1-4
The GPD 315 leaves the factory with all parameters set for 2-Wire external reference control. Figure
1-5 must be used for all external connections.
To use the GPD 315 in a 3-Wire application, drive parameters
n001, n003,
and
n004
must be
reprogrammed, using the Digital Operator. Figure 1-6 must then be used for all external connections.
A. Main Circuit Input/Output
Complete wire interconnections according to Tables 1-1 and 1-2; observe the following:
• Use 600 V vinyl-sheathed wire (75°C copper) or equivalent. Wire size should be determined
considering voltage drop of leads.
• NEVER connect AC main power to output terminals T1 ( U ), T2 ( V ), and T3 ( W ).
• NEVER allow wire leads to contact metal surfaces. Short-circuit may result.
• NEVER connect power factor correction capacitors or noise filters to GPD 315 output.
• SIZE OF WIRE MUST BE SUITABLE FOR CLASS I CIRCUITS.
• Use only factory supplied installation instructions to install optional dynamic braking resistors.
Failure to do so may cause equipment damage or personal injury.
• Motor lead length should NOT EXCEED 164 feet (50 meters), and motor wiring should be run in
a separate conduit from the power wiring. If lead length must exceed this distance, reduce
carrier frequency and consult factory for proper installation procedures.
• Use UL listed closed loop connectors or CSA certified ring connectors sized for the selected wire
gauge. Install using the correct crimp tool recommended by the connector manufacturer.
1.4 ELECTRICAL INSTALLATION
Table 1-1. Wire and Terminal Screw Sizes for GPD 315
Drive Terminal Symbol Screw Max. Torque Wire
Module lb-ft Size AWG Type
MVA001-
MVA017; M3.5 0.7 18 to 14
MVB001-
MVB009
MVB015 L1, L2, L3, B1, B2, –, +1, +2 M4 1.0 12 to 10 600V
MVA025, T1, T2, T3,
MVA033; M5 1.8 10 to 8
MVB018
Control S1–S7, SC, FS, FR,
Circuit FC, RP, AM, AC, P1, P2, PC, M2 0.3 20 to 18 Shielded wire
(All) R+, R–, S+, S– with Class 1
MA, MB, MC M3 0.6 20 to 16 wiring
TERMINAL FUNCTION VOLTAGE / SIGNAL LEVEL
L1 (R)
L2 (S) Main circuit input power supply Three Phase, 230V Drive:
L3 (T) 200 / 208 / 220 / 230V at 50/60 Hz
T1 (U)
T2 (V) Main circuit output 0 - 200 / 208 / 220 / 230V
T3 (W)
B1 For connection of braking resistor or
B2 braking resistor unit (option)
+1 DC Reactor terminals
+2
– DC Bus terminals (+1 & –)
Ground terminal (100 ohms or less) – – – –
Table 1-2. Main Circuit Terminal Functions and Voltages
Main Circuit