001
Reset model, check if the safety
standard switch is in right place
E008
E009
Parallel CAN fault
Master loss
E008
E009
Check the parallel CAN cables
between inverters, and balance
resistor is in the right place
1.Check the parallel CAN cables
between master to slaves. and
balance resistor is in the right place
2.Check if the parallel system is
lack of a master inverte r, and
reconfigure a master.
This manual suits for next models
15
Table of contents
Other Lux Power Technology Inverter manuals

Lux Power Technology
Lux Power Technology LXP 3K Hybrid User manual

Lux Power Technology
Lux Power Technology SNA6000WPV User manual

Lux Power Technology
Lux Power Technology 12K User manual

Lux Power Technology
Lux Power Technology SNA3000 WPV User manual

Lux Power Technology
Lux Power Technology SNA5000WPV User manual

Lux Power Technology
Lux Power Technology LXP8K SPEC User manual

Lux Power Technology
Lux Power Technology LXP 3600ACS User manual